What are the settings provided in synchronizing scheme (SKE Relay)?

1 Answer

Answer :

Voltage – V1- V2 = 10%

Frequency – t = 0.05 Sec (2.5 Hz)

% Slip – 0.45

Phase angle difference - 20°. 

Related questions

Description : Why synchronizing scheme has been adopted? What are interlocks provided?  

Last Answer : To check running and incoming buses, which are going to be interconnected are in synchronism with each other. Interlocks 1. Synch selector. 2. Only one breaker can operate at a time. 3. ... will bypass this synch contact). Bypass facility is provided to close the breaker on dead bus only. 

Description : A diesel driven emergency generator is prevented from being paralleled with the ship's service generators by __________. A. an electrical interlock system B. an automatic paralleling trip switch C. the synchronizing oscilloscope D. the reverse current relay

Last Answer : Answer: A

Description : The purpose of the reverse power relay, provided on a ship's service alternator panel, is to trip the circuit in the event of ______________. A. main circuit overload B. high power transfer C. generator overspeeding D. alternator motorization

Last Answer : Answer: D

Description : Protection against sustained overloads occurring in molded-case circuit breakers is provided by a/an __________. A. overvoltage release B. thermal acting trip C. thermal overload relay D. current overload relay

Last Answer : Answer: B

Description : Attempting to parallel an AC generator which is out of phase with the bus will result in which of the following problems? A. The breaker should trip. B. The KVA will decrease. C. The synchronizing lamps will burn out. D. The power factor will be unitized.

Last Answer : Answer: A

Description : A current-carrying conductor makes accidental contact with a wiring conduit. This will be indicated by a _____________. A. low switchboard wattmeter reading B. high switchboard wattmeter reading C. darkened switchboard ground detecting lamp D. darkened switchboard synchronizing lamps

Last Answer : Answer: C

Description : When paralleling two alternators, the synchronizing lamps remain lit as the synchroscope pointer approaches the 0°. This indicates the _____________. A. incoming alternator is running too fast B. alternator ... apart C. synchroscope is defective or broken D. alternator power factors are in phase

Last Answer : Answer: C

Description : When paralleling two alternators the synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates the ____________. A. alternator voltages ... alternator is in phase with the bus voltage D. synchroscope pointer is defective or broken

Last Answer : Answer: C

Description : When paralleling two alternators using three synchronizing lamps, the flickering of all three lamps becomes progressively slower and slower. This means the ______________. A. frequency of the incoming ... the bus D. terminal voltage of the incoming alternator is approaching that of the bus

Last Answer : Answer: A

Description : An AC generator panel is fitted with both synchronizing lamps and a synchroscope. When the synchroscope pointer reaches the noon position, one synchronizing light is bright and the other is dark. This ... sequence is incorrect C. the phase sequence is correct D. the generator breaker may be closed

Last Answer : Answer: B

Description : You are paralleling two alternators. The synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates that the ____________. A. alternator ... be closed C. incoming alternator is running too slowly D. synchroscope is defective or broken

Last Answer : Answer: B

Description : While paralleling two (2) AC generators using synchronizing lamps only, both lamps will go dark when the generators are ____________. A. running at the same speed B. grounded C. of the same polarity D. in phase

Last Answer : Answer: D

Description : The voltage of an operating AC turbogenerator is raised or lowered by adjusting the _____________. A. exciter generator governor controls B. synchronizing switch C. phase sequence switch D. generator field exciter

Last Answer : Answer: D

Description : As shown in the illustrations, feedback or rudder angle repeatback is used by the steering stand in which operational modes? EL-0097 A. Gyro-compass and hand steering only B. Hand steering and non-followup only C. Non-followup and gyro-compass only D. Gyro-compass and synchronizing only

Last Answer : Answer: A

Description : How synchronoscope is used for synchronizing Alternators?

Last Answer : Synchronoscope can be used for permanently connected Alternators where the correctness of phase sequence is already checked by other means. The rotation of pointer is proportional to the difference in ... alternator is running slow. If the difference in frequency is large the pointer will oscillate

Description : What are the advantages and disadvantages of three dark lamps method of synchronizing?

