The timer element of a reverse power relay cannot be energized unless _____________. A. the power flow is the same as the tripping direction B. the power flow is the opposite to the tripping direction C. the movement of the disk is damped by a permanent magnet D. one generator is motorized

1 Answer

Answer :

Answer: A

Related questions

Description : The timer element of a reverse power relay cannot be energized unless _____________. A. one generator is fully motorized B. the movement of the disk is damped by a permanent magnet C. the power flow is the same as the tripping direction D. the power flow is the opposite to the tripping direction

Last Answer : Answer: C

Description : A generator is prevented from becoming motorized by the use of a/an _____________. A. overspeed trip B. reverse power relay C. back pressure trip D. governor controls

Last Answer : Answer: B

Description : The timer element found in a reverse power relay obtains its operating torque via _____________. A. line voltage B. the main bus C. electromagnets D. a separate battery source

Last Answer : Answer: C

Description : A reverse-current relay will prevent AC generator motorization by ____________. A. automatically redirecting the load B. automatically speeding up the prime mover C. tripping the panel board main switch D. tripping the generator circuit breaker

Last Answer : Answer: D

Description : The operating torque of the upper induction disc-type element, or timer element, of an AC reverse power relay is obtained from ____________. A. the main bus B. a separate battery source C. line voltage D. electromagnets

Last Answer : Answer: D

Description : In order to safely carry out repairs to a generator circuit breaker, it must be isolated from the bus. This is accomplished by opening the _____________. A. reverse power relay B. bus disconnect link C. generator bus fuse connections D. power directional relay

Last Answer : Answer: B

Description : A constant output voltage from an AC generator is maintained by the _____________. A. prime mover governor B. exciter generator C. voltage regulator D. reverse power relay

Last Answer : Answer: C

Description : An equalizing connection between two compound-wound DC generators when paralleled, serves to _____________. A. reverse the polarity of the incoming generator as the series field weakens B. automatically ... the series field of the incoming generator D. parallel the series fields of the generators

Last Answer : Answer: D

Description : The amount of voltage induced in the windings of an AC generator depends mainly on _____________. A. the number of field poles energized B. the speed at which the stator windings rotate through the magnetic field C. the strength of the magnetic field D. all of the above

Last Answer : Answer: C

Description : In an AC synchronous motor electric propulsion plant, propeller speed is controlled by varying the _____________. A. prime mover speed B. electric coupling field strength C. number of energized main motor poles D. propulsion generator field strength

Last Answer : Answer: A

Description : Equal power factors on paralleled AC generators are maintained by an automatic _____________. A. voltage regulator B. reverse power relay C. reverse current relay D. governor control switch

Last Answer : Answer: A

Description : Diesel generators #1 and #2 are operating in parallel at near full load capacity. Diesel generator #1 suddenly trips out mechanically due to low lube oil pressure. The reverse power relay functions ... all nonvital circuits. D. Secure alarms, reset reverse power relay, and restart #1 engine.

Last Answer : Answer: C

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : The purpose of the reverse power relay, provided on a ship's service alternator panel, is to trip the circuit in the event of ______________. A. main circuit overload B. high power transfer C. generator overspeeding D. alternator motorization

Last Answer : Answer: D

Description : In the illustration, if one of the devices labeled 'TURB' should fail the ___________. EL-0003 A. device labeled 'EXC' will drive the alternator B. device labeled 'BKR' for that ... -alternator D. emergency generator should automatically start and be placed on line to supply emergency load centers

Last Answer : Answer: B

Description : Which of the following devices are protected from being motorized by a reversepower relay? A. Alternators B. Wave guides C. Exciters D. Amplidynes

Last Answer : Answer: A

Description : Coast Guard Regulations (46 CFR) require that each alternating current generator arranged for parallel operation shall be provided with _____________. A. more than one means of excitation B. individual circuit fuses C. a high back-pressure trip D. a reverse-power trip

Last Answer : Answer: D

Description : In an AC generator, direct current from a separate source is passed through the windings of the rotor _____________. A. by means of slip rings and brushes B. by means of a commutator C. by means of rotating bar magnet D. to minimize the danger of arc over

Last Answer : Answer: A

Description : A diesel driven emergency generator is prevented from being paralleled with the ship's service generators by __________. A. an electrical interlock system B. an automatic paralleling trip switch C. the synchronizing oscilloscope D. the reverse current relay

Last Answer : Answer: A

Description : As shown in the illustration, once the "LV" relay is energized for operation, what contacts must remain closed to maintain the "LV" relay energized when the control lever is moved away from the "off" or "stop" ... . B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : As shown in the illustration, what is responsible for maintaining the "LV" relay energized when the master switch handle is moved away from the "off" position? EL-0102 A. "DBa" contact. B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : When troubleshooting a motor controller, all indications are that a relay coil should be energized. If there were no magnetic pull, with rated voltage measured across the coil, the most probable cause ... open C. auxiliary contact in series with the coil is defective D. relay armature is stuck

Last Answer : Answer: A

Description : If three AC generators are operating in parallel, and one of them were to 'pull out' of synchronism with the other two generators, the ____________. A. normally operating AC generators will ... AC generators will overspeed and unload D. AC generator pulling out of synchronism will become motorized

Last Answer : Answer: B

Description : The arc resulting from the tripping of a circuit breaker is prevented from damaging the contacts by _____________. A. designing the contacts to open slowly B. directing the arc into an ... an inverse timed thermal trip for short circuit currents D. instantaneous magnetic trip for overload currents

