What is the in built protection for transformer?

1 Answer

Answer :

PRV to protect from over pressurization of tank due to the release of gases, oil etc.

This is the replacement for the explosion vent. 


Related questions

Description : What parameters or technical particulars are important to be considered while designing protection scheme of the transformer?

Last Answer : 1.Network Diagram showing the position of the transformer in the system 2.kVA or MVA rating of the transformer 3.Fault Level at the transformer 4.Voltage Ratio 5.Winding Connections 6.Per Unit ... Oil Filled 11.Length and area of cross section of the connecting leads between CTs and Relay Panel

Description : How Transformer Protection provided for internal faults?

Last Answer : 1.Bucholz Relay (1st Stage Alarm and 2nd Stage Trip) 2.Sudden Pressure Relay (1st Stage Alarm and 2nd Stage Trip) 3.Pressure Relief Valve (1st Stage Alarm and 2nd Stage Trip) 4.Pressure Switch ... 8.Gas Temperature Indicator (Alarm) 9.Silicon Breather (Passive - no alarm) 10.Smoke Detector (Alarm)

Description : What is over fluxing protection in transformer?

Last Answer : If the turns ratio of the transformer is more than 1:1, there will be higher core loss and the capability of the transformer to withstand this is limited to a few minutes only. This phenomenon is called over fluxing.

Description : What are the problems arising in differential protection in power transformer and how are they overcome?

Last Answer : 1. Difference in lengths of pilot wires on either sides of the relay. This is overcome by connecting adjustable resistors to pilot wires to get equipotential points on the pilot wires. 2. ... harmonic restraining unit is added to the relay which will block it when the transformer is energized.

Description : Mention the short comings of Merz Price scheme of protection applied to a power transformer.

Last Answer : In a power transformer, currents in the primary and secondary are to be compared. As these two currents are usually different, the use of identical transformers will give differential current, and ... turn-ratio are used, the differential current may flow through the relay under normal condition.

Description : Why delta – delta CT’s are used for star – star transformer differential protection?

Last Answer : Say primary neutral is not solidly earthed. Then for any earthfault on secondary terminal, the primary current distribution is so for external fault, the differential is likely to operate if sequence current ... into relay. The 2:1:1 distribution is possibly only for core type or delta tertiary.

Description : Why do we use O/C & E/F protection on both sides of transformer?

Last Answer : Power in feed exists on both ends.  

Description : Which of the following statements about Google App Engine (GAE) is INCORRECT. A. It's a Platform as a Service (PaaS) model. B. Automatic Scalability is built in with GAE. As ... s applications. So, applications can take advantage of reliability, performance and security of Google's infrastructure.

Last Answer : You can decide on how many physical servers required for hosting your application.

Description : Overfluxing protection is recommended for (a) distribution transformer (b) generator transformer of the power plant (c) auto-transformer of the power plant (d) station transformer of the power plant

Last Answer : (b) generator transformer of the power plant

Description : The inverse definite mean time relays are used for over current and earth fault protection of transformer against (a) heavy loads (b) internal short-circuits (c) external short-circuits (d) all of the above

Last Answer : (b) internal short-circuits

Description : For which of the following ratings of the transformer differential protection is recommended ? (a) above 30 kVA. (b) equal to and above 5 MVA (c) equal to and above 25 MVA (d) none of the above

Last Answer : (b) equal to and above 5 MVA

Description : List two limitations of Differential-Protection scheme for transformer.

Last Answer : Limitations of Differential Protection Scheme of Transformer:  1) Due to the magnetization characteristics of the CTs used, the ratio errors change with respect to the circulating currents.  2) ... & improper operation.  5) Inrush of magnetizing current may lead to inadvertent operation.

Description : Explain over-current protection of transformer.

Last Answer : Over-Current Protection of Transformer: Simple over-current & earth fault protection of transformer against external shortcircuit and excessive overloads is shown in the above figure. The ... trip command to the circuit breaker and the transformer is disconnected from load or fault.

