If fuse 'F-1' in the illustrated schematic diagram opens, ____________. EL-0017 A. the motor will run slowly B. 'A-1' and 'A-2' will open C. the motor will not start D. the start button will jam in the closed position

1 Answer

Answer :

Answer: C

Related questions

Description : Refering to the illustrated schematic diagram, which of the following statements is true when the motor is running in the forward direction? EL-0011 A. Normally-open contacts '4-5' are closed. B. Current ... switch. C. Normally-closed contacts 'R' are open. D. The blowout coils must be closed.

Last Answer : Answer: B

Description : If the three-phase motor, shown in the illustrated schematic diagram, is running in the forward direction, which of the following actions must occur before the motor will reverse rotation? EL-0011 A. Normally-closed ... 'L1' and 'L3' must be interchanged via the 'R' contacts. D. All of the above.

Last Answer : Answer: C

Description : Regarding the illustrated electrical schematic, 'S1-P', 'S1-Q', and 'S1-R' represent ____________. EL-0016 A. capacitors B. normally-closed contacts C. normally-open contacts D. normally-closed pushbutton switches

Last Answer : Answer: C

Description : As shown in the illustration, which listed action will occur first when push button 'Q' is depressed? EL-0017 A. Contacts 'H-1', 'H-2' and 'H-3' close. B. Contact 'H-4' closes. C. Operating coil 'C' energizes. D. Switch 'R' opens.

Last Answer : Answer: C

Description : The electrical schematic shown in the illustration represents a/an ____________. EL-0017 A. across-the-line starter B. primary-resistor starter C. autotransformer starter D. part-winding starter

Last Answer : Answer: A

Description : In the illustrated schematic diagram, which of the listed devices prevents the forward and reversing coils from being energized simultaneously? EL-0011 A. An 'either-or' interlock B. A mechanical interlock C. Blowout coils D. A stop button

Last Answer : Answer: A

Description : 'A-1', as shown in the illustration, is/are ____________. EL-0017 A. normally-closed overload relay contacts B. a double pole knife switch C. normally-open overload relay contacts D. a single pole knife switch

Last Answer : Answer: A

Description : The illustrated motor fails to start and gives a loud hum when the start button is depressed, your first action should be to __________. EL-0007 A. disassemble the motor to fix the centrifical ... D. hold the 'M' contactor closed by hand while wearing electrical safety gloves to get motor started

Last Answer : Answer: B

Description : As shown in the illustration, what happens when 'A' is closed, 'B' is in position '2' and component 'E2' burns out? EL-0058 A. 'H' energizes and 'D' makes contact. B. 'F' goes out allowing 'G' to disconnect. C. 'G' sounds an alarm and 'F' illuminates. D. 'C' opens causing 'A' to also open.

Last Answer : Answer: C

Description : If the motor shown in the illustration will not start when 'Q' is depressed, which of the listed components should be checked FIRST? EL-0017 A. Fuses 'F-1' and 'F-2'. B. Operating coil 'C'. C. Contacts 'H-1', 'H-2', and 'H-3'. D. Contact 'H-4'.

Last Answer : Answer: A

Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown

Last Answer : Answer: B

Description : If the illustrated motor fails to start and gives a loud hum when the start button is pushed, the problem is ________. EL-0007 A. one of the phases to the motor is not energized because of ... electrical distribution system D. 'OL1' is open because of 'T1' overload causing the motor to single phase

Last Answer : Answer: A

Description : As shown in the illustration, 'S' is the __________. EL-0017 A. safety switch B. overload trip C. start button D. stop button

Last Answer : Answer: D

Description : When an AC or a DC motor fails to start, the FIRST step in troubleshooting should be to check the ____________. A. motor windings for obvious opens B. motor controller leads for continuity C. fuse or circuit breaker D. motor controller leads for grounds

Last Answer : Answer: C

Description : When the motor shown in the illustration is running and the stop button is pushed, which of the following statements will hold true? EL-0010 A. Coil 'M' will now be energized. B. Coil 'CR' will now be energized. C. Contact 'M' will close as contact 'CR' opens. D. Contacts 'M' and 'CR' will open.

Last Answer : Answer: D

Description : The schematic diagram shown in the illustration uses symbol 'A' to represent a/an _________. EL-0011 A. non-renewable fuse link B. circuit breaker coil C. overload relay coil D. thermal overload heater

Last Answer : Answer: D

Description : In the lighting distribution circuit shown in the illustration, if all switches are closed and fuse 'F2' were to open, all lights on branches ____________. EL-0013 A. '1', '2', and '3' would go out B. '1' ... and '3' would burn dimly D. '1' and '3' would go out, while branch '2' would remain lit

Last Answer : Answer: D

Description : If the motor fails to start and a voltmeter reading between 1 and 6, as illustrated, indicates line voltage, your next step should be to ________. EL-0007 A. replace fuse '10a' B. replace or repair contact 'Ma' C. reset and determine the cause of the overload D. check line voltage between L1 and L3

Last Answer : Answer: C

Description : As shown in the illustration, the symbol is used in electrical drawings to designate a ____________. EL-0026 A. limit switch with one set of normally open contacts B. maintaining type ... type push button with a mechanical interlock D. normally closed contact held open mechanically by an interlock

Last Answer : Answer: C

Description : As shown in the illustration, which of the following conditions will occur as a result of a momentary loss of power? EL-0017 A. The motor will automatically restart when power is restored. B. 'H-4' will open, ... the motor. D. 'A-1' or 'A-2' will open, necessitating a manual restarting of the motor.

