The devices labeled 'L' in the illustration are _________. EL-0003 A. load lights indicating that the generator breaker is closed and the generator is supplying power to the main bus B. synchronizing lights. When the synchroscope is at the 12 o'clock position the lights are on at their brightest indicating that the generators are in phase C. emergency lighting for the switchboard to enable the meters to be read in case of power failure D. synchronizing lights. When the synchroscope is at the 12 o'clock position the lights are at their dimmest or out indicating the the generators are in phase

1 Answer

Answer :

Answer: D

Related questions

Description : The device labeled 'REG SW' in the illustration is used to ___________. EL-0003 A. shift from the automatic voltage regulator to the manual voltage regulator B. shift the governor control from manual to ... device 'REG ADJ' or device 'MAN ADJ' D. supply regulated control power to the switchboard

Last Answer : Answer: A

Description : In the illustration, if one of the devices labeled 'TURB' should fail the ___________. EL-0003 A. device labeled 'EXC' will drive the alternator B. device labeled 'BKR' for that ... -alternator D. emergency generator should automatically start and be placed on line to supply emergency load centers

Last Answer : Answer: B

Description : When two AC generators are being paralleled, the breaker should be closed with the synchroscope pointer rotating in the ____________. A. 'slow' direction, just before the 12 o'clock position B. 'fast' ... just before the 12 o'clock position D. 'slow' direction, just after the 12 o'clock position

Last Answer : Answer: C

Description : In the illustration, the component labeled 'EXC' is _______. EL-0003 A. a separate class II regulated DC generator for critical direct current loads B. a generator feeding the FLD ... to drive the governor for turbogenerator speed. D. the electronic driver for the switchboard metering circuits

Last Answer : Answer: B

Description : An AC generator panel is fitted with both synchronizing lamps and a synchroscope. When the synchroscope pointer reaches the noon position, one synchronizing light is bright and the other is dark. This ... sequence is incorrect C. the phase sequence is correct D. the generator breaker may be closed

Last Answer : Answer: B

Description : In the illustrated 450 VAC system, what should be provided between the bus and the device labeled 'F'? EL-0003 A. a potential transformer B. a current transformer C. an emergency disconnect device D. an audible alarm and indicating light

Last Answer : Answer: A

Description : As shown in the illustration, the function of the switch labeled 'PFSW' is to determine the ______________. EL-0003 A. bus frequency B. reactive volt amperes of the bus C. frequency of either generator D. power factor of either generator

Last Answer : Answer: D

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving fast in the clockwise direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... at any pointer position D. the same as the bus frequency but out of phase with it

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving in the fast direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... the same as the bus frequency and the circuit breaker may be closed at any pointer position

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer is revolving in the slow direction. This indicates that the frequency of the incoming machine is _____________. A. higher than ... same as the bus frequency, and the circuit breaker may be closed at any pointer position

Last Answer : Answer: B

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0° prior to closing the circuit breaker. This indicates ___________. A. the frequency of ... be closed after breaker has been reset D. there is an existing cross current between generators

Last Answer : Answer: A

Description : The purpose of the automatic bus transfer shown in the illustration is to ___________. EL-0014 A. stepdown voltage to the lighting distribution panel B. provide emergency power to ... emergency switchboard from the main switchboard D. provide overcurrent protection to the lighting distribution panel

Last Answer : Answer: B

Description : As shown in the illustration, which of the listed actions of the synchroscope pointer is occurring? EL-0002 A. Revolving slowly in the slow direction. B. Revolving rapidly in the slow direction. C. ... stationary at the 12 o'clock position since the leading edges of the A phases are in phase.

