Why delta – delta CT’s are used for star – star transformer differential protection?

1 Answer

Answer :

Say primary neutral is not solidly earthed. Then for any earthfault on secondary terminal, the primary current distribution is so for external fault, the differential is likely to operate if sequence current from flowing into relay. The 2:1:1 distribution is possibly only for core type or delta tertiary.

Related questions

Description : What are the problems arising in differential protection in power transformer and how are they overcome?

Last Answer : 1. Difference in lengths of pilot wires on either sides of the relay. This is overcome by connecting adjustable resistors to pilot wires to get equipotential points on the pilot wires. 2. ... harmonic restraining unit is added to the relay which will block it when the transformer is energized.

Description : What is the difference between delta-delta, delta-star transformer?

Last Answer : A. Delta-delta transformer is used at generating station or a receiving station for Change of Voltage (i,e) generally it is used where the Voltage is high & Current is low whereas Delta-star ... star neutral is taken as a return path and this configuration is used for Step down voltage phenomena.

Description : Why Delta Star transformer Are Used For Lighting Loads?

Last Answer : For lighting loads, neutral conductor is must and hence the secondary must be star winding. and this lighting load is always unbalanced in all three phases. To minimize the current unbalance in the primary we use delta winding in the primary. So delta / star trformer is used for lighting loads.

Description : Why input transformer of PUPS module 1 is delta-delta and module 2 is delta-star?

Last Answer : With the help of this arrangement, combined DC output from both chargers is equivalent to that from a 12-pulse rectifier. Advantage of 12-pulse rectifier is that the mains current is fairly close ... phase angle difference 30-degree between module 1 output and module 2 output give 12-pulse output. 

Description : In a three phase transformer, if the primary side is connected in star and secondary side is connected in delta, what is the angle difference between phase voltage in the two cases. (A) delta side lags by -30°. (B) star side lags by -30°. (C) delta side leads by 30°. (D) star side leads by -30°.

Last Answer : Ans: C This is vector group and has +30° displacement. Therefore, delta side leads by +30°.

Description : For which of the following ratings of the transformer differential protection is recommended ? (a) above 30 kVA. (b) equal to and above 5 MVA (c) equal to and above 25 MVA (d) none of the above

Last Answer : (b) equal to and above 5 MVA

Description : List two limitations of Differential-Protection scheme for transformer.

Last Answer : Limitations of Differential Protection Scheme of Transformer:  1) Due to the magnetization characteristics of the CTs used, the ratio errors change with respect to the circulating currents.  2) ... & improper operation.  5) Inrush of magnetizing current may lead to inadvertent operation.

Description : Write down limitation of differential protection of transformer.

Last Answer : Limitations of differential protection of transformer: 1) Due to the magnetization characteristics of the CTs used, the ratio errors change with respect to the circulating currents. 2) The pilot wires ... current (higher imbalance) due to which accuracy of sensing & operation is decreased. 

Description : To protect the power transformer (Y-Y with neutral grounded) against fault, what type of connection do the CTs have ?

Last Answer : To protect the power transformer (Y-Y with neutral grounded) against fault, what type of connection do the CTs have ? Δ-Δ connection

Description : Explain differential protection?

Last Answer : Differential protection is based on the fact that any fault within an electrical equipment would cause the current entering it, to be different, from that leaving it. Thus, we can compare the two ... phase or both and issue a trip output if the difference exceeds a pre- determined set value.

Description : What are the problems in bus zone differential protection?

Last Answer : Large number of circuits, different current levels for different circuits for external faults. Saturation of CT cores due to dc component and ac component in short circuit currents. The saturation ... the bus makes circuit complicated. Setting of relays need a change with large load changes.

Description : What is the coverage of differential protection for SUT?

Last Answer : Covers from 230 kV bushing to 6.6 kV breaker end.  

Description : What is differential protection? 

Last Answer : It is the current balance type protection, in which vector difference between current entering the winding is used for relay operation. 

Description : Why differential protection for PHT motors?

Last Answer : For more than 2500 kW motors it is required to provide differential protection. It is biased Relay against internal phase fault or earth fault very fast. Insensitive to starting current and stalling current. 

Description : Why inter-turn protection is provided along with differential protection in generator?

Last Answer : Inter-turn protects two separate windings from the fault of the generator.  

Description : for Delta-Star connection of 3-phase transformer: i) Draw the connection diagram ii) List any two advantages of this connection iii) State its area of application. 

