Will main generator differential relay pick up for generator earth faults? 

1 Answer

Answer :

No earth fault current limited to 5A, while differential setting is 10%. 

Related questions

Description : The winch shown in the illustration operates in any of the positions with the master switch in the 'lower' direction, but will not 'hoist' in any of the master switch hoist positions. Which of the listed faults ... '2M' in the power circuit may be badly corroded. D. Series relay 'FR' may be open.

Last Answer : Answer: A

Description : Large internal faults are protected by (a) merz price percentage differential protection (b) mho and ohm relays (c) horn gaps and temperature relays (d) earth fault and positive sequence relays

Last Answer : (a) merz price percentage differential protection

Description : A reverse-current relay will prevent AC generator motorization by ____________. A. automatically redirecting the load B. automatically speeding up the prime mover C. tripping the panel board main switch D. tripping the generator circuit breaker

Last Answer : Answer: D

Description : The purpose of the reverse power relay, provided on a ship's service alternator panel, is to trip the circuit in the event of ______________. A. main circuit overload B. high power transfer C. generator overspeeding D. alternator motorization

Last Answer : Answer: D

Description : Regarding an AC generator connected to the main electrical bus; as the electric load and power factor vary, a corresponding change is reflected in the generator armature reaction. These changes in ... . governor speed droop setting B. voltage regulator C. balance coil D. phase-balance relay

Last Answer : Answer: B

Description : How generator earth fault relay works? 

Last Answer : 100% earth fault relay works on the principle involving monitoring of neutral side and line side components of 3rd harmonic voltages produced by generator in service. Since the machine is grounded with ... be detected by VL3 neutral displacement module, which is tuned to find frequency.   

Description : Mention any two applications of differential relay.

Last Answer : Protection of generator & generator transformer unit; protection of large motors and busbars .

Description : Inverse definite minimum time lag relay is also called ___________ (A) pilot relay. (B) differential relay. (C) over current relay. (D) directional overcurrent relay.

Last Answer : Ans: B Inverse definite minimum time lag relay characteristic is inverse but minimum time is fixed. The operating time is inversely proportional to the magnitude of actuating quantity.

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : Why inter-turn protection is provided along with differential protection in generator?

Last Answer : Inter-turn protects two separate windings from the fault of the generator.  

Description : Why generator differential provided? 

Last Answer : For generator phase to phase faults and 3 phase faults. 

Description : What are the main types of stator winding faults?

Last Answer : Fault between phase and ground; fault between phases and inter-turn fault involving turns of the same phase winding.

Description : When paralleling two AC generators, the synchroscope selector switch and frequency meter switch should be set up to sense the frequency of the _____________. A. bus B. generator on the line C. oncoming generator D. bus transfer relay

Last Answer : Answer: C

Description : Will rotor earth fault relay operate for earth fault in main exciter winding or RCU Diode Bridge also? 

Last Answer : Yes. 

Description : Diesel generators #1 and #2 are operating in parallel at near full load capacity. Diesel generator #1 suddenly trips out mechanically due to low lube oil pressure. The reverse power relay functions ... all nonvital circuits. D. Secure alarms, reset reverse power relay, and restart #1 engine.

Last Answer : Answer: C

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : In order to safely carry out repairs to a generator circuit breaker, it must be isolated from the bus. This is accomplished by opening the _____________. A. reverse power relay B. bus disconnect link C. generator bus fuse connections D. power directional relay

Last Answer : Answer: B

Description : A diesel driven emergency generator is prevented from being paralleled with the ship's service generators by __________. A. an electrical interlock system B. an automatic paralleling trip switch C. the synchronizing oscilloscope D. the reverse current relay

Last Answer : Answer: A

Description : In the illustration, if one of the devices labeled 'TURB' should fail the ___________. EL-0003 A. device labeled 'EXC' will drive the alternator B. device labeled 'BKR' for that ... -alternator D. emergency generator should automatically start and be placed on line to supply emergency load centers

Last Answer : Answer: B

Description : The timer element of a reverse power relay cannot be energized unless _____________. A. the power flow is the same as the tripping direction B. the power flow is the opposite to the tripping direction C. the movement of the disk is damped by a permanent magnet D. one generator is motorized

Last Answer : Answer: A

Description : As shown in the illustration, when the 'speed control' system is in 'SPLIT' _______________. EL-0096 A. Relays #1, #5 and #8 are not used B. the 'slew rated controller' is grounded through Relay ... E/P converters' are bypassed and air is fed directly to the governors via the 'load sharing valve'

Last Answer : Answer: C

Description : The 'function generator' of the control circuit illustrated _______________. EL-0095 A. can be programmed to produce a non-linear output for a linear input depending on operating conditions B. is used for ... which or how many engines are needed for a required vessel speed D. all of the above

Last Answer : Answer: A

Description : The timer element of a reverse power relay cannot be energized unless _____________. A. one generator is fully motorized B. the movement of the disk is damped by a permanent magnet C. the power flow is the same as the tripping direction D. the power flow is the opposite to the tripping direction

Last Answer : Answer: C

Description : A generator is prevented from becoming motorized by the use of a/an _____________. A. overspeed trip B. reverse power relay C. back pressure trip D. governor controls

Last Answer : Answer: B

Description : A constant output voltage from an AC generator is maintained by the _____________. A. prime mover governor B. exciter generator C. voltage regulator D. reverse power relay

Last Answer : Answer: C

Description : A differential relay measures the vector difference between (a) two currents (b) two voltages (c) two or more similar electrical quantities (d) none of the above

Last Answer : (c) two or more similar electrical quantities

Description : Describe the operation of current differential relay with neat sketch.