Last Answer : Advantages: · The synchronous switch using lamps is inexpensive · Checking for correctness of the phase sequence can be obtained in a simple manner which is essential especially when the Alternator ... The frequency of the incoming Alternator in relation to the bus-bar frequency is not available.

Description : What is synchronizing?

Last Answer : The operation of connecting an alternator in parallel with another alternator or with common bus bars is known as synchronizing.

Description : What are the methods of synchronizing?

Last Answer : a. Lamp method. Dark lamp method and bright lamp method. b. Synchroscope method.

Description : A series resistance is added to the over-current relay in a bus bar differential protection scheme which: a. Helps to develop some voltage across it which otherwise should appear across the relay and is ... the effects of CT saturation and lowers the pickup value of the relay d. All of the above 

Last Answer : A series resistance is added to the over-current relay in a bus bar differential protection scheme which: a. Helps to develop some voltage across it which otherwise should appear across the relay and is ... the effects of CT saturation and lowers the pickup value of the relay d. All of the above 

Description : Which of the following services is NOT provided by the post offices in India ? A. Savings Bank Scheme B. Retailing of Mutual Funds C. Sale of stamp Papers (Judicial) D. Issuance of Demand Drafts E. Life Insurance cover

Last Answer : D. Issuance of Demand Drafts Explanation: Issuance of Demand Drafts is NOT provided by the post offices in India.

Description : In order to promote the participation of students in agricultural business, Student scheme is being run, under which practical experience of agriculture is provided to undergraduate students, what does “E” stand for in READY? a. Export b. Empowerment c. Enlightenment d. Entrepreneurship

Last Answer : d. Entrepreneurship

Description : In order to promote the participation of students in agricultural business, Student scheme is being run, under which practical experience of agriculture is provided to undergraduate students, what does “E” stand for in READY? a. Export b. Empowerment c. Enlightenment d. Entrepreneurship

Last Answer : d. Entrepreneurship

Description : The KW load is evenly distributed between two alternators just placed in parallel by adjusting _____________. A. a balance coil B. the governor settings C. the field excitation D. a rheostat

Last Answer : Answer: B

Description : If two AC generators have just been placed in parallel, the true power load is initially distributed evenly by _____________. A. a balance coil B. changing field excitation C. adjusting the governor control settings D. a rheostat

Last Answer : Answer: C

Description : The division of the kilowatt load between two AC generators operating in parallel is controlled by the settings and characteristics of the _____________. A. voltage regulators B. field rheostats C. reverse power relays D. prime mover governors

Last Answer : Answer: D

Description : The load sharing characteristics of two diesel generators operating in parallel are mostly dependent on their governor ____________. A. load limit settings B. idle speed settings C. speed limit settings D. speed droop settings

Last Answer : Answer: D

Description : What are the torque settings used in IPBD connection?

Last Answer : M12 (Nut bolt) 4506 100 kg-cm or 55 NM M16 (Nut bolt) 9006 250 kg-cm or 80 NM M20 (Nut bolt) 18006300 kg-cm or 100 NM 

Description : A CRO screen has ten divisions on the horizontal scale. If a voltage signal 5 sin 314t+45 deg)is examined with a line base settings of 5 msec/div, the number of cycles of signal displayed on the screen will be a) 0.5 cycles b) 2.5 cycles c) 5 cycles d) 10 cycles

Last Answer : Ans: 2.5 cycles

Description : Synchronizing iCal to Google Calendar?

Last Answer : get on http://Digg.com they have an article talking about how you can do it. Just search iCal.

Description : How would one squeeze more channels of communication into TDM frames of standard length? A. Shorten the time delay for each channel B. Raise the amplitude C. Add modulators D. Remove the synchronizing pulses

Last Answer : A. Shorten the time delay for each channel

Description : The process of converting analog signals into digital signals so they can be processed by a receiving computer is referred to as: a. modulation b. demodulation c. synchronizing d. digitising

Last Answer : digitising

Description : The process of converting analog signals into digital signals so they can be processed by a receiving computer is referred to as a. modulation b. demodulation c. synchronizing d. Digitizing

Last Answer : b. demodulation

Description : What is the purpose of a synchronizing network in a servo system?

