As shown in the illustration, which of the listed actions of the synchroscope pointer is occurring? EL-0002 A. Revolving slowly in the slow direction. B. Revolving rapidly in the slow direction. C. Revolving rapidly in the fast direction. D. It would be stationary at the 12 o'clock position since the leading edges of the A phases are in phase.

1 Answer

Answer :

Answer: C

Related questions

Description : When two AC generators are being paralleled, the breaker should be closed with the synchroscope pointer rotating in the ____________. A. 'slow' direction, just before the 12 o'clock position B. 'fast' ... just before the 12 o'clock position D. 'slow' direction, just after the 12 o'clock position

Last Answer : Answer: C

Description : You are attempting to parallel two AC generators and the synchroscope pointer is revolving in the slow direction. This indicates that the frequency of the incoming machine is _____________. A. higher than ... same as the bus frequency, and the circuit breaker may be closed at any pointer position

Last Answer : Answer: B

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving fast in the clockwise direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... at any pointer position D. the same as the bus frequency but out of phase with it

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving in the fast direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... the same as the bus frequency and the circuit breaker may be closed at any pointer position

Last Answer : Answer: A

Description : Which of the following actions must be carried out prior to closing the alternator circuit breaker according to the graph shown in the illustration? EL-0002 A. Increase the alternator voltage. B. Decrease the line voltage. C. Increase the line voltage. D. Decrease the line frequency.

Last Answer : Answer: A

Description : When paralleling two alternators the synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates the ____________. A. alternator voltages ... alternator is in phase with the bus voltage D. synchroscope pointer is defective or broken

Last Answer : Answer: C

Description : You are paralleling two alternators. The synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates that the ____________. A. alternator ... be closed C. incoming alternator is running too slowly D. synchroscope is defective or broken

Last Answer : Answer: B

Description : If the pointer of the synchroscope is rotating in the slow direction when you are preparing to parallel two alternators, the _____________. A. incoming machine is turning faster than the load alternator B ... alternator is ready to split D. incoming machine is beginning to pick up some of the load

Last Answer : Answer: B

Description : What controls rudder movement when the Operation Selector Switch shown in the illustration is in the 'NFU' position? EL-0097 A. Steering wheel B. Non-followup controller C. Gyro-compass D. Course selector pointer

Last Answer : Answer: B

Description : What controls the rudder when the 'operation selector switch' of the steering stand shown in the illustration is in the 'HAND' position? EL-OO98 A. Non-followup controller B. Gyro-compass C. Course selector pointer D. Steering wheel

Last Answer : Answer: D

Description : When paralleling two alternators, the synchronizing lamps remain lit as the synchroscope pointer approaches the 0°. This indicates the _____________. A. incoming alternator is running too fast B. alternator ... apart C. synchroscope is defective or broken D. alternator power factors are in phase

Last Answer : Answer: C

Description : An AC generator panel is fitted with both synchronizing lamps and a synchroscope. When the synchroscope pointer reaches the noon position, one synchronizing light is bright and the other is dark. This ... sequence is incorrect C. the phase sequence is correct D. the generator breaker may be closed

Last Answer : Answer: B

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0° prior to closing the circuit breaker. This indicates ___________. A. the frequency of ... be closed after breaker has been reset D. there is an existing cross current between generators

Last Answer : Answer: A

Description : When the master switch for the winch shown in the illustration is in the 'off' position, and the line & safe switches are closed, which of the listed relays should be energized? EL-0102 A. 'DB' & '2T' B. 'DB' & '4M' C. 'FR-B.O.' & 'LV' D. '1M' & '1A'

Last Answer : Answer: C

Description : The winch shown in the illustration operates in any of the positions with the master switch in the 'lower' direction, but will not 'hoist' in any of the master switch hoist positions. Which of the listed faults ... '2M' in the power circuit may be badly corroded. D. Series relay 'FR' may be open.

Last Answer : Answer: A

Description : Which of the listed figures shown in the illustration represents devices connected in a three-phase delta-delta arrangement? EL-0084 A. A B. B C. C D. D

Last Answer : Answer: A

Description : Which of the listed figures shown in the illustration represents devices connected in a three-phase delta-wye arrangement? EL-0084 A. A B. B C. C D. D

Last Answer : Answer: C

Description : Which of the listed figures shown in the illustration represents devices connected in a three-phase wye-delta arrangement? EL-0084 A. A B. B C. C D. D

Last Answer : Answer: D

Description : Which of the listed figures shown in the illustration represents devices connected in a three-phase wye-wye arrangement? EL-0084 A. A B. B C. C D. D

Last Answer : Answer: B

Description : Which of the synchroscope illustrations depicts the appropriate direction of rotation and position for closing the circuit breaker when paralleling AC generators? EL-0053 A. A B. B C. C D. D

Last Answer : Answer: D

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : The only point in the steering stand shown in the illustration which needs periodic lubrication is the ______________. EL-0098 A. repeater assembly ball bearings B. steering wheel bearing C. operation selector switch D. course selector pointer

Last Answer : Answer: B

Description : As shown in the illustration, the D.C. motor's direction of rotation in changed by changing the _________________. EL-0101 A. polarity of the generator field B. direction of three-phase motor rotation C. direction of generator rotation D. polarity of the motor field

Last Answer : Answer: A

Description : If the three-phase motor, shown in the illustrated schematic diagram, is running in the forward direction, which of the following actions must occur before the motor will reverse rotation? EL-0011 A. Normally-closed ... 'L1' and 'L3' must be interchanged via the 'R' contacts. D. All of the above.

