What is tertiary winding?

1 Answer

Answer :

Some three phase transformers may have a third winding called tertiary winding apart from primary and secondary. It is also called auxiliary winding or stabilizing winding. The tertiary winding is provided in a transformer for any one of the following reasons, i) to supply small additional load at a different voltage ii) to give supply to phase compensating devices such as capacitors which work at different voltages. iii) to limit short circuit current. iv) to indicate voltage in high voltage testing transformer

Related questions

Description : What is tertiary winding? What is Three Winding Transformer? What are its advantages?

Last Answer : A. In some high rating transformers, one winding, in addition to the primary and secondary winding, is used. This is known as Tertiary Winding of Transformer. Because of this third winding, the ... it assists in limitation of fault current in the event of a short circuit from line to neutral.

Description : What is the Difference Between "Insulating", "Isolating", and "Shielded Winding" Transformers?

Last Answer : Insulating and Isolating transformers are identical. These terms are used to describe the isolation of the primary and secondary windings, or insulation between the two. A shielded winding transformer, ... are connected to each other electrically, are not of the insulating or isolating variety.

Description : In transformers, why the low voltage winding is placed near the core?

Last Answer : The winding & Core are both made of metals and so an insulation have to be placed in between them, the thickness of insulation depends on the voltage rating of the winding. In order to reduce the insulation requirement the low voltage winding place near the core.

Description : What are the necessary tests to determine the efficiency, voltage regulation, and temperature rise of winding & insulation of transformer?

Last Answer : 1.Direct loading test 2.Open circuit test 3. Short circuit test 4. Sumpner's or back to back test

Description : What is Six winding transformer?

Last Answer : Three windings in primary and three windings in secondary are used, They are three phase transformers.They are connected in either star-star, delta-delta, star delta or delta star.

Description : What is Three winding transformer?

Last Answer : Three windings are used each work as primary and secondary. Also primary and secondary windings are conductively couple. They are three phase auto transformer

Description : What is Two winding transformer?

Last Answer : Two separate windings one as primary and other as secondary are used. Both windings are magnetically coupled.

Description : 32 With S2 closed and S1 open, the current waveform in the delta winding will be [GATE 2009] A. a sinusoidal at fundamental frequency B. flat-topped with third harmonic C. only third-harmonic D. none of these

Last Answer : C. Only third harmonic

Description : 28.In a two winding transformer, the emf /turn in secondary winding is always......the induced emf power turn in primary A. equal to k times B. equal to 1/k times C. equal D. greater than

Last Answer : C. equal

Description : 27] In a transformer, the leakage flux of each winding is proportional to the current in that winding because A. Ohm's law applies to magnetic circuits B. Leakage paths do no saturate C. the two windings are electrically isolated D. mutual flux is confined to the core

Last Answer : B. Leakage path do not saturate

Description : 6 In a two winding transformer, the primary and secondary induced emf E1 & E2 are always A. equal in magnitude B. anti phase with each other C. in phase with each other D. determined by load on transformer secondary

Last Answer : C. In phase with each other

Description : 21.The ordinary two winding transformer's primary and secondary windings always have A. different no of turns B. same size of copper wire C. a common magnetic circuit D. separate magnetic circuits

Last Answer : C. A common magnetic circuit

Description : 12] Which is not the basic element of the transformer? A. core B. primary winding C. secondary winding D. mutual flux

Last Answer : D. Mutual flux

Description : 7 The main advantage of auto transformer over a two winding transformer is A. Hysteresis losses are reduced B. Saving in winding material C. Copper losses are negligible D. Eddy losses are totally eliminated

Last Answer : A) hysteresis losses is reduced

Description : What is the difference between “Insulating,” “Isolating,” and “Shielded Winding” transformers?

Last Answer : Insulating and isolating transformers are identical. These terms are used to describe the isolation of the primary and secondary windings, or insulation between the two. A shielded transformer is ... secondary are connected to each other electrically, are not of the insulating or isolating variety.

