During the start-up of the circuit shown in the illustration, it is noted that the ends of component 'C' remain lighted but the tube does not illuminate. The cause of this problem is ____________. EL-0081 A. component 'A' is open B. component 'D' is closed C. component 'C' is the wrong wattage D. component 'B' contacts are stuck closed

1 Answer

Answer :

Answer: D

Related questions

Description : When replacing component 'B' of the circuit shown in the illustration, it is important to know that ____________. EL-0081 A. it is polarity sensitive and must be inserted as indicated on its ... provide the capacitor's initial charge D. it must match the circuit voltage and component 'C' wattage

Last Answer : Answer: D

Description : When changing out component 'B' of the circuit shown in the illustration, it is important to know that ____________. EL-0081 A. it is polarity sensitive and must be inserted as indicated on its ... provide the capacitor's initial charge D. it must match the circuit voltage and component 'C' wattage

Last Answer : Answer: D

Description : The purpose of the capacitor within component 'B' of the circuit shown in the illustration is to ____________. EL-0081 A. prolong the life of the component's contacts B. discharge the neon within ... the inductive reactance in the circuit D. store power to operate the circuit should 'D' open

Last Answer : Answer: A

Description : What is indicated by gradual blackening at the ends of component 'C' shown in the illustration? EL-0081 A. The unit is in danger of exploding. B. The tube is nearing the end of its useful life. C. The circuit voltage is too high. D. The circuit current is too high.

Last Answer : Answer: B

Description : In the lighting distribution circuit shown in the illustration, if all switches are closed and fuse 'F2' were to open, all lights on branches ____________. EL-0013 A. '1', '2', and '3' would go out B. '1' ... and '3' would burn dimly D. '1' and '3' would go out, while branch '2' would remain lit

Last Answer : Answer: D

Description : As shown in the illustration, the symbol is used in electrical drawings to designate a ____________. EL-0026 A. limit switch with one set of normally open contacts B. maintaining type ... type push button with a mechanical interlock D. normally closed contact held open mechanically by an interlock

Last Answer : Answer: C

Description : When 'selector switch' 'SEL8' shown in the illustration is in the 'TEST' position, contacts '3,4' and '7,8' are respectively ____________. EL-0100 A. open; closed B. closed; open C. open; open D. closed; closed

Last Answer : Answer: B

Description : When 'selector switch' 'SEL8' shown in the illustration is in the 'OFF' position, contacts '3,4' and '7,8' are respectively ____________. EL-0100 A. open; closed B. closed; open C. open; open D. closed; closed

Last Answer : Answer: A

Description : 'A-1', as shown in the illustration, is/are ____________. EL-0017 A. normally-closed overload relay contacts B. a double pole knife switch C. normally-open overload relay contacts D. a single pole knife switch

Last Answer : Answer: A

Description : When using the test set-up shown in the illustration, the lighted lamp indicates the winding is ____________. EL-0027 A. grounded B. good C. open D. shorted

Last Answer : Answer: A

Description : What is represented by the two parallel lines within component 'A' of the circuit shown in the illustration? EL-0081 A. A ground connection B. An iron core C. Ventilation openings D. A mounting base

Last Answer : Answer: B

Description : Which component of the circuit shown in the illustration is the ballast? EL-0081 A. A B. B C. C D. D

Last Answer : Answer: A

Description : When maintaining the circuit shown in the illustration, what dangers are associated with component 'C' should it become broken? EL-0081 A. Glass fragments may cut a person's skin. B. The contained mercury ... highly toxic. C. The inside coating of phosphor is highly poisonous. D. All of the above.

Last Answer : Answer: D

Description : Which component of the circuit shown in the illustration is the starter? EL-0081 A. A B. B C. C D. D

Last Answer : Answer: B

Description : Which component of the circuit shown in the illustration is the lamp? EL-0081 A. A B. B C. C D. D

Last Answer : Answer: C

Description : As shown in the illustration, 'H1' and 'H2' are ___________. EL-0058 A. fixed capacitors B. variable capacitors C. contacts, closed when the circuit is energized D. contacts, open when the circuit is energized

Last Answer : Answer: D

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : In the illustration, the contacts between terminals 26 and 27 should be closed when _________. EL-0046 A. using one generator in isochronous mode only B. using two or more generators in ... through varying loads in parallel or single operation D. the circuit breaker is closed for that generator

Last Answer : Answer: C

Description : The winch shown in the illustration will not operate in any speed in the lowering direction and at an abnormal speed in 'first point hoist'. The possible cause is that _______________. EL-0102 A. ... '1M' in the power circuit are badly corroded D. master switch contacts 'MS6' have weak springs

Last Answer : Answer: B

Description : To stop the electric motor shown in the illustration, the stop button is depressed, causing ____________. EL-0012 A. coil 'MS' to become de-energized B. contacts 'CR1' and 'MR4' to open C. contacts 'MR1', 'MR2', and 'MR3' to open D. contacts 'MS1', 'MS2', and 'MS3' to open

Last Answer : Answer: C

Description : When 'selector switch' 'SEL8' shown in the illustration is in the 'ON' position, contacts '3,4' and '7,8' are respectively ______________. EL-0100 A. open; closed B. closed; open C. open; open D. closed; closed

Last Answer : Answer: D

Description : An open-circuit fault between the pressure switch and the 'annunciator module' shown in the illustration would cause the alarm circuit to react in the same manner as if ___________. EL-0094 A. 3.5 ... below switch setting C. 50 PSI were applied to the 'setpoint module' D. the pressure switch closed

Last Answer : Answer: B

Description : Component 'C' in section 'I' shown in the illustration represent ____________. EL-0093 A. a selectable holding coil arrangement B. a 'fuse blown' indicator circuit C. 'reset' and 'trouble' lamps D. a handset with switch and voice elements

Last Answer : Answer: D

Description : As shown in the illustration, what happens when 'A' is closed, 'B' is in position '2' and component 'E2' burns out? EL-0058 A. 'H' energizes and 'D' makes contact. B. 'F' goes out allowing 'G' to disconnect. C. 'G' sounds an alarm and 'F' illuminates. D. 'C' opens causing 'A' to also open.

