The ground indicating light on the main electrical switchboard is indicating a ground. The best procedure for locating the grounded circuit is to _____________. A. trace the circuit paths while looking for burned spots B. check circuit resistances with a megohmmeter connected between the grounded line and the distribution panel framework C. open the circuit breakers on the distribution panel, one at a time, until the lights no longer indicate a ground D. check all circuits for continuity

1 Answer

Answer :

Answer: C

Related questions

Description : A ground is indicated by the ground-detecting system on the main electrical switchboard. The FIRST step in locating the actual ground is to _____________. A. close all circuit breakers in ... ground detection system indicates normal C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : Multiple grounds have developed and were initialy indicated by the grounddetecting system as one ground. The FIRST step in locating the grounds is to _____________. A. examine the main bus bars ... no longer indicates any grounds C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : The part of the shipboard electrical system used to control the distribution of power to the branch circuits, is the _____________. A. bridge control panel B. disconnect links C. governor relay box D. main switchboard

Last Answer : Answer: D

Description : A ground in an electrical circuit outside the engine room _____________. A. cannot be detected under normal conditions B. is of no consequence to engineering personnel C. is indicated at the branch circuit breaker panel D. is indicated by the ground detecting lamps on the main switchboard

Last Answer : Answer: D

Description : The purpose of a short circuit forcing module (short time trip) installed in a branch line is to provide ____________. A. high speed clearance of low impedance short circuits in the branch B. ... C. isolation of short circuits by selective tripping of branch circuit breakers D. all of the above

Last Answer : Answer: D

Description : The leads from a megohmmeter are attached to the leads of an AC motor field coil. A reading of infinity is obtained indicating a/an ____________. A. open field coil B. shorted field coil C. grounded field coil D. shunted field coil

Last Answer : Answer: A

Description : When shipboard electrical distribution circuits are connected in parallel, additional parallel circuits will cause the total circuit resistance to _____________. A. increase, causing a drop in the line current B ... an increase in the line voltage D. decrease, causing an increase in the line current

Last Answer : Answer: D

Description : The purpose of a main switchboard circuit breaker's reverse-power trip is to _____________. A. prevent main circuit overload B. protect the circuit breaker blowout coil C. prevent alternator motorization D. prevent low voltage tripout

Last Answer : Answer: C

Description : A 'dead front' switchboard is one _____________. A. without switches on it B. with insulated switches and no exposed terminals C. without circuit breakers D. without safety hand rails nor rubber mats

Last Answer : Answer: B

Description : According to Coast Guard Regulations (46 CFR), the talking and calling circuits of a sound powered telephone system must be _____________. A. intrinsically safe B. independent of each other C. independently grounded D. connected to a common ground

Last Answer : Answer: B

Description : With both ends of a three conductor cable disconnected and arranged without the conductors touching each other, an ohmmeter reading of 'zero' ohms between the ends of one conductor would indicate _____________. A. continuity B. a partial ground C. the resistance is infinite D. a short circuit

Last Answer : Answer: A

Description : Before testing insulation with a megohmmeter, the windings of large machines should be grounded for about 15 minutes just prior to the test as the ______________. A. insulation may be damaged ... number of leakage paths D. larger machines may acquire a charge of static electricity during operation

Last Answer : Answer: D

Description : Before testing insulation with a megohmmeter, the windings of large machines should be grounded for about 15 minutes just prior to the test, because the ___________. A. static charge of the machine ... number of leakage paths C. insulation may be damaged D. insulation may be covered with moisture

Last Answer : Answer: A

Description : A megohmmeter is connected to each end of an individual motor winding. A low ohm reading indicates ____________. A. an open coil B. a loose coil C. good continuity D. a dirty coil

Last Answer : Answer: C

Description : Which of the following statements is correct concerning the circuits in a sound powered telephone system? A. The ringing circuit is composed of only one common wire to ground. B. The common ... connected to each station. D. The talking and calling circuits are electrically dependent upon each other.

Last Answer : Answer: B

Description : A ground on a particular phase of a three-phase low voltage distribution system would be indicated by a _____________. A. high switchboard wattmeter reading B. low switchboard wattmeter reading C. dark or dim switchboard ground detecting light D. bright switchboard ground detecting light

Last Answer : Answer: C

Description : The final step in testing a circuit for a ground involves the use of a megohmmeter. A grounded switch or cable will be indicated by a megohmmeter reading of ____________. A. 'zero' B. infinity C. steady in the high range D. unsteady in the low range

Last Answer : Answer: A

Description : A current-carrying conductor making electrical contact with a wiring conduit will be indicated by a _____________. A. high switchboard wattmeter reading B. totally dark switchboard ground detecting light C. low switchboard wattmeter reading D. all of the above

Last Answer : Answer: B

Description : A current carrying conductor making an electrical contact with a wiring metal conduit is indicated by a _____________. A. low switchboard wattmeter reading B. reading of 1.0 on the power factor meter C. high switchboard voltmeter reading D. totally darkened switchboard ground-detecting light

Last Answer : Answer: D

Description : While testing a semi-conductor diode with an ohmmeter, both the forward and reverse readings are almost in the infinity range. This would indicate that the unit is _____________. A. good B. open C. grounded D. shorted