Description : A certain transformer has 200 turns in the primary winding, 50 turns in the secondary winding and 120 volts applied to the primary. What is the voltage across the secondary?  (A) 30 Volts (B) 480 Volts (C) 120 Volts (D) 60 Volts

Last Answer : A certain transformer has 200 turns in the primary winding, 50 turns in the secondary winding and 120 volts applied to the primary. What is the voltage across the secondary?  (A) 30 Volts (B) 480 Volts (C) 120 Volts (D) 60 Volts

Last Answer : The short circuit in any winding of the transformer is the result of impulse voltage.

Last Answer : In the transformer low voltage winding has got more cross-sectional area.

Last Answer : Primary winding of a transformer could either be a low voltage or high voltage winding.

Last Answer : High voltage winding in a transformer has more number of turns.

Last Answer : High voltage winding of the transformer has less cross-sectional area.

Last Answer :  Sandwich type winding is used in 3 phase shell-type transformer.

Last Answer : yes High Voltage side of Transformer winding have more number of turns. and low voltage side of Transformer winding have less number of turns.

Description : What is the use of Tertiary winding? 

Last Answer : Star connected circuit, which has an isolated neutral there can be no zero sequence components. Since the zero sequence components are by definition in time phase with another their sum can not ... of current have a return path or unless the transformer are provided with tertiary winding. 

Description : What are the transformer losses?

Last Answer : Answer: TRANSFORMER LOSSES - There are mainly two kinds of losses in a transformer namely 1. Copper loss (ohmic loss) and 2.magnetic loss (core loss). Copper losses are caused by the ... ohmic loss the following two losses are also present in the transformer stray load loss and dielectric loss.

Description : Why Silica gel is used in transformers?

Last Answer : Silica Gel is used to remove the moisture in the air entering in to the transformer. During the breathing of the transformer air enters in to the transformer. This air makes contact with the hot ... Silica gel crystals will be in blue color initially and after absorbing moisture it turns to pink.

Description : What are the conditions for parallel operation of two transformers ?

Last Answer : Transformers which are to be operated parallel should have to satisfy the following conditions: Polarities of both the transformers should be same else lead to short circuit Voltage rating of ... Phase displacement of transformers should be same Phase sequence of two transformers should be same

Description : At what power maximum efficiency of power transformer and distribution transformer is designed

Last Answer : Maximum efficiency of the transformer is attained at certain load factor (α) when core losses of transformer is equal to the copper losses. PCore loss = α ^2 X PCopper loss From the ... the day. Hence distribution transformers are designed to have maximum efficiency at 50% of the rated full load

Description : What happen when Transformer is given DC supply ?

Last Answer : When DC supply is given to the transformer primary winding no back emf is induced in the transformer. Importance of Back emf is that it limits the current drawn by the machine. In the absence ... in burning down of primary winding. So when dc supply is given to transformer primary windings will burn

Description : During No load why the power factor of the transformer is very low ?

Last Answer : Current flowing through the transformer consists of two components. Magnetizing current (Im) which is in quadrature (90 0 ) to the applied voltage and in phase current which is in phase to the applied voltage ... power factor of transformer during no load condition will by in the order of 0.1 to 0.2

Description : What is the significance of vector grouping in Power Transformers?

Last Answer : Answer:Every power transformer has a vector group listed by its manufacturer. Fundamentally it tells you the information about how the windings are connected (delta or wye) and the phace difference betweent ... Delta primary, Wye Secondry and the current is at 11 o clock reffered to the voltage.

Description : What is the supply rated o/p if two single phase transformer connect to give three phase o/p from a three phase I/p?

Last Answer : A. Each transformer is only capable of supplying 86.6%of its o/p rating

Description : How to connect two single phase transformer to give three phase o/p from a three phase I/p ?

Last Answer : A. They would have to connect in an open-delta.

Description : What advantage has the star connection over the delta connection ?

Last Answer : A. Each star connection transformer is wound for only 57.7% of line voltage . In hv transmission, this admits of much smaller transformer being built for high voltage than possible with delta connection, because of less insulation.

Description : What is the advantage is obtained in the delta connection ?