Last Answer : Disadvantages: i) In this type of connection, the secondary voltage is not in phase with the primary. Hence it is not possible to operate this connection in parallel with star-star or delta-delta ... iv) As line current is equal to phase current the conductor size of winding should be large. 

Description : A three-phase transformer, connected in star-delta, is composed of three single-phase transformers, each rated 127/ 13.2 kV. The line-to-line voltage ratio for the three-phase transformer is: A) 220 / 13.2 kV B) 127 / 13.2 kV C) 127 / 220 kV D) 220 / 220 kV

Last Answer : A three-phase transformer, connected in star-delta, is composed of three single-phase transformers, each rated 127/ 13.2 kV. The line-to-line voltage ratio for the three-phase transformer is: 220 / 13.2 kV 

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Last Answer : Delta/star transformer works satisfactorily when on balanced as well as unbalanced loads.

Description : Figure 'A' of the diagram shown in the illustration represents a ______________. EL-0092 A. differential transformer B. saturable reactor C. synchro system D. magnetic amplifier

Last Answer : Answer: C

Description : What is advantage of cast resin CT’s? 

Last Answer : Can withstand bursting forces under short ckt, protect damages against external causes impervious to moisture.  

Description : What is the various design of CT's in switchyard?

Last Answer : Bus coupler CT's- live tank design 2000-1000A/1A All other CT's- dead tank design 800-600-400A/1A - lines and GT. 125A/1A – SUT

Description : Why core balance CT is preferred over residual connected CT’s to sense earth fault in 6.6 kV feeders?

Last Answer : a) To avoid relay mal-operation due to CT saturation b) Better sensitivity is got. c) High pickup and TMS avoided in IDMT earth fault relay. 

Description : Where core balance CT’s are used? 

Last Answer : In earth fault protection used. It senses the zero sequence current.  

Description : What is the advantage of housing CT’s with in bushings? 

Last Answer : Bushing acts as a primary insulator for the CT.  

Description : Mention the initial commissioning checks on CT’s, PT’s and relays.

Last Answer : Commissioning checks on CT a) Terminal marking correctness. b) Polarity of terminals. c) Insulation resistance between primary and secondary. d) Insulation resistance between primary to earth and secondary ... h) Burden check of relay. i) Primary injection test. j) Secondary injection test. 

Description : The electrical schematic illustrated in figure A, depicts a/an _____________. EL-0059 A. autotransformer B. Delta Wye transformer C. primary EMF generator D. potential transformer

Last Answer : Answer: D

Description : In a three-phase, open-delta connected transformer, the line current is equal to _____________. A. the phase current B. three times the phase current C. the sum of any two phase currents D. the difference of any two phase currents

Last Answer : Answer: A

Description : If P is the power of a star connected system then what will be power of an equivalent delta connected system? A..P B. 3P C. P/3 D. None of the above

Last Answer : Ans: A

Description : Disadvantages of Star-Delta Starting of Induction motor?

Last Answer : In Star-Delta starting induction motor stator is connected in star connection for starting after picking up speed it is connected to delta connection. When induction motor is connected in star connection ... . This also results in reduced starting torque (1/3 times compared to delta connection).

Description : What advantage has the star connection over the delta connection ?

Last Answer : A. Each star connection transformer is wound for only 57.7% of line voltage . In hv transmission, this admits of much smaller transformer being built for high voltage than possible with delta connection, because of less insulation.

Description : Why Delta Star Transformers are used for Lighting Loads?

Last Answer : A. For lighting loads, neutral conductor is must and hence the secondary must be star winding.This lighting load is always unbalanced in all three phases. To minimize the current unbalance in the primary we use delta winding in the primary. So delta / star transformer is used for lighting loads.

Description : State the voltage and current relation in star and delta connection. 

Last Answer : In star connection line current is equal to the phase current and line voltage is √3 times that of phase voltage. In delta connection line voltage is equal to the phase voltage and line current is √3 times that of phase current. 

Description : What are the value of voltage and current in star connection and in delta connection?

Last Answer : Star connection a. IL = IPh. b. VL = √3 VPh. ∴ VPh = VL/√3. Note: in star connection we are getting neutral point and we can able to measure the phase as well as line voltage. Delta connection a. VL = VPh. b. IL = √3 IPh. ∴ IPh = IL/√3.

