The illustrated motor fails to start and gives a loud hum when the start button is depressed, your first action should be to __________. EL-0007 A. disassemble the motor to fix the centrifical switch so the start windings will be energized B. push the stop button to deenergize the 'M' coil C. reset the thermal overload D. hold the 'M' contactor closed by hand while wearing electrical safety gloves to get motor started

1 Answer

Answer :

Answer: B

Related questions

Description : If the illustrated motor fails to start and gives a loud hum when the start button is pushed, the problem is ________. EL-0007 A. one of the phases to the motor is not energized because of ... electrical distribution system D. 'OL1' is open because of 'T1' overload causing the motor to single phase

Last Answer : Answer: A

Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown

Last Answer : Answer: B

Description : If the motor fails to start and a voltmeter reading between 1 and 6, as illustrated, indicates line voltage, your next step should be to ________. EL-0007 A. replace fuse '10a' B. replace or repair contact 'Ma' C. reset and determine the cause of the overload D. check line voltage between L1 and L3

Last Answer : Answer: C

Description : The motor starts when the start button in the illustration is pushed, but stops when the button is released the trouble is _________. EL-0007 A. the incorrect thermal overload coil B. a faulty 'M' coil C. a dirty contact on the Disc.Sw. at 'L3' D. a faulty holding relay contact

Last Answer : Answer: D

Description : If the circuit shown in the illustration were energized and operating properly, which of the devices listed would be open? EL-0007 A. The stop push-button B. The start push-button C. Contact 'Ma' D. Contact 'OL1'

Last Answer : Answer: B

Description : To stop the electric motor shown in the illustration, the stop button is depressed, causing ____________. EL-0012 A. coil 'MS' to become de-energized B. contacts 'CR1' and 'MR4' to open C. contacts 'MR1', 'MR2', and 'MR3' to open D. contacts 'MS1', 'MS2', and 'MS3' to open

Last Answer : Answer: C

Description : When the motor shown in the illustration is running and the stop button is pushed, which of the following statements will hold true? EL-0010 A. Coil 'M' will now be energized. B. Coil 'CR' will now be energized. C. Contact 'M' will close as contact 'CR' opens. D. Contacts 'M' and 'CR' will open.

Last Answer : Answer: D

Description : As shown in the illustration, which listed action will occur first when push button 'Q' is depressed? EL-0017 A. Contacts 'H-1', 'H-2' and 'H-3' close. B. Contact 'H-4' closes. C. Operating coil 'C' energizes. D. Switch 'R' opens.

Last Answer : Answer: C

Description : Refering to the illustrated schematic diagram, which of the following statements is true when the motor is running in the forward direction? EL-0011 A. Normally-open contacts '4-5' are closed. B. Current ... switch. C. Normally-closed contacts 'R' are open. D. The blowout coils must be closed.

Last Answer : Answer: B

Description : As shown in the illustration, 'S' is the __________. EL-0017 A. safety switch B. overload trip C. start button D. stop button

Last Answer : Answer: D

Description : As shown in the illustration, the symbol is used in electrical drawings to designate a ____________. EL-0026 A. limit switch with one set of normally open contacts B. maintaining type ... type push button with a mechanical interlock D. normally closed contact held open mechanically by an interlock

Last Answer : Answer: C

Description : A three-phase, induction-type motor experiences an open in one phase. Which of the listed automatic protective devices will prevent the machine from being damaged? A. Overspeed trip B. Thermal overload relay C. Three-pole safety switch D. Magnetic blowout coil

Last Answer : Answer: B

Description : In the illustration if the compressor fails to start but the condenser fan motor is running the problem is _______. EL-0042 A. no power between L1 and L2 B. the yellow wire is open at the freezer temperature control switch C. the overload is open D. the blue wire from the defrost heater is open

Last Answer : Answer: C

Description : In the illustration if the compressor fails to start but the condenser fan motor is running the problem is _______. EL-0043 A. no power between L1 and L2 B. the yellow wire is open at the freezer temperature control switch C. the overload is open D. the blue wire from the defrost heater is open

Last Answer : Answer: C

Description : If a magnetic controller contactor fails to pick up when the coil voltage is applied to the contactor coil, the cause may be _____________. A. overload B. misalignment of the affected contactor contacts C. low spring pressure D. an open contactor coil

Last Answer : Answer: D

Description : In the illustrated schematic diagram, which of the listed devices prevents the forward and reversing coils from being energized simultaneously? EL-0011 A. An 'either-or' interlock B. A mechanical interlock C. Blowout coils D. A stop button

Last Answer : Answer: A

Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button

Last Answer : Answer: D

Description : In the illustrated test, if the lamp fails to light on any of the three windings then _________. EL-0027 A. all three windings are grounded and the motor should be sent out for repair B. ... the motor controller and the controller should be checked D. the test should be redone at a higher voltage

Last Answer : Answer: C

Description : If fuse 'F-1' in the illustrated schematic diagram opens, ____________. EL-0017 A. the motor will run slowly B. 'A-1' and 'A-2' will open C. the motor will not start D. the start button will jam in the closed position

Last Answer : Answer: C

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : A single-phase induction motor fails to start. The rotor is spun rapidly with the line switch closed. Having started by this method it is noted that the motor fluctuates between a very slow ... lies in the ______ A. starting winding B. centrifugal mechanism C. centrifugal switch D. running winding

