What are the torque settings used in IPBD connection?

1 Answer

Answer :

M12 (Nut bolt) 4506 100 kg-cm or 55 NM

M16 (Nut bolt) 9006 250 kg-cm or 80 NM

M20 (Nut bolt) 18006300 kg-cm or 100 NM 

Related questions

Description : What are the tests to be carried during PM checks of IPBD?  

Last Answer : a) Physical inspection of bus for any spark or overheating or discoloration. b) Physical inspection of copper braided flexibles for discoloration. c) Physical inspection of inspection window gaskets, seal off ... Tan-delta test of IPBD m) IR value measurement n) Cleanliness checks entire IPBD. 

Description : What are the isolations required for working on IPBD/ Generator?

Last Answer : a. Generator field breaker open and tagged. b. GT breaker open and earth switch closed.  c. Barring gear motor stopped and tagged. d. Generator PT's isolated and tagged. e. CB 472 and CB 474 open ... 's are isolated and tagged. f. Before doing any work on brush gear 64F1 relay to be taken out. 

Description : What is the protection for IPBD? 

Last Answer : Generator – GT overall differential protection.  

Description : What is use of hot air blower in IPBD?

Last Answer : To remove moisture and to prevent moisture condensation inside the duct at commissioning time or in long shutdown periods. 

Description : Why seal-off bushings are used in IPBD?  

Last Answer : To prevent interchange of air at different temperature and leakage of hydrogen or infiltration of dust into the bus duct. 

Description : Why aluminium bus bars are silver-plated in IPBD?

Last Answer : Aluminium bus bars are silver-plated at flexible connection to prevent the galvanic corrosion ant also for low contact resistance. 

Description : Why neoprene rubber bellows are used in IPBD?

Last Answer : Neoprene rubber bellows are used near the terminals of the equipment and also at building wall from indoor to outdoor area to allow thermal expansion and to minimise vibrations. 

Description : What are the salient features of IPBD?  

Last Answer : a. This for a vital link between generator, GT, UAT, SPPT, SET and neutral grounding transformer. b. The continuous enclosure operating at ground potential limits the leakage flux outside the enclosure ... maintenance is nil. j. Separate parts erected IPBD. Hence changing parts makes it easy. 

Description : Why flexible expansion joints are used in IPBD?

Last Answer : To cater thermal expansion and contraction due to heating and to eliminate mechanical vibrations to the equipment. 

Description : What is type of nut and bolts are used in IPBD?  

Last Answer : Non-magnetic stainless steel nut and bolts are used in IPBD to restrict magnetic effect at joints.  

Description : Why neoprene rubber bellows in generator IPBD?

Last Answer : Prevent vibrations transmitted from generator to IPBD.  

Description : What are the torque settings for Kia 2700 cylinder head and tappet clearance?

Last Answer : Feel Free to Answer

Description : What is Chevy flywheel torque settings?

Last Answer : Need answer

Description : The KW load is evenly distributed between two alternators just placed in parallel by adjusting _____________. A. a balance coil B. the governor settings C. the field excitation D. a rheostat

Last Answer : Answer: B

Description : If two AC generators have just been placed in parallel, the true power load is initially distributed evenly by _____________. A. a balance coil B. changing field excitation C. adjusting the governor control settings D. a rheostat

Last Answer : Answer: C

Description : The division of the kilowatt load between two AC generators operating in parallel is controlled by the settings and characteristics of the _____________. A. voltage regulators B. field rheostats C. reverse power relays D. prime mover governors

Last Answer : Answer: D

Description : The load sharing characteristics of two diesel generators operating in parallel are mostly dependent on their governor ____________. A. load limit settings B. idle speed settings C. speed limit settings D. speed droop settings

Last Answer : Answer: D

Description : What are the settings provided in synchronizing scheme (SKE Relay)?

Last Answer : Voltage – V1- V2 = 10% Frequency – t = 0.05 Sec (2.5 Hz) % Slip – 0.45 Phase angle difference - 20°. 

Description : A CRO screen has ten divisions on the horizontal scale. If a voltage signal 5 sin 314t+45 deg)is examined with a line base settings of 5 msec/div, the number of cycles of signal displayed on the screen will be a) 0.5 cycles b) 2.5 cycles c) 5 cycles d) 10 cycles

Last Answer : Ans: 2.5 cycles

Description : Which of the following instruments have least torque/weight ratio: a) Dynamometer type b) PMMC c) Attraction type moving iron d) Repulsion type moving iron

Last Answer : Ans: A

Description : Squirrel cage induction motor has a) Zero starting torque b) Very small starting torque c) Medium starting torque d) Very high starting torque

Last Answer : Ans: B

Description : Which of the following statements describes what will occur if the motor shown in the illustration is required to carry 150% of full load? EL-0056 A. The primary counter emf will be increased. B. ... slip will decrease. D. The slip value, stator current curve, and torque curve will all coincide.

Last Answer : Answer: B

Description : The torque and current curves for a three-phase induction motor with a cage rotor, are shown in the illustration. Which of the following statements is true concerning the depicted curves? EL-0056 A. As slip ... D. If the motor is loaded to the point where 40% slip has resulted, it will stall.

Last Answer : Answer: D

Description : The torque produced by a DC motor armature is the product of the force acting at the armature surface multiplied by _____________. A. work done by the armature in one revolution B. effective ... arm at the center of rotation of the armature D. perpendicular distance to its center of rotation

Last Answer : Answer: D

Description : An increase in the amount of current flow through the armature of a shunt motor is the final result of a/an _____________. A. increase in the load on the motor B. decrease in the load on the motor C. increase in counter EMF D. decrease in armature torque

Last Answer : Answer: A

Description : Which of the following is a characteristic of fractional horsepower repulsion start motors? A. They start with a rotating stator field. B. The short circuiting ring is removed from the commutator while ... brushes are removed from the commutator while starting. D. They have a low starting torque.

