What are the value of voltage and current in star connection and in delta connection?

1 Answer

Answer :

Star connection
a. IL = IPh.
b. VL = √3 VPh. ∴ VPh = VL/√3.
Note: in star connection we are getting neutral point and we can able to measure
the phase as well as line voltage.
Delta connection
a. VL = VPh.
b. IL = √3 IPh. ∴ IPh = IL/√3.

Related questions

Description : State the voltage and current relation in star and delta connection. 

Last Answer : In star connection line current is equal to the phase current and line voltage is √3 times that of phase voltage. In delta connection line voltage is equal to the phase voltage and line current is √3 times that of phase current. 

Description : What advantage has the star connection over the delta connection ?

Last Answer : A. Each star connection transformer is wound for only 57.7% of line voltage . In hv transmission, this admits of much smaller transformer being built for high voltage than possible with delta connection, because of less insulation.

Description : In a three phase transformer, if the primary side is connected in star and secondary side is connected in delta, what is the angle difference between phase voltage in the two cases. (A) delta side lags by -30°. (B) star side lags by -30°. (C) delta side leads by 30°. (D) star side leads by -30°.

Last Answer : Ans: C This is vector group and has +30° displacement. Therefore, delta side leads by +30°.

Description : Draw the star and delta connection. State any one conversion formula.

Last Answer : star and delta connection

Description : for Delta-Star connection of 3-phase transformer: i) Draw the connection diagram ii) List any two advantages of this connection iii) State its area of application. 

Last Answer : Disadvantages: i) In this type of connection, the secondary voltage is not in phase with the primary. Hence it is not possible to operate this connection in parallel with star-star or delta-delta ... iv) As line current is equal to phase current the conductor size of winding should be large. 

Description : Compare star and Delta Connection.

Last Answer : Compare Star and Delta connected system:  Star connected system Delta connected system   In STAR connection, the starting or finishing ends (Similar ends) of three coils are connected together to form the ... VPH Line Current is √3 times of Phase Current. i.e. IL = √3 IPH

Description : What is difference between Star and Delta Connection?

Last Answer : Star is        1. Open ckt       2. At center point present  neutral   Delta is     1.   Closed ckt 2.      Neutral not present in this case 

Description : One important difference between wye-connected and delta-connected generators is that delta connections have ____________. A. line voltages equal to the vector sum of the phase voltages B. phase voltages 90° ... C. line current equal to the phase current D. line voltage equal to the phase voltage

Last Answer : Answer: D

Description : What is the advantage is obtained in the delta connection ?

Last Answer : A. When three transformer are obtained in delta, one may be removed and two remaining unit will carry 57.7% of the original three phase load and thus maintain the continuity of supply.

Description : Write the relation between phase and line current, phase and line voltage for Star connection.

Last Answer : Line voltage is equal to root three times of phase voltage and line and phase currents are equal in star connection

Description : If P is the power of a star connected system then what will be power of an equivalent delta connected system? A..P B. 3P C. P/3 D. None of the above

Last Answer : Ans: A

Description : Disadvantages of Star-Delta Starting of Induction motor?

Last Answer : In Star-Delta starting induction motor stator is connected in star connection for starting after picking up speed it is connected to delta connection. When induction motor is connected in star connection ... . This also results in reduced starting torque (1/3 times compared to delta connection).

Description : Why Delta Star Transformers are used for Lighting Loads?

Last Answer : A. For lighting loads, neutral conductor is must and hence the secondary must be star winding.This lighting load is always unbalanced in all three phases. To minimize the current unbalance in the primary we use delta winding in the primary. So delta / star transformer is used for lighting loads.

Description : What is the difference between delta-delta, delta-star transformer?

Last Answer : A. Delta-delta transformer is used at generating station or a receiving station for Change of Voltage (i,e) generally it is used where the Voltage is high & Current is low whereas Delta-star ... star neutral is taken as a return path and this configuration is used for Step down voltage phenomena.

Description : Why Delta Star transformer Are Used For Lighting Loads?

Last Answer : For lighting loads, neutral conductor is must and hence the secondary must be star winding. and this lighting load is always unbalanced in all three phases. To minimize the current unbalance in the primary we use delta winding in the primary. So delta / star trformer is used for lighting loads.

Description : Why input transformer of PUPS module 1 is delta-delta and module 2 is delta-star?