Last Answer : Answer: B

Description : The contacts operated by the D.C. relay coil shown in the illustration are located in the schematic diagram prints at coordinates ____________. EL-0100 A. '41Y' on this page B. '52M52M' and '52H35M' C. '57R' on this page D. '52N' on page '57R'

Last Answer : Answer: C

Description : To stop the electric motor shown in the illustration, the stop button is depressed, causing ____________. EL-0012 A. coil 'MS' to become de-energized B. contacts 'CR1' and 'MR4' to open C. contacts 'MR1', 'MR2', and 'MR3' to open D. contacts 'MS1', 'MS2', and 'MS3' to open

Last Answer : Answer: C

Description : As shown in the illustration, which of the operations listed will happen when the 'jog button' is pushed? EL-0010 A. Coil 'CR' closes the normally open 'CR' contacts. B. Coil 'M' opens contact 'M'. C. Coil 'M' closes contact 'M'. D. Contact 'M' remains open despite the jog button being pushed.

Last Answer : Answer: C

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : As shown in the illustration, the same indication occurs when 'C' opens as when ____________. EL-0058 A. 'E2' burns out B. 'H2' opens C. 'G' opens D. 'F' burns out

Last Answer : Answer: A

Description : When 'selector switch' 'SEL8' shown in the illustration is in the 'TEST' position, contacts '3,4' and '7,8' are respectively ____________. EL-0100 A. open; closed B. closed; open C. open; open D. closed; closed

Last Answer : Answer: B

Description : When 'selector switch' 'SEL8' shown in the illustration is in the 'OFF' position, contacts '3,4' and '7,8' are respectively ____________. EL-0100 A. open; closed B. closed; open C. open; open D. closed; closed

Last Answer : Answer: A

Description : Which component is responsible for energizing solenoid 'B1-B2' and releasing the brake for the winch motor shown in the illustration? EL-0102 A. Contactor '3M' B. A spring not shown in the schematic diagram C. Resistor 'B2-R1' D. Relay 'FR-B.O.'

Last Answer : Answer: A

Description : Which of the illustrations listed below is representative of a motor controller's 'schematic' or 'elementary' diagram? A. EL-0023 B. EL-0007 C. EL-0037 D. EL-0058

Last Answer : Answer: B

Description : You are paralleling two alternators. The synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates that the ____________. A. alternator ... be closed C. incoming alternator is running too slowly D. synchroscope is defective or broken

Last Answer : Answer: B

Description : If the fuse shown on the schematic (figure 3-10) opens, what lights will operate?

Last Answer : Only the brake lights.

Description : In the illustrated device, the part labeled '1A' _________. EL-0001 A. are start and run windings for a single phase shaded pole induction motor B. is the stator for a polyphase induction ... armature for a squirrel cage rotor motor D. are direct current shunt field windings for a universal motor

Last Answer : Answer: B

Description : The electrical schematic illustrated in figure A, depicts a/an _____________. EL-0059 A. autotransformer B. Delta Wye transformer C. primary EMF generator D. potential transformer

Last Answer : Answer: D

Description : On the meter scale illustrated, while using the R X 1 scale, the reading at 'F' will be ____________. EL-0047 A. 1.8 ohms B. 6.0 ohms C. 9.4 ohms D. 0.6 ohms

Last Answer : Answer: D

Description : On the meter scale illustrated, while using the R X 100 scale, the reading at 'F' will be ____________. EL-0047 A. 60 ohms B. 40 ohms C. 30 ohms D. 3 kohms

Last Answer : Answer: A

Description : Component F in the illustrated device is for _________. EL-0033 A. short circut protection B. latching the trip unit closed after resetting the breaker C. overload protection D. providing a flexible connection between the input terminal G and the tripping unit E

Last Answer : Answer: C

Description : During the start-up of the circuit shown in the illustration, it is noted that the ends of component 'C' remain lighted but the tube does not illuminate. The cause of this problem is ____________. EL- ... ' is closed C. component 'C' is the wrong wattage D. component 'B' contacts are stuck closed

Last Answer : Answer: D

Description : What is the resistance value indicated by the multimeter scale illustrated, if the range switch is set at R X 1, and the needle is at the position indicated by the letter 'F'? EL-0047 A. 0.6 ohms B. 6 ohms C. 9.6 ohms D. .38 ohms

Last Answer : Answer: A

Description : What operational characteristics do the components labeled as 'S' and 'R' represent in the motor controller diagram shown in the illustration? EL-0080 A. Standard and Reverse directions B. Stop and Restart features C. Subnormal and Regular loading D. Start and Run functions

Last Answer : Answer: D

Description : In the schematic diagram of the DC compound generator shown in the illustration, the positive ammeter reading is 500 amps and the negative ammeter reading is 475 amps. What is the current flow through the neutral bus? EL-0037 A. 0 amp B. 12.5 amp C. 25 amp D. 975 amp

Last Answer : Answer: C

Description : The schematic diagram shown in the illustration represents which of the listed solid-state circuits? EL-0069 A. Bridge rectifier B. Magnetic amplifier C. Flip-flop generator D. Cathodic amplifier

Last Answer : Answer: A

Description : The circuit illustrated represents a 2 wire DC ground detecting system. If the positive bus is grounded and the test button is pushed, which of the lamps will be brightest? EL-0008 A. X B. Y C. both will be equal brightness. D. both will go out.

Last Answer : Answer: C

Description : In the illustrated ground detection system with a ground on phase A, if the switch is opened __________. EL-0009 A. lamp A will dim or go out depending on the severity of the ground B. all three ... lamp A will be brighter D. lamp A will start flickering if the ground is in an AC induction motor

Last Answer : Answer: B

Description : If a single-phase induction motor fails to start, the problem may be _____________. A. an open in the run winding B. a shorted shunt field C. a closed centrifugal switch D. low circuit frequency

Last Answer : Answer: A