Last Answer : Answer: C

Description : As shown in the illustration, which of the operations listed will happen when the 'jog button' is pushed? EL-0010 A. Coil 'CR' closes the normally open 'CR' contacts. B. Coil 'M' opens contact 'M'. C. Coil 'M' closes contact 'M'. D. Contact 'M' remains open despite the jog button being pushed.

Last Answer : Answer: C

Description : As shown in the illustration, which listed action will occur first when push button 'Q' is depressed? EL-0017 A. Contacts 'H-1', 'H-2' and 'H-3' close. B. Contact 'H-4' closes. C. Operating coil 'C' energizes. D. Switch 'R' opens.

Last Answer : Answer: C

Description : If the motor shown in the illustration will not start when 'Q' is depressed, which of the listed components should be checked FIRST? EL-0017 A. Fuses 'F-1' and 'F-2'. B. Operating coil 'C'. C. Contacts 'H-1', 'H-2', and 'H-3'. D. Contact 'H-4'.

Last Answer : Answer: A

Description : If the circuit shown in the illustration were energized and operating properly, which of the devices listed would be open? EL-0007 A. The stop push-button B. The start push-button C. Contact 'Ma' D. Contact 'OL1'

Last Answer : Answer: B

Description : Which of the listed electrical devices is represented by the symbol shown in the illustration? EL-0055 A. Fixed resistance resistor B. Coil with magnetic core C. DC motor or generator shunt field D. Transformer

Last Answer : Answer: D

Description : As shown in the illustration, the electrical symbol is used to indicate which of the listed types of motors? EL-0054 A. Shunt motor. B. Series motor. C. Compound motor. D. Tri-field motor.

Last Answer : Answer: C

Description : Which of the devices listed is indicated by the electronic symbol lettered as 'A', shown in the illustration? EL-0016 A. Thyristor B. Diode C. Capacitor D. Transistor

Last Answer : Answer: B

Description : Which of the listed conditions occur when '4th point lower' is selected on the winch shown in the illustration? EL-0102 A. Master switch contacts '3', '4', '6', '8', '9', & '10' close. B. Contactors '2, 3, & 4M' and ' ... , '7', '8', and '9' close. D. Contactors '1 & 3M' and '1, 2, & 3A' pick up.

Last Answer : Answer: B

Description : Which of the listed conditions occur when selection is made for 'third point hoist' on the winch shown in the illustration? EL-0102 A. Master switch contacts '5', '6', '7', '8', and '9' close. B. Contactors '2M', ' ... ' and '2A' drop out. D. Master switch contacts '3','4', '6', '8', and '9' close.

Last Answer : Answer: D

Description : The schematic diagram shown in the illustration represents which of the listed solid-state circuits? EL-0069 A. Bridge rectifier B. Magnetic amplifier C. Flip-flop generator D. Cathodic amplifier

Last Answer : Answer: A

Description : Which of the devices listed is indicated by the symbols lettered 'A' to 'F', shown in the illustration? EL-0016 A. Diodes B. Linear inductors C. Capacitors D. Transistors

Last Answer : Answer: A

Description : As shown in the illustration, which of the elements listed does the line 'B' represent in the basic schematic symbol of a PNP transistor? EL-0068 A. Base B. Emitter C. Cathode D. Collector

Last Answer : Answer: D

Description : If the values of 'C' and 'R' shown in the illustration were 1 microfarad and 100 kOhms respectively, at what listed time would 'C' be considered fully charged? EL-0086 A. 0.1 second B. 0.2 second C. 0.5 second D. 5 seconds

Last Answer : Answer: C

Description : If the values of 'C' and 'R' shown in the illustration were 1 microfarad and 100 kOhms, which of the listed time intervals would equal one 'time constant'? EL-0086 A. 0.1 second B. 0.2 second C. 0.5 second D. 5.0 seconds

Last Answer : Answer: A

Description : If the values of 'C' and 'R' shown in the illustration were 1 microfarad and 3 Megohms respectively, at what listed time would 'C' be considered fully charged? EL-0086 A. 0.33 second B. 3 seconds C. 6 seconds D. 15 seconds

Last Answer : Answer: D

Description : If the values of C and R shown in the illustration were 1-microfarad and 3- Megohms respectively, which of the listed intervals would equal one 'time constant'? EL-0086 A. 0.33 second B. 3 seconds C. 6 seconds D. 15 seconds

Last Answer : Answer: B

Description : Which of the listed types of lighting circuits does the diagram shown in the illustration represent? EL-0081 A. High pressure sodium B. Low voltage quartz C. Mercury vapor D. Standard fluorescent

Last Answer : Answer: D