Description : Write down limitation of differential protection of transformer.

Last Answer : Limitations of differential protection of transformer: 1) Due to the magnetization characteristics of the CTs used, the ratio errors change with respect to the circulating currents. 2) The pilot wires ... current (higher imbalance) due to which accuracy of sensing & operation is decreased. 

Description : State use of any four relays for the protection of traction transformer. 

Last Answer : Relays for the protection of traction transformers:  Inverse time over current relay as back up protection on primary (HV side) - over current protection of transformer and other equipment.  ... .  Buchholz relay - protection from incipient earth or inter winding faults inside the transformer

Last Answer : The inverse definite mean time relays are used for over current and earth fault protection of transformer against internal short-circuits.

Description : 19 Transformer cores are built up from laminations rather than from solid metal so that A. Oil penetrates the core more easily B. Eddy current loss is reduced C. Less lamination is required for the windings D. Turn ratio is higher than voltage ratio

Last Answer : B. Eddy current loss is reduced

Description : Emulsifier protection is associated with: a) Grounding protection b) Dielectric strength protection of cables and conductors c) Lightning protection d) Fire protection

Last Answer : Ans: D

Description : Where automatic restart does not present a hazard after a power failure, Coast Guard Regulations (46 CFR) require motor controllers for auxiliaries vital to the propelling equipment to be provided ... overload protection B. low voltage protection C. low voltage release D. reverse current protection

Last Answer : Answer: C

Description : Which of the spaces listed is defined as a 'location requiring an exceptional degree of protection' when considering the installation of shipboard electrical equipment? A. Machinery space B. Chart room C. Console room D. Accommodation space

Last Answer : Answer: A

Description : The wiring diagram for the motor starting circuit shown in the illustration indicates ______________. EL-0007 A. resistance starting B. reduced voltage starting C. low voltage protection D. low voltage release

Last Answer : Answer: C

Description : Which of the following statements is true concerning the motor controller diagram shown in the illustration? EL-0023 A. Terminal 'T2' is hot only on high speed. B. Both indicating lights will be lit on ... high speed operation only. D. 'L2' is always connected to 'T2' whenever the motor is running.

Last Answer : Answer: D

Description : The purpose of the automatic bus transfer shown in the illustration is to ___________. EL-0014 A. stepdown voltage to the lighting distribution panel B. provide emergency power to ... emergency switchboard from the main switchboard D. provide overcurrent protection to the lighting distribution panel

Last Answer : Answer: B

Description : Component F in the illustrated device is for _________. EL-0033 A. short circut protection B. latching the trip unit closed after resetting the breaker C. overload protection D. providing a flexible connection between the input terminal G and the tripping unit E

Last Answer : Answer: C

Description : A fuse will 'blow' if _____________. A. an electric motor is stopped suddenly by opening a switch B. the flow of current to the protection device is reversed C. the electrical current exceeds the rated value of the fuse D. unequal resistors are connected in parallel

Last Answer : Answer: C

Description : Periodic testing of circuit breakers is necessary to assure that a correctly rated and properly installed unit _________________. A. can trip faster as it increases in age B. will continue to provide ... not exceed its interrupting capacity D. be able to withstand at least 125% of applied voltage

Last Answer : Answer: B

Description : The 'reset' contacts of the master switch shown in the illustration provides the winch controller with ___________. EL-0102 A. low voltage release B. overload protection C. low voltage protection D. high power factor correction

Last Answer : Answer: C

Description : The speed of a series wound winch motor is controlled by ____________. A. varying the voltage applied to the motor B. the weight of the load on the cargo boom C. overcurrent protection devices in the motor D. a hydraulic speed-limiting governor

Last Answer : Answer: A

Description : The circuit shown in the illustration represents a ________. EL-0090 A. battery charging circuit B. synchronous exciter C. depth sounding unit D. cathodic protection system

