If a transformer has 50 turns in the primary winding and 10 turns in the secondary winding, what is the reflective resistance if the secondary load resistance is 250 ohms?

A.250 ohms

B.25 ohms

C.6,250 ohms

D.62,500 ohms

2 Answers

Answer :

If a transformer has 50 turns in the primary winding and 10 turns in the secondary winding, what is the reflective resistance if the secondary load resistance is 250 ohms?

A.250 ohms

B.25 ohms

C.6,250 ohms

D.62,500 ohms

Answer :

6,250 ohms

Related questions

Description : A certain transformer has 400 turns in the primary winding and 2,000 turns in the secondary winding. The turns ratio is? A.0.2 B.0.4 C.5 D.25

Last Answer : A certain transformer has 400 turns in the primary winding and 2,000 turns in the secondary winding. The turns ratio is? A.0.2 B.0.4 C.5 D.25

Description : A certain transformer has 200 turns in the primary winding, 50 turns in the secondary winding and 120 volts applied to the primary. What is the voltage across the secondary?  (A) 30 Volts (B) 480 Volts (C) 120 Volts (D) 60 Volts

Last Answer : A certain transformer has 200 turns in the primary winding, 50 turns in the secondary winding and 120 volts applied to the primary. What is the voltage across the secondary?  (A) 30 Volts (B) 480 Volts (C) 120 Volts (D) 60 Volts

Description : When the turns ratio of a transformer is 20 and the primary ac voltage is 12 V, the secondary voltage is? A.12 V B.120 V C.240 V D.2,400 V

Last Answer : When the turns ratio of a transformer is 20 and the primary ac voltage is 12 V, the secondary voltage is? A.12 V B.120 V C.240 V D.2,400 V

Description : The turns ratio of a transformer having 200 primary turns and 1,200 secondary turns is? A.6 B.24 C.1.66 D.66

Last Answer : The turns ratio of a transformer having 200 primary turns and 1,200 secondary turns is? A.6 B.24 C.1.66 D.66

Description : Relative to the secondary winding of a step-up transformer, the primary winding will have _____________. A. more turns B. fewer turns C. half as many turns D. twice as many turns

Last Answer : Answer: B

Description : The doorbell on your house requires a 12 volt alternating current. A transformer having a primary winding of 1,600 turns is to be used to step down your house's 110-volt alternating current. How many turns are there on the secondary winding?

Last Answer : ANSWER: 175 TURNS 

Description : The primary winding of a 220/6 V, 50 Hz transformer is energised from 110 V, 60 Hz supply. The secondary output voltage will be (A) 3.6 V. (B) 2.5 V. (C) 3.0 V. (D) 6.0 V.

Last Answer : (C) 3.0 V.

Description : The primary winding of a 220/6 V, 50 Hz transformer is energised from 110 V, 60 Hz supply. The secondary output voltage will be (A) 3.6 V. (B) 2.5 V. (C) 3.0 V. (D) 6.0 V.

Last Answer : The primary winding of a 220/6 V, 50 Hz transformer is energised from 110 V, 60 Hz supply. The secondary output voltage will be 3.0 V.

Description : The primary winding of a 220/6 V, 50 Hz transformer is energised from 110 V, 60 Hz supply. The secondary output voltage will be; (A) 3.6 (B) 2.5 V (C) 3.0 V (D) 6.0 V

Last Answer : The primary winding of a 220/6 V, 50 Hz transformer is energised from 110 V, 60 Hz supply. The secondary output voltage will be: 3.0 V

Description : If a 120v transformer has 200 turns the secondary winding has 20 turns what is the secondary winding voltage?

Last Answer : 12v

Description : What is the secondary winding voltage if a 120v transformer has 200 turns the secondary winding has 20 turns?

Last Answer : 12 volts

Description : 21.The ordinary two winding transformer's primary and secondary windings always have A. different no of turns B. same size of copper wire C. a common magnetic circuit D. separate magnetic circuits

Last Answer : C. A common magnetic circuit

Description : For a 100% efficient transformer, the primary winding has 1000 turns and the secondary 100 turns. If the power input to the above transformer is 1000 watts, the power output is_________.

Last Answer : For a 100% efficient transformer, the primary winding has 1000 turns and the secondary 100 turns. If the power input to the above transformer is 1000 watts, the power output is 1000 watts.