Last Answer : Answer: C

Description : In the illustration, the contacts between terminals 26 and 27 should be closed when _________. EL-0046 A. using one generator in isochronous mode only B. using two or more generators in ... through varying loads in parallel or single operation D. the circuit breaker is closed for that generator

Last Answer : Answer: C

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : You are paralleling two alternators. The synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates that the ____________. A. alternator ... be closed C. incoming alternator is running too slowly D. synchroscope is defective or broken

Last Answer : Answer: B

Description : When paralleling two alternators the synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates the ____________. A. alternator voltages ... alternator is in phase with the bus voltage D. synchroscope pointer is defective or broken

Last Answer : Answer: C

Description : Which of the synchroscope illustrations depicts the appropriate direction of rotation and position for closing the circuit breaker when paralleling AC generators? EL-0053 A. A B. B C. C D. D

Last Answer : Answer: D

Description : Undervoltage trips are frequently installed on switchboard circuit breakers to trip ____________. A. out generators in the event of severe arcing or sparking B. out generators when there is reversal of power ... , but continues to run D. out generators when there is low voltage in the main circuit

Last Answer : Answer: D

Description : Attempting to parallel an AC generator which is out of phase with the bus will result in which of the following problems? A. The breaker should trip. B. The KVA will decrease. C. The synchronizing lamps will burn out. D. The power factor will be unitized.

Last Answer : Answer: A

Description : Before servicing the device indicated as 'A' in panels #1 and #3 of the illustration, the device labeled 'CT' must __________. EL-0003 A. have the disconnected leads taped to prevent ... D. have one lead grounded to discharge static electricity for the prevention of damage to electronic components

Last Answer : Answer: C

Description : The source of emergency lighting and power at loss of normal ship's power on a cargo vessel should be obtained from the ______________. A. emergency generator supply to the emergency ... switchboard C. battery supply to the main switchboard D. turbogenerator supply to the emergency switchboard

Last Answer : Answer: A

Description : Which of the listed sections of an emergency switchboard is used to supply power for alarm signals under emergency conditions? A. The generator and bus transfer section B. The 450 volt, 60 cycle, 3 phase bus C. The 120 volt, 3 phase, 60 cycle bus D. The 24 volt DC bus

Last Answer : Answer: D

Description : In the lighting distribution circuit shown in the illustration, if all switches are closed and fuse 'F2' were to open, all lights on branches ____________. EL-0013 A. '1', '2', and '3' would go out B. '1' ... and '3' would burn dimly D. '1' and '3' would go out, while branch '2' would remain lit

Last Answer : Answer: D

Description : When paralleling two AC generators, the synchroscope selector switch and frequency meter switch should be set up to sense the frequency of the _____________. A. bus B. generator on the line C. oncoming generator D. bus transfer relay

Last Answer : Answer: C

Description : A diesel driven emergency generator is prevented from being paralleled with the ship's service generators by __________. A. an electrical interlock system B. an automatic paralleling trip switch C. the synchronizing oscilloscope D. the reverse current relay

Last Answer : Answer: A

Description : Which of the following statements is correct concerning the motor performance curves and data table shown in the illustration? EL-0006 A. The motor RPM at full load is 1737 RPM. B. The motor draws 12.62 kw ... If the motor was developing 10 HP its power factor would be 0.92. D. All of the above.

Last Answer : Answer: D

Description : After a black out the emergency generator comes on; On restoring the main supply we are closing the circuit breaker of the main generator without bothering about synchronizing. How is this possible?

Last Answer : There is a power link connection breaker between the main generator and the emergency generator. During black out, this breaker trips. The emergency generator starts and its breaker closes and feeds only ... , there is no paralleling between main and emergency generator. Ask E/O for more details.

