If a magnetic controller contactor fails to pick up when the coil voltage is applied to the contactor coil, the cause may be _____________. A. overload B. misalignment of the affected contactor contacts C. low spring pressure D. an open contactor coil  

1 Answer

Answer :

Answer: D

Related questions

Description : If a magnetic controller relay fails to drop out when the coil voltage is removed from the relay, the probable cause may be _____________. A. excessive spring tension B. overvoltage C. excessive current D. welded contacts

Last Answer : Answer: D

Description : Magnetic controller contacts may become welded together during operating conditions as a result of _____________. A. high spring pressure B. high ambient temperature C. an open coil D. low voltage on operating coil

Last Answer : Answer: D

Description : If a magnetic controller contact fails to pick up when the operating coil is energized, one possible cause may be _______________. A. low spring pressure B. low voltage to the coil C. the residual magnetism of the contact faces D. dirty contact faces

Last Answer : Answer: B

Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown

Last Answer : Answer: B

Description : A loud buzzing noise at the contacts of a magnetic controller could indicate _____________. A. weak contact spring pressure B. misalignment of the magnet faces C. excessive line current D. mechanical binding

Last Answer : Answer: B

Description : A shading coil used in an AC magnetic controller, functions to _____________. A. reduce vibration and noise in the contactor B. prevent flux buildup in the operating coil C. eliminate arcing when the contacts close D. energize the operating coil and 'pull in' the contacts

Last Answer : Answer: A

Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button

Last Answer : Answer: D

Description : Magnetic controller contacts may become welded together during operation because of _____________. A. excessive magnetic gap B. low contact pressure C. an open coil D. excessive ambient temperature

Last Answer : Answer: B

Description : Magnetic controller contacts may become welded together during operation due to _____________. A. an open coil B. low contact pressure C. excessive ambient temperature D. excessive magnetic gap

Last Answer : Answer: B

Description : When troubleshooting a magnetic controller, it is found that the contacts are welded together. The most probable cause is _____________. A. excessive operation at low load B. high ambient temperature C. low voltage on the operating coil D. high voltage on the operating coil

Last Answer : Answer: C

Description : During its operation, loud buzzing and resultant welding of contacts of a magnetic relay may be caused by __________. A. overheating of the contactor coil B. low voltage on the operating coil C. low insulation resistance to ground D. lubrication of the contact bearing points

Last Answer : Answer: B

Description : The pitting of controller contacts can be caused by _____________. A. excessive spring pressure B. insufficient contact pressure C. continuous motor overload D. all of the above

Last Answer : Answer: B

Description : The illustrated motor fails to start and gives a loud hum when the start button is depressed, your first action should be to __________. EL-0007 A. disassemble the motor to fix the centrifical ... D. hold the 'M' contactor closed by hand while wearing electrical safety gloves to get motor started

Last Answer : Answer: B

Description : The winch shown in the illustration will not operate in any speed in the lowering direction and at an abnormal speed in 'first point hoist'. The possible cause is that _______________. EL-0102 A. ... '1M' in the power circuit are badly corroded D. master switch contacts 'MS6' have weak springs

Last Answer : Answer: B

Description : The 'reset' contacts of the master switch shown in the illustration provides the winch controller with ___________. EL-0102 A. low voltage release B. overload protection C. low voltage protection D. high power factor correction

Last Answer : Answer: C

Description : The arc resulting from the tripping of a circuit breaker is prevented from damaging the contacts by _____________. A. designing the contacts to open slowly B. directing the arc into an ... an inverse timed thermal trip for short circuit currents D. instantaneous magnetic trip for overload currents

Last Answer : Answer: B

Description : The purpose of a magnetic relay is to _____________. A. open a circuit only in the event of overload B. remotely open and close contacts C. provide overcurrent protection during starting D. relay voltages at increased power

Last Answer : Answer: B

Description : Humming or buzzing of electric contacts is a symptom of ____________. A. low voltage on the operating coil B. power failure to the operating coil C. a control circuit ground D. a control circuit overload

Last Answer : Answer: A

Description : During maintenance of circuit breakers, _______________. A. always smooth roughened contact surfaces with a file B. never pass more than rated breaker current through the overload heater element C. ... wear and misalignment of main contacts D. assume heater elements installed are of correct size

Last Answer : Answer: C

Description : A loud buzzing noise in an AC controller is probably caused by _____________. A. poor contact with the overload relay B. an incorrectly sized heater C. a broken shading coil D. abnormal starting current

Last Answer : Answer: C

Description : Motor starter or controller contacts may become welded together if the contacts _____________. A. open too quickly and arc B. close under excessive pressure C. open or close too quickly D. close under excessive starting current

Last Answer : Answer: D

Description : Motor controller or starter contacts may become pitted and welded together if the contacts _____________. A. open under loaded conditions B. close slowly with light pressure C. open too quickly and arc D. close quickly with proportionate pressure

Last Answer : Answer: B

Description : When troubleshooting a motor controller, all indications are that a relay coil should be energized. If there were no magnetic pull, with rated voltage measured across the coil, the most probable cause ... open C. auxiliary contact in series with the coil is defective D. relay armature is stuck

Last Answer : Answer: A

Description : The purpose of a main switchboard circuit breaker's reverse-power trip is to _____________. A. prevent main circuit overload B. protect the circuit breaker blowout coil C. prevent alternator motorization D. prevent low voltage tripout

Last Answer : Answer: C

Description : In the illustration, the purpose of part B is to _________. EL-0033 A. increase resistance in series with the contacts as they close to prevent arcing B. create a magnetic field in the steel ... event of an overload D. provide ventilation to the contact when the breaker is close to rated capacity

Last Answer : Answer: B

Description : The winch shown in the illustration operates in any of the positions with the master switch in the 'lower' direction, but will not 'hoist' in any of the master switch hoist positions. Which of the listed faults ... '2M' in the power circuit may be badly corroded. D. Series relay 'FR' may be open.