Last Answer : With the help of this arrangement, combined DC output from both chargers is equivalent to that from a 12-pulse rectifier. Advantage of 12-pulse rectifier is that the mains current is fairly close ... phase angle difference 30-degree between module 1 output and module 2 output give 12-pulse output. 

Description : Why delta – delta CT’s are used for star – star transformer differential protection?

Last Answer : Say primary neutral is not solidly earthed. Then for any earthfault on secondary terminal, the primary current distribution is so for external fault, the differential is likely to operate if sequence current ... into relay. The 2:1:1 distribution is possibly only for core type or delta tertiary.

Description : What are the advantages of star-delta starter with induction motor?

Last Answer : The main advantage of using the star delta starter is reduction of current during the starting of the motor. Starting current is reduced to 3-4 times of current of Direct online starting Hence the starting current is reduced , the voltage drops during the starting of motor in systems are reduced

Description : Why Delta Star Transformers are used for Lighting Loads?

Last Answer : For lighting loads, neutral conductor is must and hence the secondary must be star winding and this lighting load is always unbalanced in all three phases.  To minimize the current unbalance in the primary we use delta winding in the primary So delta / star transformer is used for lighting loads.

Description : Why star delta starter is preferred with induction motor?

Last Answer : Star delta starter is preferred with induction motor due to following reasons: Starting current is reduced 3-4 times of the direct current due to which voltage drops and hence it causes less ... caused. In addition, starting torque is increased and it prevents the damage of motor winding.

Description : Which of the following statements about a three-phase wye connection is correct? A. The line current is 1.73 times the phase current. B. The phase current is 1.73 times the line current. C. The line voltage is 1.73 times the phase voltage. D. The phase voltage is 1.73 times the line voltage.

Last Answer : Answer: C

Description : To properly use a hook-on-type volt/ammeter to check current flow, you must FIRST _____________. A. de-energize the circuit to allow connection of the instrument in series B. hook the jaws ... test leads to the appropriate terminals D. short the test leads and calibrate the instrument to zero

Last Answer : Answer: B

Description : In testing a three-phase delta winding for an open circuit using a megohmmeter, you must ______________. A. test each phase with all connections intact B. measure the voltage across the open ... groups to avoid short circuiting D. open the delta-connections to avoid shunting the phase being tested

Last Answer : Answer: D

Description : Three resistances of 3 Ω each are connected in delta. The value of the resistances in the equivalent star is : (A) 27 (B) 9 (C) 1.5 (D) 1 Ω

Last Answer : 9

Description : The line voltage EL in a star connection is equal to.... (Ep = phase voltage)

Last Answer : The line voltage EL in a star connection is equal to √3 .Ep (Ep = phase voltage)

Description : In a three-phase, open-delta connected transformer, the line current is equal to _____________. A. the phase current B. three times the phase current C. the sum of any two phase currents D. the difference of any two phase currents

Last Answer : Answer: A

Description : Current measuring instruments must always be connected in _____________. A. series with a circuit B. parallel with a circuit C. series-parallel with a circuit D. delta with the shunt

Last Answer : Answer: A

Description : What will happen if transformer in parallel connection have different voltage ratio?

Last Answer : Two transformers in Parallel should have the same primary and secondary voltage ratings. Any error in the voltage ratio would cause heavy circulating currents to flow between the transformers. ... in overloading of one transformer. This circulating current will result in increased copper losses.

Description : What is Delta Connection ?

Last Answer : When three resistors are connected in such a way that a closed loop is formed by connecting the first end of one resistor to the second end of the other resistor and a line or lead is drawn from each connection point then it is called delta connection.

Last Answer : Advantages of open delta connection of 3-phase transformer:  1. When one of the phase in case of delta-delta bank is out of order by any reason, the service will be continued till ... demand in future (about 33%) will be supplied by converting open delta connection to delta-delta connection.

Description : Write the formula from Star to Delta ?

Last Answer : Answer : Dividing the product of the resistors connected to the star by dividing the resistors of the opposite arm by taking two together, the quotient is equal to the value of each resistor connected.

Description : What equipment are star delta starters used in?

Last Answer : Star Delta starter is used to start the AC motors with rating generally higher than 11 kw, depending upon the type of load.