Description : The 24 volt DC bus on the emergency switchboard is used to supply power to the _____________. A. general alarm system B. gyrocompass power failure alarm system C. smoke detection system D. all of the above

Last Answer : Answer: D

Description : A three-phase alternator is operating at 450 volts with the switchboard ammeter indicating 300 amps. The kw meter currently indicates 163.6 KW, with a power factor of 0.7. If the power factor increases to 0.8, the KW meter would then read ____________. A. 181.4 KW B. 186.8 KW C. 194.2 KW D. 201.4 KW

Last Answer : Answer: B

Description : When paralleling two alternators, the synchronizing lamps remain lit as the synchroscope pointer approaches the 0°. This indicates the _____________. A. incoming alternator is running too fast B. alternator ... apart C. synchroscope is defective or broken D. alternator power factors are in phase

Last Answer : Answer: C

Description : Before any work on electrical or electronic equipment is performed, which of the following precautions should be carried out? A. De-energize the applicable switchboard bus. B. Bypass the interlocks. C. ... supply circuit breaker in the open position. D. Station a man at the circuit supply switch.

Last Answer : Answer: C

Description : The electrical energy necessary to power a sound-powered telephone's small vibrating bell is obtained from _________. A. the emergency batteries for the general alarm B. each station's hand-cranked generator C. the emergency switchboard D. normal 115 volt DC supplies

Last Answer : Answer: B

Description : In the illustration if BRANCH NO. 1 is a lighting circuit for crew's berthing, Federal Regulations (46 CFR) require the maximum fuse rating for that branch to be _________. EL-0013 A. 80% of the connected load B. 15 amps C. 20 amps D. 30 amps

Last Answer : Answer: C

Description : In the illustration if BRANCH NO. 1 is a lighting circuit for crew's berthing, 46 CFR requires the maximum fuse rating for that branch to be _________. EL-0013 A. 15 amps B. 80% of the connected load C. 20 amps D. 30 amps

Last Answer : Answer: C

Description : The diagram shown in the illustration represents a _________. EL-0058 A. dual speed, 2-winding motor controller B. navigation running light circuit C. single phase, 2-motor selectable starter D. common fluorescent lighting circuit

Last Answer : Answer: B

Description : Which of the following statements is true concerning the motor controller diagram shown in the illustration? EL-0023 A. Terminal 'T2' is hot only on high speed. B. Both indicating lights will be lit on ... high speed operation only. D. 'L2' is always connected to 'T2' whenever the motor is running.

Last Answer : Answer: D

Description : A shore power circuit breaker should be closed only _____________. A. when the ship's generators have been directly paralleled to those on shore B. in a shipyard C. if a quick disconnect coupling is used D. when the ship's generators have been removed from the bus

Last Answer : Answer: D

Description : Automatic voltage regulators provided on switchboards function to _____________. A. regulate the AC load on the generator B. protect the switchboard from high voltage C. govern prime mover speed to control voltage D. vary the field excitation to the generators

Last Answer : Answer: D

Description : Considering the function of the circuit shown in the illustration, what is the purpose of supplying the thrust lever potentiometers with both (+) and (-) 15 volts? EL-0095 A. To select which ... alternate voltage supply if the other fails. D. So as to automatically select the position of Relay #

Last Answer : Answer: B

Description : A faulty 'function generator' shown in the illustration may prevent _____________. EL-0095 A. proper pitch control from both the 'bridge' and 'engine room thrust levers' B. the 'split potentiometer ... control pitch C. the pitch meter from indicating accurately D. relays #2 and/or #3 from energizing

Last Answer : Answer: A

Description : Upon failure of the normal power supply, the emergency generator is placed on the line by the _____________. A. main bus tie feeder B. automatic bus transfer device C. line connection feeder D. power failure alarm bus

Last Answer : Answer: B

Description : In an emergency, the fastest way to interrupt power and stop the winch shown in the illustration is for the ____________. EL-0102 A. mate to open the disconnect switch at 'L1' and 'L2' B. ... watch engineer to open the winch circuit breaker D. electrician to open the test link at the controller

Last Answer : Answer: B

Description : When paralleling two alternators using three synchronizing lamps, the flickering of all three lamps becomes progressively slower and slower. This means the ______________. A. frequency of the incoming ... the bus D. terminal voltage of the incoming alternator is approaching that of the bus

Last Answer : Answer: A

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D