Last Answer : Answer: B

Description : The most effective method of locating a loose commutator bar in a D.C. motor is by _____________. A. visual inspection B. jiggling each by hand C. sounding each bar with a light weight hammer D. checking with a calibrated torque wrench

Last Answer : Answer: C

Description : If the driving torque, such as that produced by a diesel engine, creates pulsations when coupled with a synchronous generator operating in parallel; the generator rotor may be periodically pulled ahead or behind ... as it rotates. This co A. hunting B. direct coupling C. peaking D. harmonic coupling

Last Answer : Answer: A

Description : If air gap readings for an electical generating machine have changed significantly from the last reading, you should check _________. A. the bearings B. insulation readings and machine cleanliness C. the prime mover thrust bearing D. the field coil bolts for the proper torque values

Last Answer : Answer: A

Description : The twisting force developed by a motor and applied to a shaft is called _____________. A. magnetism B. electromotive force C. torque D. voltage

Last Answer : Answer: C

Description : If a three-phase induction motor is operated under a light load and it develops an open in one of its supply lines, the motor will _____________. A. continue to run, but will vibrate and have reduced ... speed up due to the reduced number of poles C. run cooler due to reduced current flow D. stop

Last Answer : Answer: A

Description : If the centrifugal switch or relay used for cutting out the starting winding of a split-phase induction motor fails to open once the motor is in operation, the _____________. A. motor will overspeed B ... C. motor will immediately stall under load D. motor torque will be above normal at rated speed

Last Answer : Answer: B

Description : The operating torque of the upper induction disc-type element, or timer element, of an AC reverse power relay is obtained from ____________. A. the main bus B. a separate battery source C. line voltage D. electromagnets

Last Answer : Answer: D

Description : If the driving torque, such as that produced by a diesel engine, creates pulsations when coupled with a synchronous generator operating in parallel; the generator rotor may be periodically pulled ... windings B. direct coupling C. increase governor speed droop D. decreasing governor speed droop

Last Answer : Answer: A

Description : The amount of mechanical force or torque produced by an electric motor depends on the ________________. A. strength of its magnetic field B. amount of armature current flow C. length of conductor in the field D. all of the above

Last Answer : Answer: D

Description : The primary function of an electric motor is to ___________. A. develop torque B. generate high voltages C. produce a magnetic field D. generate high electrical resistance

Last Answer : Answer: A

Description : Which of the following operating characteristics for DC motors is considered to give high starting torque? A. series B. shunt C. cumulative-compound D. differential-compound

Last Answer : Answer: A

Description : A characteristic of a wound-rotor induction motor, with a high resistance rotor winding, is _____________. A. low starting torque B. high starting torque C. high speed D. low starting voltage

Last Answer : Answer: B

Description : If an induction motor were to be operated at 90% rated voltage, _____________. A. there would be an increase in starting torque B. starting current would increase slightly C. synchronous speed would decrease slightly D. the slip would increase

Last Answer : Answer: D

Description : The function of the autotransformers used with the starters of large AC motors is to provide _____________. A. increased voltage for starting B. increased torque for starting C. reduced voltage for starting D. speed control

Last Answer : Answer: C

Description : The full load torque of an electric motor is the __________. A. minimum torque developed by the motor accelerating from stop to full speed B. turning moment exerted by the motor at rated load ... and frequency D. turning moment exerted by the motor from any rotor angular position at any load

Last Answer : Answer: B

Description : Excessive heat in an operating motor controller can result from _____________. A. a closed starter contact B. loose connections C. missing arc chutes D. low motor starting torque

Last Answer : Answer: B

Description : An across-the-line starter provides ___________________. A. maximum torque B. slow starting power C. high speed D. reduced voltage

Last Answer : Answer: A

Description : If a three-phase induction motor malfunctions and drops to a single-phase (one supply line open) ____________. A. the motor will continue to run if it is not heavily loaded B. more torque will be ... be able to be restarted D. the motor will immediately stop and can only be restarted at no load

Last Answer : Answer: A

Description : The timer element found in a reverse power relay obtains its operating torque via _____________. A. line voltage B. the main bus C. electromagnets D. a separate battery source

Last Answer : Answer: C

Description : Regarding an induction motor, the power developed by the rotor automatically adjusts itself to the _____________. A. power required to drive the load B. speed required to drive the load C. current flow in the motor stator D. torque developed by the rotating field

Last Answer : Answer: A

Description : What is the function of the interpoles installed in DC motors? A. To provide greater torque by strengthening the main field. B. To provide sparkless commutation without having to shift the brushes. C. To limit the production of counter-electromotive force. D. To limit the starting surge current.

Last Answer : Answer: B

Description : Reduced voltage applied to a motor during the starting period will _____________. A. result in decreased acceleration time only B. lower the starting current and increase accelerating time C. cause a greater starting torque D. increase the starting current and pump capacity

Last Answer : Answer: B

Description : Across-the-line starters are used with AC motors to provide _____________. A. reduced starting current B. regulated starting current C. high starting torque D. controlled starting acceleration

Last Answer : Answer: C

Description : The rotor slots of a repulsion-type motor are generally skewed (placed nonparallel to the rotor axis) to _________. A. produce a constant starting torque B. permit a greater air gap with the starter C. permit a smaller air gap with the starter D. reduce eddy current losses

Last Answer : Answer: A