Last Answer : Answer: C

Description : The vertical dotted line connecting the small circular symbols at coordinates '05L', '09L', '13L', '21L', '25L', etc., shown in the illustration, indicate that all _______________. EL-0100 A. contacts are ... board 'TB2' C. wires are grounded at both ends of the line D. wires have a common shield

Last Answer : Answer: B

Description : As shown in the illustration, once the "LV" relay is energized for operation, what contacts must remain closed to maintain the "LV" relay energized when the control lever is moved away from the "off" or "stop" ... . B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : The contacts operated by the D.C. relay coil shown in the illustration are located in the schematic diagram prints at coordinates ____________. EL-0100 A. '41Y' on this page B. '52M52M' and '52H35M' C. '57R' on this page D. '52N' on page '57R'

Last Answer : Answer: C

Description : Power necessary to operate the horn relay shown in the illustration ____________. EL-0093 A. comes from each station's magneto B. is supplied from a 115 volt source C. is conducted through the relay's contacts D. also lights lamps 'R' and 'T'

Last Answer : Answer: A

Description : As shown in the illustration, all 'MS' contacts are opened and closed by means of ________. EL-0073 A. operating coils B. magnets C. manual operation of the master switches D. solenoid switches

Last Answer : Answer: C

Description : When the operating handle is in the 'off' position, which master switch contacts for the winch shown in the illustration are closed? EL-0102 A. 'MS-DB & OL' B. 'MS-3, 5, 6, 7, & 8' C. 'MS-LVa & OL' D. 'MS-3, 7 & Reset'

Last Answer : Answer: D

Description : The 'reset' contacts of the master switch shown in the illustration are ______________. EL-0102 A. closed only when the master switch is 'off' B. closed only when the master switch selects a 'run' condition C. opened separately by the winch operator D. opened when line voltage drops 10%

Last Answer : Answer: A

Description : As shown in the illustration, a 'pitch cutback' feature is incorporated in the system. This circuit reduces pitch amount to prevent engine overload when it senses ____________. EL-0095 A. pitch error of ... servo' C. excessive propeller speed or fuel to either engine D. only one engine on the line

Last Answer : Answer: C

Description : What is represented by the solid dots within components 'B' and 'C' of the diagram shown in the illustration? (See illustration EL-0081) EL-0081 A. The fact that these parts are subject to wear and ... only. C. The particular components contain a gas such as neon or argon. D. All of the above.

Last Answer : Answer: C

Description : Which of the listed types of lighting circuits does the diagram shown in the illustration represent? EL-0081 A. High pressure sodium B. Low voltage quartz C. Mercury vapor D. Standard fluorescent

Last Answer : Answer: D

Description : In an emergency, the fastest way to interrupt power and stop the winch shown in the illustration is for the ____________. EL-0102 A. mate to open the disconnect switch at 'L1' and 'L2' B. ... watch engineer to open the winch circuit breaker D. electrician to open the test link at the controller

Last Answer : Answer: B

Description : In order to prevent the winch shown in the illustration from turning while troubleshooting the controller circuit, _________________. EL-0102 A. set the dynamic brake by clamping contact 'DB' closed B. set the ... at 'B1' and 'B2' D. open the test link preventing current flow to the armature

Last Answer : Answer: D

Description : In order to decrease the resistance of the 50K pot located at '21Q/R' shown in the illustration, the wiper of the actual component must be moved ____________. EL-0099 A. to the left B. to the right C. clockwise D. counterclockwise

Last Answer : Answer: D

Description : Component 'D' in section 'I' shown in the illustration represents a ____________. EL-0093 A. selector switch B. vibrating reed indicator C. junction box D. ring counter

Last Answer : Answer: A

Description : Regarding the illustrated electrical schematic, 'S1-P', 'S1-Q', and 'S1-R' represent ____________. EL-0016 A. capacitors B. normally-closed contacts C. normally-open contacts D. normally-closed pushbutton switches

Last Answer : Answer: C

Description : When the motor shown in the illustration is running and the stop button is pushed, which of the following statements will hold true? EL-0010 A. Coil 'M' will now be energized. B. Coil 'CR' will now be energized. C. Contact 'M' will close as contact 'CR' opens. D. Contacts 'M' and 'CR' will open.

Last Answer : Answer: D

Description : As shown in the illustration, which of the operations listed will happen when the 'jog button' is pushed? EL-0010 A. Coil 'CR' closes the normally open 'CR' contacts. B. Coil 'M' opens contact 'M'. C. Coil 'M' closes contact 'M'. D. Contact 'M' remains open despite the jog button being pushed.

Last Answer : Answer: C

Description : The winch shown in the illustration operates in any of the positions with the master switch in the 'lower' direction, but will not 'hoist' in any of the master switch hoist positions. Which of the listed faults ... '2M' in the power circuit may be badly corroded. D. Series relay 'FR' may be open.

Last Answer : Answer: A