Description : In a certain loaded transformer, the secondary voltage is one-fourth the primary voltage. The secondary current is? A.one-fourth the primary current B.four times the primary current C.equal to the primary current D.one-fourth the primary current and equal to the primary current

Last Answer : In a certain loaded transformer, the secondary voltage is one-fourth the primary voltage. The secondary current is? A.one-fourth the primary current B.four times the primary current C.equal to the primary current D.one-fourth the primary current and equal to the primary current

Description : The primary coil of a transformer is connected to a 60 V ac source. The secondary coil is connected to a 330 ohms load. The turns ratio is 3:1. What is the secondary voltage? A.2 V B.20 V C.180 V D.18 V

Last Answer : The primary coil of a transformer is connected to a 60 V ac source. The secondary coil is connected to a 330 ohms load. The turns ratio is 3:1. What is the secondary voltage? A.2 V B.20 V C.180 V D.18 V

Description : When a transformer is used to step down voltage, the low voltage winding is _____________. A. part of the core B. the primary coil C. not insulated D. the secondary coil

Last Answer : Answer: D

Description : In a tap changing transformer, the tappings are provided on (a) primary winding (b) secondary winding (c) high voltage winding (d) any of the above

Last Answer : (b) secondary winding

Description : 28.In a two winding transformer, the emf /turn in secondary winding is always......the induced emf power turn in primary A. equal to k times B. equal to 1/k times C. equal D. greater than

Last Answer : C. equal

Description : 6 In a two winding transformer, the primary and secondary induced emf E1 & E2 are always A. equal in magnitude B. anti phase with each other C. in phase with each other D. determined by load on transformer secondary

Last Answer : C. In phase with each other

Description : 12] Which is not the basic element of the transformer? A. core B. primary winding C. secondary winding D. mutual flux

Last Answer : D. Mutual flux

Description : A 220/440 V, 50 Hz, 5 KVA, single phase transformer operates on 220V, 40Hz supply with secondary winding open circuited. Then (A) Both eddy current and hysteresis losses decreases. (B) Both ... same but hysteresis loss increases. (D) Eddy current loss increases but hysteresis loss remains the same.

Last Answer : (A) Both eddy current and hysteresis losses decreases.

Description : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: (A) both the eddy current and the hysteresis losses will decrease ... losses will increase (D) eddy current losses will increase but the hysteresis losses will remain the same

Last Answer : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: both the eddy current and the hysteresis losses will decrease

Description : Which of the following statements identifies the difference between the primary windings and the secondary windings of a 2:1 stepdown transformer? A. The secondary windings have twice as much resistance ... primary windings. D. The secondary windings have half as many turns as the primary windings.

Last Answer : Answer: D

Description : A transformer steps down 220V to 40 volts. If the secondary turns are 40 then primary turns will be: a. 20 b. 40 c. 120 d. 220

Last Answer : d. 220V

Description : 52 A transformer has 1000 primary turns, connected to 250V ac supply. To get 400V secondary voltage the no of secondary turns should be A. 1600 B. 250 C. 400 D. 1250

Last Answer : A. 1600

Description : 29.In transformer terminology, the ratio 20:1 indicates that A. there are 20 turns on primary one turn on secondary B. secondary voltage is 1/20th of the primary C. primary current is 20 times greater than the secondary current D. for every 0 turns on primary, there is one turn on secondary

Last Answer : A. there are 20 turns on primary one turn on secondary

Description : If the secondary turns of a transformer are doubled and at the same time primary voltage is reduced to half then the secondary voltage will

Last Answer : If the secondary turns of a transformer are doubled and at the same time primary voltage is reduced to half then the secondary voltage will not change

Last Answer : Turns ratio= N1/ N2 IN Scott connection Main transformer turns ratio = N1 /N2 Teaser transformer turns ratio= 0.866N1/N2 Where N1= number of turns in primary winding N2= number of turns in secondary winding

Last Answer : High voltage winding in a transformer has more number of turns.

Last Answer : yes High Voltage side of Transformer winding have more number of turns. and low voltage side of Transformer winding have less number of turns.

Description :  If a secondary coil has 40 turns, and, a primary coil with 20 turns is charged with 50 V of potential difference, then the potential difference in the secondary coil would be A. 50 V in secondary coil B. 25 V in secondary coil C. 60 V in secondary coil D. 100 V in secondary coil

Last Answer : 100 V in secondary coil

Description : The primary turns of a 444 V/222 V, 50 Hz single-phase transformer with a core cross-sectional area of 100 cm2, and a maximum flux density of 1.0 T is (A) 100 (B) 200 (C) 222 (D) 400

Last Answer : The primary turns of a 444 V/222 V, 50 Hz single-phase transformer with a core cross-sectional area of 100 cm2, and a maximum flux density of 1.0 T is 200

Description : An auto transformer is preferred over an ordinary two winding transformer due to: a) Safety of operation b) Availability of taps on secondary c) Copper savings d) All the above

Last Answer : Ans: C

Description : The hook-on AC volt-ammeter consists essentially of a split-core and a rectifiertype instrument connected to the secondary winding of a _____________. A. potential transformer B. control transformer C. current transformer D. reactance transformer

Last Answer : Answer: C

Description : What causes a voltage to be developed across the secondary winding of a transformer?