Last Answer : A. When three transformer are obtained in delta, one may be removed and two remaining unit will carry 57.7% of the original three phase load and thus maintain the continuity of supply.

Description : What is the 3 ph transformer ?

Last Answer : A. A 3ph transformer is that transformer which is equivalent to three single phase transformer but wound on one core and enclosed within one common case.

Description : What parameters or technical particulars are important to be considered while designing protection scheme of the transformer?

Last Answer : 1.Network Diagram showing the position of the transformer in the system 2.kVA or MVA rating of the transformer 3.Fault Level at the transformer 4.Voltage Ratio 5.Winding Connections 6.Per Unit ... Oil Filled 11.Length and area of cross section of the connecting leads between CTs and Relay Panel

Description : What can be the reasons for the failure of the transformer?

Last Answer : Answer: Transformer is one of the most expensive equipments in the Power System. Failure of the transformer can cause outage of power supply for even days. However, multiple things can go wrong with ... relays. 3.Short Circuits 4.Open Circuits 5.Earth Faults 6.Over Voltage 7.Reduced system frequency

Description : How Transformer Protection provided for internal faults?

Last Answer : 1.Bucholz Relay (1st Stage Alarm and 2nd Stage Trip) 2.Sudden Pressure Relay (1st Stage Alarm and 2nd Stage Trip) 3.Pressure Relief Valve (1st Stage Alarm and 2nd Stage Trip) 4.Pressure Switch ... 8.Gas Temperature Indicator (Alarm) 9.Silicon Breather (Passive - no alarm) 10.Smoke Detector (Alarm)

Description : What are the tests done to minimize internal faults?

Last Answer : 1.Dissolved Gas Analysis (DGA): Faults due to arcing, high current breakdown of oil, localized sparking, partial discharge of oil, localized overheating or hot spots, etc. causes ... Over current relays with under voltage blocking 6.Zero sequence protection. 7.Negative phase sequence protection

Description : What are the reasons for Oil degradation?

Last Answer : 1.Degradation 2.Oxidation 3.Contamination a) Dielectric breakdown voltage indicates the presence of electrically conductive contaminants in oil. b) Interfacial tension and acid number (sometimes called ... c) Water content is temperature dependent. d) Power factor is also temperature dependent.

Description : How does change in frequency affect the operation of a given transformer?

Last Answer : a) Iron loss .........increases with a decrease in frequency. A 60-Hz transformer will have nearly 11% higher losses when worked on 50Hz instead of 60 Hz. However, when a 25-Hz ... ....since total loss is greater at a lower frequency, the temperature is increased with decrease in frequency.

Description : What effects are produced by change in voltage?

Last Answer : a) Iron loss.........varies approximately as V2. b) Cu loss.........it also varies as V2 but decreases with an increase in voltage if constant kVA output is assumed. c ... ..for constant kVA output, iron temperatures increase whereas Cu temperatures decrease with increase in voltages and vice-versa.

Description : Does the transformer draw any current when its secondary is open?

Last Answer : Yes, no-load primary current.

Description : In practice, what determines the thickness of the laminate or stampings?

Last Answer : Frequency.

Description : How can eddy current loss be minimized?

Last Answer : By laminating the core.

Description : Mention the factors on which hysteresis loss depends?

Last Answer : (i) Quality and amount of iron in the core (ii) Flux density and (iii) Frequency.

Description : How is magnetic leakage reduced to a minimum in commercial transformers?

Last Answer : By interleaving the primary and secondary windings.

Description : What are the conditions for parallel operation of two transformers ?

Last Answer : Transformers which are to be operated parallel should have to satisfy the following conditions: Polarities of both the transformers should be same else lead to short circuit Voltage rating of ... Phase displacement of transformers should be same Phase sequence of two transformers should be same

Description : WHAT is ZIG ZAG Grounding Transformer

Last Answer : ANSWER: Three Single Phase Transformers can be connected to have a three phase Zig Zag Transformer. This system can be used for either grounding or developing a fourth WIRE from a three phase neutral. An example ... - three phase - three wire system to a 480Y/277 V - three phase - four wire system