Description : What are the advantages of star-delta starter with induction motor?

Last Answer : The main advantage of using the star delta starter is reduction of current during the starting of the motor. Starting current is reduced to 3-4 times of current of Direct online starting Hence the starting current is reduced , the voltage drops during the starting of motor in systems are reduced

Description : Why Delta Star Transformers are used for Lighting Loads?

Last Answer : For lighting loads, neutral conductor is must and hence the secondary must be star winding and this lighting load is always unbalanced in all three phases.  To minimize the current unbalance in the primary we use delta winding in the primary So delta / star transformer is used for lighting loads.

Description : Why star delta starter is preferred with induction motor?

Last Answer : Star delta starter is preferred with induction motor due to following reasons: Starting current is reduced 3-4 times of the direct current due to which voltage drops and hence it causes less ... caused. In addition, starting torque is increased and it prevents the damage of motor winding.

Description : ECE Board Exam March 1996 Which of the following pulse modulation systems is analog? A. Delta B. Differential PCM C. PWM D. PCM

Last Answer : C. PWM

Description : What parameters or technical particulars are important to be considered while designing protection scheme of the transformer?

Last Answer : 1.Network Diagram showing the position of the transformer in the system 2.kVA or MVA rating of the transformer 3.Fault Level at the transformer 4.Voltage Ratio 5.Winding Connections 6.Per Unit ... Oil Filled 11.Length and area of cross section of the connecting leads between CTs and Relay Panel

Description : How Transformer Protection provided for internal faults?

Last Answer : 1.Bucholz Relay (1st Stage Alarm and 2nd Stage Trip) 2.Sudden Pressure Relay (1st Stage Alarm and 2nd Stage Trip) 3.Pressure Relief Valve (1st Stage Alarm and 2nd Stage Trip) 4.Pressure Switch ... 8.Gas Temperature Indicator (Alarm) 9.Silicon Breather (Passive - no alarm) 10.Smoke Detector (Alarm)

Description : What is over fluxing protection in transformer?

Last Answer : If the turns ratio of the transformer is more than 1:1, there will be higher core loss and the capability of the transformer to withstand this is limited to a few minutes only. This phenomenon is called over fluxing.

Description : Mention the short comings of Merz Price scheme of protection applied to a power transformer.

Last Answer : In a power transformer, currents in the primary and secondary are to be compared. As these two currents are usually different, the use of identical transformers will give differential current, and ... turn-ratio are used, the differential current may flow through the relay under normal condition.

Description : What is the in built protection for transformer?

Last Answer : PRV to protect from over pressurization of tank due to the release of gases, oil etc. This is the replacement for the explosion vent. 

Description : Why do we use O/C & E/F protection on both sides of transformer?

Last Answer : Power in feed exists on both ends.  

Description : Large internal faults are protected by (a) merz price percentage differential protection (b) mho and ohm relays (c) horn gaps and temperature relays (d) earth fault and positive sequence relays

Last Answer : (a) merz price percentage differential protection

Description : Explain the “Differential Protection Scheme” used for alternators with neat labeled diagram.

Last Answer : Differential Protection Scheme for Alternator: Figure shows the differential protection provided to 3 phase alternator. Here identical CTs are placed on both sides of 3 phase alternator and ... causing its operation. Relay sends trip signal to the CB, thereby alternator circuit is tripped.

Description : Explain differential protection scheme for busbars with neat sketch.

Last Answer : Differential Protection Scheme for Bus bar:  Under normal conditions, the sum of the currents entering the bus bar zone is equal to those leaving it and no current flows through the relay ... of these currents will flow through the relay coil causing opening of circuit breaker of bus-bar.

Description : Explain differential protection of busbar.

Last Answer : Differential protection Scheme for bus bar: Under normal conditions the sum of the currents entering the bus bar zone is equal to those leaving it and no current flows through the relay ... . The difference of these currents will flow through the relay coil causing opening of circuit breaker.

Description : A series resistance is added to the over-current relay in a bus bar differential protection scheme which: a. Helps to develop some voltage across it which otherwise should appear across the relay and is ... the effects of CT saturation and lowers the pickup value of the relay d. All of the above 

Last Answer : A series resistance is added to the over-current relay in a bus bar differential protection scheme which: a. Helps to develop some voltage across it which otherwise should appear across the relay and is ... the effects of CT saturation and lowers the pickup value of the relay d. All of the above