Last Answer : Operation of Current Differential Relay: Figure shows an arrangement of an overcurrent relay connected to operate as a differential relay for alternator protection under fault conditon. ... current flows through relay coil, causing relay to operate for protection of alternator winding.

Description : A series resistance is added to the over-current relay in a bus bar differential protection scheme which: a. Helps to develop some voltage across it which otherwise should appear across the relay and is ... the effects of CT saturation and lowers the pickup value of the relay d. All of the above 

Last Answer : A series resistance is added to the over-current relay in a bus bar differential protection scheme which: a. Helps to develop some voltage across it which otherwise should appear across the relay and is ... the effects of CT saturation and lowers the pickup value of the relay d. All of the above 

Description : In a biased differential relay, the bias is defined as the ratio of  A) Number of turns of restraining coil and operating coil B) Operating coil current and restraining coil current C) Faulteurrent and operating coil current D) Fault current and restraining coil current

Last Answer : In a biased differential relay, the bias is defined as the ratio of Number of turns of restraining coil and operating coil 

Description : The purpose of the restraining coil in a biased differential relay is  (A) To reduce CT saturation during fault.  (B) To increase the sensitivity of the relay.  (C) To match the transformation ratio.  (D) To limit the spill current through the relay during heavy external fault.

Last Answer : d

Last Answer : A differential relay measures the vector difference between two or more similar electrical quantities.

Description : Which of the listed faults cannot be eliminated, EXCEPT by turning or grinding a commutator with a rigidly supported tool? A. Sparking brushes B. Eccentricity C. High mica D. Blackened commutator

Last Answer : Answer: B

Description : Sparking of D.C. motor brushes can be caused by __________. A. an open commutating winding B. many mechanical, electrical or operating faults C. an open interpole D. all of the above

Last Answer : Answer: B

Description : Which of the following represents a characteristic of an ungrounded electrical distribution system? A. Accidental contact between one line and ground does not cause an outage. B. Double ground faults on ... unnecessary. D. Accidental contact between one line and ground will always cause an outage.

Last Answer : Answer: A

Description : How Transformer Protection provided for internal faults?

Last Answer : 1.Bucholz Relay (1st Stage Alarm and 2nd Stage Trip) 2.Sudden Pressure Relay (1st Stage Alarm and 2nd Stage Trip) 3.Pressure Relief Valve (1st Stage Alarm and 2nd Stage Trip) 4.Pressure Switch ... 8.Gas Temperature Indicator (Alarm) 9.Silicon Breather (Passive - no alarm) 10.Smoke Detector (Alarm)

Description : What are the tests done to minimize internal faults?

Last Answer : 1.Dissolved Gas Analysis (DGA): Faults due to arcing, high current breakdown of oil, localized sparking, partial discharge of oil, localized overheating or hot spots, etc. causes ... Over current relays with under voltage blocking 6.Zero sequence protection. 7.Negative phase sequence protection

Description : What are the different types of faults in a transformer?

Last Answer : The internal faults include phase faults, ground faults, inter-turn faults, tap-changer failure, and leakage oil from tank. The external faults include system phase faults, system ground faults, over loads and over fluxing.

Description : State the various types of unsymmetrical faults.

Last Answer : Line to ground ,line to line and double line to ground faults

Description : State the different types of faults.

Last Answer : Symmetrical faults and unsymmetrical faults and open conductor faults.

Description : What are the causes of bus zone faults?

Last Answer : Failure of support insulator resulting in earth fault Flashover across support insulator during over voltage Heavily polluted insulator causing flashover Earthquake, mechanical damage etc.

Description : What are faults associated with an alternator?

Last Answer : (a) External fault or through fault (b) Internal fault 1, Short circuit in transformer winding and connection 2, Incipient or slow developing faults

Description : What are the various faults that would affect an alternator?

Last Answer : (a) Stator faults 1, Phase to phase faults 2, Phase to earth faults 3, Inter turn faults (b) 1, Earth faults 2, Fault between turns 3, Loss of excitation due to fuel failure (c) 1, Over ... rise, resulting in shattering of the turbine low pressure casing (d) 1, Fault on lines 2, Fault on busbars

Description : What are the various faults to which a turbo alternator is likely to be subjected?

Last Answer : Failure of steam supply; failure of speed; overcurrent; over voltage; unbalanced loading; stator winding fault .

Description : How are faults are classified?

Last Answer : The faults are classified as shunt and series faults. The shunt faults are due to short circuits in conductors and the series faults are due to oped conductors.

Description : The operating torque of the upper induction disc-type element, or timer element, of an AC reverse power relay is obtained from ____________. A. the main bus B. a separate battery source C. line voltage D. electromagnets

Last Answer : Answer: D

Description : The timer element found in a reverse power relay obtains its operating torque via _____________. A. line voltage B. the main bus C. electromagnets D. a separate battery source

Last Answer : Answer: C

Description : The part of the shipboard electrical system used to control the distribution of power to the branch circuits, is the _____________. A. bridge control panel B. disconnect links C. governor relay box D. main switchboard

Last Answer : Answer: D

Description : Which of the following statements represents the main difference between a relay and a contactor? A. Contactors control current and relays control voltage. B. A relay is series connected and a contactor ... loads than relays. D. Contactors are made from silver and relays are made from copper.

Last Answer : Answer: C