1. Type : Out door.
2. Scheme : Double main bus bar with bypass switching scheme is provided.
This allows maintenance of one bus or one CB without interruption.
3. Normal voltage : 220 kV.
4. Rated voltage : 245 kV (400 kV)
5. Impulse voltage : 1050 kV (peak)
6. One-minute level : 460 kV (rms.)
7. Dynamic current capacity: 102 kA (peak) and 40 kA for one sec.
8. Rated current capacity : 2000 A for main and 1600 A for feeder bus.
9. Clearances : Phase to earth – 2100 mm.
Phase to phase – 2100 mm.
Phase to ground – 5500 mm.
Sectional clearance – 4300 mm.
Creepage clearance – (Total) 5600 mm.
– (Protected) 2800 mm.
10. Maximum temperature rise above ambient - 45°C.
11. CB – SF6
12. Isolator – motor operated rotating type.
13. Number of bays – 16 Nos.