Last Answer : Answer: D

Description : Which of the listed items will stop a motor due to a reduction in voltage and restart it when the voltage is restored to normal? A. Low voltage protection circuit B. Non-renewable link fuse C. Renewable link fuse D. Low voltage release circuit

Last Answer : Answer: D

Description : Impressed current cathodic protection is used on vessels instead of _________________. A. fire alarm systems B. repeated painting C. sacrificial zincs D. vacuum tube degaussing systems

Last Answer : Answer: C

Description : In an impressed current cathodic protection system, the anode is ____________. A. connected to the hull and deteriorates with time B. insulated from the hull and does not waste away C. connected to the hull but does not waste away D. insulated from the hull but deteriorates with time

Last Answer : Answer: B

Description : The amount of current flow required for the cathodic protection of a vessel is dependent upon the _________. A. amount of bare steel surface B. speed of the ship through the water C. temperature of the water D. all of the above

Last Answer : Answer: D

Description : The purpose of a magnetic relay is to _____________. A. open a circuit only in the event of overload B. remotely open and close contacts C. provide overcurrent protection during starting D. relay voltages at increased power

Last Answer : Answer: B

Description : RC time constant characteristics, as shown in the illustration, are important in _____________. EL-0086 A. bridge rectifiers for alternator excitation B. timing and pulse shaping circuits C. transistor power amplifier biasing D. motor controller overload protection

Last Answer : Answer: B

Description : The purpose of a motor undervoltage protection device is to _____________. A. prevent high armature current when power is restored B. start the motor at a very low voltage C. trip the load off the motor in case of fire D. protect personnel from low voltage shocks

Last Answer : Answer: A

Description : The purpose of an impressed current cathodic protection system aboard ship is to _______________. A. prevent corrosion of the hull, propeller, rudder and line shafting B. neutralize the vessel's ... the presence of salt air D. maintain a minimum constant alternator load to prevent overheating

Last Answer : Answer: A

Description : The type of control circuit that will not permit automatic restarting after power is restored, following a power failure is called _____________. A. low voltage protection B. low voltage release C. overload lockout D. reduced voltage restart

Last Answer : Answer: A

Description : The type of feature afforded auxiliaries vital to the operation of propelling equipment, where automatic restart after a voltage failure would not create a hazard, is termed _____________. A. low voltage protection B. high amperage protection C. low voltage release D. high amperage release

Last Answer : Answer: C

Description : Fuses placed in series with a thermal trip-type circuit breaker are used for _____________. A. time-delay protection B. short-circuit protection C. short duration surge protection D. sustained overload protection

Last Answer : Answer: B

Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button

Last Answer : Answer: D

Description : A low-voltage protection circuit is used in electric motor starting equipment to _____________. A. trip circuit contactors when the motor overspeeds due to low voltage B. trip circuit ... voltage without manually resetting D. prevent the motor from restarting automatically on restoration of voltage

Last Answer : Answer: D

Description : Protection against sustained overloads occurring in molded-case circuit breakers is provided by a/an __________. A. overvoltage release B. thermal acting trip C. thermal overload relay D. current overload relay

Last Answer : Answer: B

Description : A molded-case circuit breaker provides protection against short circuits by using a/an ________________. A. electromagnet B. shading coil C. arc quencher D. burn away strip

Last Answer : Answer: A

Description : A molded-case breaker provides protection against short circuits by using a/an ____________. A. shading coil B. arc quencher C. electromagnet D. holding coil

Last Answer : Answer: C

Description : How the electrical power system protection is divided?

Last Answer : The overall system protection is divided into • Generator protection • Transformer protection • Busbar protection • Transmission line protection and • Feeder protection

Description : What are the different relays that employed for protection of apparatus and transmission lines?

Last Answer : Answer: The relays that are usually employed for protection of transmission lines include • Over current relay • Directional relay • Distance relay • Under Voltage relay • Under-frequency relay • Thermal relay • Differential relay • Phase sequence relays • pilot relays