Last Answer : Answer: B

Description : When paralleling two AC generators, the synchroscope selector switch and frequency meter switch should be set up to sense the frequency of the _____________. A. bus B. generator on the line C. oncoming generator D. bus transfer relay

Last Answer : Answer: C

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : If you reverse both the field and the armature connections to a DC propulsion motor, _____________. A. the direction of motor rotation will change B. the brushes will become overheated C. a magnetic lock will occur in the motor D. the direction of motor rotation will remain the same

Last Answer : Answer: D

Description : The direction of propeller shaft rotation in a turbo-electric synchronous propulsion drive motor is changed by reversing the _____________. A. polarity of the propulsion motor B. polarity of the propulsion generator C. phase sequence of power to the motor D. phase sequence of power to the generator

Last Answer : Answer: C

Description : If the connections for the field and the armature on a DC motor are reversed, _____________. A. the motor will run as a generator B. the motor will not run C. the direction of rotation will be the same D. the direction of rotation will be reversed

Last Answer : Answer: C

Description : A short circuit in the armature of a DC motor will cause the motor to _____________. A. run fast B. hum when energized C. spark at the brushes D. fail to start

Last Answer : Answer: C

Description : In addition to testing the calibration of a circuit breaker, maintenance should include all of the following EXCEPT ______________. A. changing out of magnetic elements and thermal heaters yearly B. ... for loose or missing parts D. making sure foreign matter does not block tripping element

Last Answer : Answer: A

Description : If coils 'R1-R2-R3' at the receiver of figure 'B' shown in the illustration turned opposite of those in the transmitter, what corrective action should be taken to have both turn in the same direction? EL-0092 A ... is needed. C. Interchange leads 'R1' and 'R3'. D. Interchange leads 'R2' and 'R3'.

Last Answer : Answer: C

Description : Reversing any two of the three rotor leads on a wound-rotor induction motor will _____________. A. increase motor performance B. decrease motor performance C. reverse the motor rotation D. have no effect on the direction of rotation or motor performance

Last Answer : Answer: D

Description : For a traction transformer circuit breaker state: 1) Rated current and rupturing capacity 2) Any two tests it should be capable of withstanding 3) Overall tripping time and relay time.

Last Answer : Ans: 1) Rated current --- 750 A and Rupturing capacity --- 500 MVA  2) Any two tests it should be capable of withstanding --- Breaking test , Reclosing test , Endurance test ( any two )  3) Overall tripping time --- 0.14 sec and Relay time --- 0.04 sec 

Description : The reactive power drawn by a motor from an AC generator is the power which is _____________. A. used to establish the magnetic field of the motor B. lost in overcoming friction in the ... by current flow through the windings D. transmitted directly through the rotor shaft to perform useful work

Last Answer : Answer: A

Description : Moving the rheostat handle shown in the illustration, that is used to control a DC generator, towards the 'raise' direction will increase the _____________. EL-0030 A. field resistance B. armature resistance C. armature speed D. line voltage

Last Answer : Answer: D

Description : Discharge switches are often located on hand-driven meggers. The purpose of these switches is to discharge capacitive charges stored in the _____________. A. megger hand generator B. megger movement coils C. tested equipment while conducting test D. tested equipment after testing

Last Answer : Answer: D

Description : An alternator operating in parallel begins to vibrate severely and eventually trips out on the reverse power relay. The cause of the vibration was a result of ______________________. A. the ... C. the alternator was operating out of synchronism D. flashover at the alternator collector rings

Last Answer : Answer: C

Description : Why is it a good practice to have the frequency of the incoming alternator adjusted slightly higher than that of the loaded alternator when paralleling two alternators? A. This allows the oncoming machine to ... line. C. The reverse power relay is prevented from activating. D. All of the above.

Last Answer : Answer: D

Description : What is reverse power relay?

Last Answer : A:Reverse Power flow relay are used in generating stations's protection. A generating stations is supposed to fed power to the grid and in case generating units are off,there is no generation in the ... power from grid. To stop the flow of power from grid to generator we use reverse power relay.

Description : What is reverse power relay?

Last Answer : Reverse Power flow relay are used to stop the flow of power from grid to station generator when the generating units are off.

Description : Why low forward power relay used in parallel to reverse power relay?

Last Answer : A small steam leak through CIES valves will keep the machine floating on to grid at low power. So even if turbine trip, relay picks up, there is no trip actually. So low forward power relay (0.54%) used to detect the condition. 

Description : What is reverse power relay?

Last Answer : Reverse Power flow relay are used in generating stations' protection.  A generating station is supposed to feed power to the grid and in case generating units are off, there is no generation in the ... power from grid. To stop the flow of power from grid to generator we use reverse power relay.

Description : Magnet chatter or 'pumping' occurring in a magnetic contactor can be caused by ______________. A. dirt or grease on pole faces B. mechanical interference in the contacts C. chattering contacts on the control relay D. magnetic lock out of the contacts

Last Answer : Answer: C

Description : (2) experience collision less frequently Explanation: When an electric field is applied, both the valence electrons and the free electrons move in the same direction. The hole direction is opposite to that ... to free electrons. This means mobility is also less for a hole compared to free electron.

Last Answer : Carbon dioxide is called a greenhouse gas because - (1) its concentration remains always higher than other gases (2) it is used in photosynthesis (3) it absorbs infrared radiation (4) it emits visible radiation