Last Answer : Answer: D

Description : As shown in the illustration, what is responsible for maintaining the "LV" relay energized when the master switch handle is moved away from the "off" position? EL-0102 A. "DBa" contact. B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : As part of a routine maintenance program for deck machinery, you should ___________. A. inspect electrical wiring and pushbutton switches for evidence of corrosion or burned insulation B. disassemble ... covers and ventilate as weather permits D. Check drum switch contact pressure every three months

Last Answer : Answer: A

Description : A short circuit in the armature of a DC motor will cause the motor to _____________. A. run fast B. hum when energized C. spark at the brushes D. fail to start

Last Answer : Answer: C

Description : The winch shown in the illustration will not operate in any speed in the lowering direction and at an abnormal speed in 'first point hoist'. The possible cause is that _______________. EL-0102 A. ... '1M' in the power circuit are badly corroded D. master switch contacts 'MS6' have weak springs

Last Answer : Answer: B

Description : The winch shown in the illustration operates in any of the positions with the master switch in the 'lower' direction, but will not 'hoist' in any of the master switch hoist positions. Which of the listed faults ... '2M' in the power circuit may be badly corroded. D. Series relay 'FR' may be open.

Last Answer : Answer: A

Description : The 'safe switch' of the winch controller shown in the illustration is operated _______________. EL-0102 A. through the master switch handle B. when heater circuit current is high C. by contactor coil 'FR' D. manually by the winch operator

Last Answer : Answer: D

Description : If the contacts of a motor starter or controller fail to drop out when the 'stop' button is depressed the ____________. A. contacts are carrying excessive current B. contacts have become welded together C. shading coil is broken D. shading coil is loose

Last Answer : Answer: B

Description : In the illustrated device, the part labeled '1A' _________. EL-0001 A. are start and run windings for a single phase shaded pole induction motor B. is the stator for a polyphase induction ... armature for a squirrel cage rotor motor D. are direct current shunt field windings for a universal motor

Last Answer : Answer: B

Description : The 'reset' contacts of the master switch shown in the illustration provides the winch controller with ___________. EL-0102 A. low voltage release B. overload protection C. low voltage protection D. high power factor correction

Last Answer : Answer: C

Description : During its operation, loud buzzing and resultant welding of contacts of a magnetic relay may be caused by __________. A. overheating of the contactor coil B. low voltage on the operating coil C. low insulation resistance to ground D. lubrication of the contact bearing points

Last Answer : Answer: B

Description : In the illustrated ground detection system with a ground on phase A, if the switch is opened __________. EL-0009 A. lamp A will dim or go out depending on the severity of the ground B. all three ... lamp A will be brighter D. lamp A will start flickering if the ground is in an AC induction motor

Last Answer : Answer: B

Description : As shown in the illustration, once the "LV" relay is energized for operation, what contacts must remain closed to maintain the "LV" relay energized when the control lever is moved away from the "off" or "stop" ... . B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : If overloading a DC machine becomes necessary in an emergency, you should ____________. A. cool the machine with portable blowers and fans B. hold thermal overload relays open with blocks of ... the windings for cooling D. increase the residual magnetism value of windings to reduce eddy currents

Last Answer : Answer: A

Description : Shading coils are installed on AC full-voltage starters to _____________. A. eliminate contact chatter B. dissipate opening contact arcs C. delay current build up in the holding coil D. protect the motor windings from momentary starting current overload

Last Answer : Answer: A

Description : Component F in the illustrated device is for _________. EL-0033 A. short circut protection B. latching the trip unit closed after resetting the breaker C. overload protection D. providing a flexible connection between the input terminal G and the tripping unit E

Last Answer : Answer: C

Description : When the master switch for the winch shown in the illustration is in the 'off' position, and the line & safe switches are closed, which of the listed relays should be energized? EL-0102 A. 'DB' & '2T' B. 'DB' & '4M' C. 'FR-B.O.' & 'LV' D. '1M' & '1A'

Last Answer : Answer: C

Description : Was it really necessary to hold reset while I push the power button?

Last Answer : If it's like most imbedded technology, the reset button holds it in reset or basically a powered-up, but off mode. This kept it from doing anything to the internal EEPROM (like reading from it, ... random inputs to it) that might corrupt the data, while you turned it off (removing power from it).

Description : If the motor shown in the illustration will not start when 'Q' is depressed, which of the listed components should be checked FIRST? EL-0017 A. Fuses 'F-1' and 'F-2'. B. Operating coil 'C'. C. Contacts 'H-1', 'H-2', and 'H-3'. D. Contact 'H-4'.

Last Answer : Answer: A

Description : If a single-phase induction motor fails to start, the problem may be _____________. A. an open in the main winding B. a shorted shunt field C. a closed centrifugal switch D. low circuit frequency

Last Answer : Answer: A

Description : If a single-phase induction motor fails to start, the problem may be _____________. A. an open in the run winding B. a shorted shunt field C. a closed centrifugal switch D. low circuit frequency

Last Answer : Answer: A

Description : The schematic diagram shown in the illustration uses symbol 'A' to represent a/an _________. EL-0011 A. non-renewable fuse link B. circuit breaker coil C. overload relay coil D. thermal overload heater

Last Answer : Answer: D

Description : Component 'C' in section 'I' shown in the illustration represent ____________. EL-0093 A. a selectable holding coil arrangement B. a 'fuse blown' indicator circuit C. 'reset' and 'trouble' lamps D. a handset with switch and voice elements

Last Answer : Answer: D