Last Answer : The magnetic lines generated by the current in the primary cut

Description : 50 The equivalent resistance of the primary of the transformer having K = 5, R1 = 0.1 ohm when referred to secondary becomes .....ohm A. 0.5 B. 0.02 C. 0.004 D. 2.5

Last Answer : A. 0.5

Description : What is the maximum current allowed to be drawn from the secondary of a 2 KVA step-down transformer with a turns ratio of four to one if connected across a 440 volt line? A. 1.1 amps B. 4.5 amps C. 18.1 amps D. 22.7 amps

Last Answer : Answer: C

Description : Increasing the number of turns of wire on the secondary of a transformer will  (A) Decrease the secondary current (B) Increase the primary current (C) Have no effect on the secondary current (D) Increase the secondary current

Last Answer : Increasing the number of turns of wire on the secondary of a transformer will Decrease the secondary current 

Last Answer : Primary winding of a transformer could either be a low voltage or high voltage winding.

Description : A single-phase, 50 kVA, 250 V/500 V two winding transformer has an efficiency of 95% at full load, unity power factor. If it is re-configured as a 500 V/750 V auto-transformer, its efficiency at its new rated load at unity power factor will be  (A) 95.752% (B) 97.851% (C) 98.276% (D) 99.241%

Last Answer : A

Description : The low voltage winding of a 400/230 V, 1-phase, 50 Hz transformer is to be connected to a 25 Hz, the supply voltage should be

Last Answer : The low voltage winding of a 400/230 V, 1-phase, 50 Hz transformer is to be connected to a 25 Hz, the supply voltage should be 115 V.

Description : In potential transformers, the secondary turns are increased slightly and the primary and secondary windings are wound as closely as possible to compensate for  (a) Phase angle and ratio error, ... loss and hysteresis loss, respectively  (d) The hysteresis loss and eddy current loss, respectively

Last Answer : In potential transformers, the secondary turns are increased slightly and the primary and secondary windings are wound as closely as possible to compensate for Ratio and phase angle error, respectively 

Description : What is the maximum allowable primary current of a 2 KVA step-down transformer with a four to one turns ratio if connected across a 440 volt line? A. 1.1 amps B. 4.5 amps C. 18.1 amps D. 27.7 amps

Last Answer : Answer: B

Description : The turns ratio required to match an 80 ohms source to a 320 ohms load is? A.80 B.20 C.4 D.2

Last Answer : c

Description : A load with an impedance of 440 ohms is connected across the secondary of the transformer illustrated. If the input voltage is 110 VAC and the step-up ratio is 10 to 1, what will be the primary current? EL-0055 A. 2.5 amps B. 25 amps C. 250 amps D. current cannot be determined with information given

Last Answer : Answer: B

Description : A load is connected to the secondary of the transformer illustrated and the current through the load is 10 amps. If the step-up ratio is 10 to 1 and the input voltage is 110 VAC, what will be the current flow through the primary? EL-0055 A. 1 amp B. 10 amps C. 100 amps D. 1000 amps

Last Answer : Answer: C

Description : A 1:5 step-up transformer has 120V across the primary and 600 ohms resistance across the secondary. Assuming 100% efficiency, the primary current equals (A) 0.2 Amp. (B) 5 Amps. (C) 10 Amps. (D) 20 Amps.

Last Answer : I1= V1 /R1 = 120/600 = 0.2 (η = 100%, losses are zero ∴V1 = VR = I1R1)

Description : A transformer has a turns ratio of two to one. If a 100 ohm resistor is connected on the high side, its resistance as measured on the low side would be: w) 25 ohms x) 50 ohms y) 100 ohms z) 400 ohms

Last Answer : ANSWER: W -- 25 OHMS

Description : The value of exciting or magnetizing current depends upon which of the following factors ? (a) Total m.m.f. required (b) The number of turns in the exciting winding (c) The way in which the winding is distributed (d) All of the above

Last Answer : (d) All of the above

Description : What is the output current of a 480 Volt primary 208 volt secondary - 3 phase transformer?

Last Answer : You need to mention the Load connected to find the current.