Description : What is star / delta ?*

Last Answer : In star VL = √3 VΦ In delta VL = VΦ

Description : Is the alternator connected star or delta

Last Answer : Look up in Dennis T Hall. Also in your ship ask E/O. Normally star.

Description : If a motor is wound star and you want to change to delta what should you do?

Last Answer : Open the terminal connection box. Remove the shorting link connecting the common connection (star) point of A2, B2 and C2. With the 3 phase windings marked A1A2, B1B2, C1C2, connect A2 to B1, B2 to C1 and C2 to A1.

Description : Is the ship's alternator Star wound or Delta wound?

Last Answer : Refer Dennis T Hall

Description : What is the meaning of Star winding/ Delta winding?

Last Answer : Refer Dennis T Hall

Description : Convert the delta network into equivalent star network.

Last Answer : Delta to start network R1 = 4x6/ 4+6+2 = 24/12 =2/1= 2Ω R2 = 2x6/ 4+6+2 = 12/12= 1 = 1Ω R3 = 4x 2/ 4+6+2 = 8/12= 2/3= 0.66Ω

Description : Derive an expression for delta to star transformation. 

Last Answer : For delta network the resistance between the terminals 1 and 2 consists of R12 in parallel with  (R23+R31) Hence ,the resistance between the terminals 1 and 2 is In case of star network the ... equation( ii) from( i),we get Adding equations (iii) and( iv),we have 

Description : Calculate the equivalent resistance between A & B using star-delta conversion

Last Answer : Solution :  Converting Inner star in to delta-  Resistances 4 and 6 are in parallel in all branch so

Description : Develop the control circuit for star-delta starter used for starting a 3 ∅ induction motor.

Last Answer : Control Circuit for Star-Delta Starter: 1) Automatic Star-Delta Starter: OR 2) Semi- automatic Star-Delta Starter:

Description : Delta to Star Conversion Example

Last Answer : Delta to Star Conversion Example

Description : Wye (Star) to Delta Conversion

Last Answer : Wye (Star) to Delta Conversion

Description : Star to delta conversion examples

Last Answer : Star to delta conversion example 1

Description : Draw and explain star delta starter for 3 phase induction motor

Last Answer : Star Delta Starter for 3 Phase Induction Motor:  Diagram Explanation: The stator winding of the motor which is designed for delta operation is connected in star during starting ... which connects stator windings in delta connection. Now each stator phase gets full line voltage VL.

Description : Describe the power and control circuit for automatic Star-Delta starter for 3-phase induction motor.

Last Answer : Power circuit: Control circuit: 

Description : Can you guys explain the advantages of frequency converter against the star delta or soft starter?

Last Answer : ¬Soft starters  A soft starter is, as you would expect, a device which ensures a soft starting of a motor. A softstarter has different characteristics to the other starting ... at rated current from zero to full speed. Frequency converters are becoming cheaper all the time.

Description : A three-phase transformer, connected in star-delta, is composed of three single-phase transformers, each rated 127/ 13.2 kV. The line-to-line voltage ratio for the three-phase transformer is: A) 220 / 13.2 kV B) 127 / 13.2 kV C) 127 / 220 kV D) 220 / 220 kV

Last Answer : A three-phase transformer, connected in star-delta, is composed of three single-phase transformers, each rated 127/ 13.2 kV. The line-to-line voltage ratio for the three-phase transformer is: 220 / 13.2 kV 

Description : Consider the following statements: Star delta starter is used in 3-phase induction motor because it  1. Prevents heating of the motor winding  2. Ensures permissible minimum starting current  3. Is regulated by electricity ... and 4 are correct (c) 1, 3 and 4 are correct (d) 1 and 2 are correct 

Last Answer : Consider the following statements: Star delta starter is used in 3-phase induction motor because it  1. Prevents heating of the motor winding  2. Ensures permissible minimum starting current  3. Is regulated by ... and 4 are correct (c) 1, 3 and 4 are correct (d) 1 and 2 are correct 

Description : If an unsymmetrical line to ground fault occurs at the secondary terminals of a delta/star, ungrounded transformer, then  (A) zero sequence currents are present on both sides of the transformer  (B) ... side  (D) zero sequence currents are present on the primary side but not on the secondary side

Last Answer : If an unsymmetrical line to ground fault occurs at the secondary terminals of a delta/star, ungrounded transformer, then zero sequence currents are absent on both sides of the transformer