Last Answer : Answer: A

Description : The 'safe switch' of the winch controller shown in the illustration is operated _______________. EL-0102 A. through the master switch handle B. when heater circuit current is high C. by contactor coil 'FR' D. manually by the winch operator

Last Answer : Answer: D

Description : Shading coils are installed on AC full-voltage starters to _____________. A. eliminate contact chatter B. dissipate opening contact arcs C. delay current build up in the holding coil D. protect the motor windings from momentary starting current overload

Last Answer : Answer: A

Description : A circuit is protected from overheating by a/an ___________. A. pyrometer B. thermal overload relay C. magnetic contactor D. overload transformer

Last Answer : Answer: B

Description : Burning of controller contacts, when opening, is prevented by _____________. A. coating the contact surfaces lightly with petroleum jelly B. magnetic blowout coils C. an overvoltage release D. an overcurrent release

Last Answer : Answer: B

Description : If the motor fails to start and a voltmeter reading between 1 and 6, as illustrated, indicates line voltage, your next step should be to ________. EL-0007 A. replace fuse '10a' B. replace or repair contact 'Ma' C. reset and determine the cause of the overload D. check line voltage between L1 and L3

Last Answer : Answer: C

Description : If the line voltage to the controller shown in the illustration is 440 volts, what voltage is applied across the motor when contacts 'S' close? EL-0080 A. 110 volts B. 220 volts C. 440 volts D. 660 volts

Last Answer : Answer: B

Description : If many turns of an alternating current coil for a contactor become short circuited, the coil _____________. A. will continue to operate B. will probably burn out immediately C. will operate on reduced current D. temperature will drop

Last Answer : Answer: B

Description : If many turns of an alternating current coil for a contactor become short circuited, the coil _____________. A. temperature will drop B. will probably burn out immediately C. will continue to operate D. will operate on reduced current

Last Answer : Answer: B

Description : Magnet chatter or 'pumping' occurring in a magnetic contactor can be caused by ______________. A. dirt or grease on pole faces B. mechanical interference in the contacts C. chattering contacts on the control relay D. magnetic lock out of the contacts

Last Answer : Answer: C

Description : A three-phase, induction-type motor experiences an open in one phase. Which of the listed automatic protective devices will prevent the machine from being damaged? A. Overspeed trip B. Thermal overload relay C. Three-pole safety switch D. Magnetic blowout coil

Last Answer : Answer: B

Description : If a transformer is connected to a DC source, the transformer will overload at the ____________. A. contacts B. primary coil C. secondary coil D. core

Last Answer : Answer: B

Description : If a single-phase induction motor fails to start, the problem may be _____________. A. an open in the main winding B. a shorted shunt field C. a closed centrifugal switch D. low circuit frequency

Last Answer : Answer: A

Description : If a single-phase induction motor fails to start, the problem may be _____________. A. an open in the run winding B. a shorted shunt field C. a closed centrifugal switch D. low circuit frequency

Last Answer : Answer: A

Description : RC time constant characteristics, as shown in the illustration, are important in _____________. EL-0086 A. bridge rectifiers for alternator excitation B. timing and pulse shaping circuits C. transistor power amplifier biasing D. motor controller overload protection

Last Answer : Answer: B

Description : If a DC motor runs faster than designed, with all other conditions being normal, the possible cause could be a/an ______________. A. shorted shunt field coil B. open armature coil C. reversed commutating pole D. overload

Last Answer : Answer: A

Description : If a synchronous motor begins to vibrate severely and pull out of synchronism, the cause may be ____________. A. an overload B. an open in the field coils C. no exciter voltage D. all of the above

Last Answer : Answer: D

Description : When troubleshooting motor controllers, a shorted relay or contactor coil is often indicated by _______________. A. a resistance reading of 'infinity' on an ohmmeter B. charred insulation and/or a blown ... of the coil's leads to ground D. a higher-than-normal voltage reading across the winding

Last Answer : Answer: B

Description : An open shunt field in a direct current machine may be located by connecting the field circuit to an external power source, equal to the rated field voltage or less, and tested with a voltmeter from ... C. any suitable ground to any available line lead D. any field pole to each field coil lead

Last Answer : Answer: A

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : If the contacts of a motor starter or controller fail to drop out when the 'stop' button is depressed the ____________. A. contacts are carrying excessive current B. contacts have become welded together C. shading coil is broken D. shading coil is loose

Last Answer : Answer: B