Last Answer : To switch control of the amplifier between either the coarse signal and the fine error signal.

Description : After a black out the emergency generator comes on; On restoring the main supply we are closing the circuit breaker of the main generator without bothering about synchronizing. How is this possible?

Last Answer : There is a power link connection breaker between the main generator and the emergency generator. During black out, this breaker trips. The emergency generator starts and its breaker closes and feeds only ... , there is no paralleling between main and emergency generator. Ask E/O for more details.

Description : What is dark lamp and bright lamp method for synchronizing? How is the connection made?

Last Answer : Formerly, three light bulbs were connected between the generator terminals and the system terminals. As the generator speed changes, the lights will rise and fall in intensity at a rate proportional to ... to the system may be closed and the generator will then stay in synchronism with the system.

Description : ____________ carries signalling and synchronizing commands. a) Traffic channels b) Control channels c) Signalling channels d) Forward channels

Last Answer : b) Control channels

Description : why equalizing pulses are needed. Draw the vertical synchronizing pulse structure.

Last Answer : The ½ line difference just prior to the start of serrated vertical pulse does not affect the horizontal deflection synchronization but it does affect the vertical synchronization and the interlaced scanning. The ... the vertical sync pulse to occur at the correct time after every field.

Description : For distribution network which type of Switching scheme is employed?

Last Answer : For distribution network Ring Main busbar scheme is employed. It has the provision that if power interruption occurs to one bus section due to maintenance or fault, power can be fed the bus from other side of the power system.

Description : Give two basic speed control scheme of DC shunt motor?

Last Answer : Answer: 1. By using flux control method: in this method a rheostat is connected across the field wdg to control the field current. So by changing the current the flux produced by the field wdg can ... ) can be varied, and since speed is directly proportional to Eb-IaRa the speed can be controlled.

Description : What parameters or technical particulars are important to be considered while designing protection scheme of the transformer?

Last Answer : 1.Network Diagram showing the position of the transformer in the system 2.kVA or MVA rating of the transformer 3.Fault Level at the transformer 4.Voltage Ratio 5.Winding Connections 6.Per Unit ... Oil Filled 11.Length and area of cross section of the connecting leads between CTs and Relay Panel

Description : Mention any two disadvantage of carrier current scheme for transmission line only.

Last Answer : The program time (ie, the time taken by the carrier to reach the other end-upto .1% mile); the response time of band pass filter; capacitance phase-shift of the transmission line .

Description : Mention the short comings of Merz Price scheme of protection applied to a power transformer.

Last Answer : In a power transformer, currents in the primary and secondary are to be compared. As these two currents are usually different, the use of identical transformers will give differential current, and ... turn-ratio are used, the differential current may flow through the relay under normal condition.

Description : What are the uses of EMTR scheme? 

Last Answer : 1. To restore class III when class IV supply fails. 2. To extend supply to class II when UPS fails. 3. In one DG condition to load restoration. 4. Sub sequent restoration of large motor loads. 

Description : What are the conditions for Auto transfer scheme?

Last Answer : Backup protections are not allowed to initiate the Auto transfer. Because under voltage may exist in the bus. Similarly protection in LV of the transformers are not initiating the Auto transfer scheme. There are three metrics used ... in GT. 4. Fault in 220 kV bus (SUT). 5. Fault in SUT (86M).  

Description : What are the types Auto transfer scheme?

Last Answer : 1. Fast transfer scheme to close the tie-breaker in less than 200 milli seconds. This limits transient current and voltage dip in the bus and does quick acceleration of the motors. 2. Slow transfer after 200 milli seconds.  

Description : Why stabilising resistor in REF or residual E/F scheme? 

Last Answer : Required against CT saturation under heavy through fault currents.  

Description : In accordance with Coast Guard Regulations (46 CFR), each battery operated relay-controlled lantern must _____________. A. be readily portable B. contain a dry cell battery having a minimum capacity of ... automatic battery charger to maintain the battery in a fully charged state D. all of the above

Last Answer : Answer: C

Description : As shown in the illustration, once the "LV" relay is energized for operation, what contacts must remain closed to maintain the "LV" relay energized when the control lever is moved away from the "off" or "stop" ... . B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C