Last Answer : Answer: B

Description : The purpose of the automatic bus transfer shown in the illustration is to ___________. EL-0014 A. stepdown voltage to the lighting distribution panel B. provide emergency power to ... emergency switchboard from the main switchboard D. provide overcurrent protection to the lighting distribution panel

Last Answer : Answer: B

Description : When troubleshooting a console circuit card which is suspected of being faulty, the first step would be to _____. A. pull the card and measure the value of all resistors B. check for the ... for burned components D. check for continuity of circuit board traces and then the gain of each transistor

Last Answer : Answer: C

Description : Undervoltage trips are frequently installed on switchboard circuit breakers to trip ____________. A. out generators in the event of severe arcing or sparking B. out generators when there is reversal of power ... , but continues to run D. out generators when there is low voltage in the main circuit

Last Answer : Answer: D

Description : You can determine if a circuit breaker has tripped by ________________. A. examining the position of the handle B. checking for which of the breakers is warm C. looking for a burned-out link D. all of the above

Last Answer : Answer: A

Description : A voltmeter located on a control panel has been operating correctly for six months, suddenly burns out. After removing it, it is found that neither side of the meter has been grounded. When ... side and the ground C. installed exactly as the old installation D. grounded to the positive side

Last Answer : Answer: C

Description : When a megohmmeter is being used on a alternating current machine, the meter pointer will dip toward 'zero' and then gradually rise to the true resistance value if the motor insulation is _____________. A. grounded B. good C. shorted D. dirty

Last Answer : Answer: B

Description : A grounded switch or cable will be indicated by a megohmmeter reading of _____________. A. infinity B. 'zero' C. being unsteady in the high range D. being unsteady in the low range

Last Answer : Answer: B

Description : On a switchboard, if all three ground detection lamps remain burning at half intensity when the test button is depressed, which of the listed conditions is indicated? A. No grounds exist. B. All three phases are grounded. C. The test switch is grounded. D. The current transformers are shorted.

Last Answer : Answer: A

Description : When using a megohmmeter to determine which shunt field coil is grounded in a DC machine, you must ____________. A. insulate the field frame from the ship's hull B. disconnect each shunt ... C. use a motor driven high capacity megohmmeter D. remove all main line lead connections before testing

Last Answer : Answer: B

Description : The electrical energy necessary to transmit a person's voice over a sound-powered telephone circuit is obtained from _____________. A. dry cell batteries B. the ship's service switchboard C. the emergency switchboard D. the speaker's voice

Last Answer : Answer: D

Description : When working on electrical circuits containing large capacitors, in addition to deenergizing the circuit, which of the listed precautions should also be taken? A. Keep all radio equipment ... capacitor insulation resistance. C. Ground the capacitor terminals. D. Check capacitor circuit polarity.

Last Answer : Answer: C

Description : In electronic circuits, DC voltages can be positive (+) or negative (-) when measured with respect to the _________. A. printed circuit board 'common' trace B. chassis, console frame or hull 'ground' C. analogue or digital circuitry 'common' bus D. all of the above

Last Answer : Answer: D

Description : Which of the following statements regarding the use of a current measuring instrument is correct? A. It must be connected in series with the circuit. B. You should always start with the lowest range ... of polarity. D. An external shunt is generally utilized where current is less than 10 amperes.

Last Answer : Answer: A

Description : If you obtain a low resistance reading with a megohmmeter connected between terminals 'A' and 'C' of the three-phase, wye-connected winding shown in the illustration, there is __________. EL-0074 A. no open circuit ... 'B' C. an open circuit between 'A' and 'C' D. an open circuit in both windings

Last Answer : Answer: A

Description : In which of the situations listed will a megohmmeter give the most accurate readings? A. While the machine is in operation. B. While the machine is discharging static electricity. C. Immediately prior to ... machine. D. When the machine has been shut down and grounded for a period of 15 minutes.

Last Answer : Answer: D

Description : When troubleshooting AC motors, a portable growler can be used for locating ____________. A. open field coils B. grounded field coils C. grounded stator coils D. shorted stator coils

Last Answer : Answer: D

Description : Accidental grounds in a shipboard electrical system must be repaired as soon as possible as they will ____________. A. result in immediate power outages B. damage circuit breakers C. appear on the ground detection system D. damage insulation and may cause outages

Last Answer : Answer: D

Description : Before any work on electrical or electronic equipment is performed, which of the following precautions should be carried out? A. De-energize the applicable switchboard bus. B. Bypass the interlocks. C. ... supply circuit breaker in the open position. D. Station a man at the circuit supply switch.

Last Answer : Answer: C

Description : A flickering ground detection lamp on a DC system would indicate a _____________. A. multiple-ground condition in the distribution system B. ground in an armature coil of an operating machine C. ground in a motor accompanied with a short D. short between two adjacent bars of the generator commutator

Last Answer : Answer: B

Description : In preparing to take insulation resistance readings on a main generator, the windings should be grounded for about 15 minutes prior to the test to _____________. A. allow accurate zeroing of the meter ... the windings D. help the windings to cool to the same temperature as the ground test connection

Last Answer : Answer: C

Description : In the lighting distribution circuit shown in the illustration, if all switches are closed and fuse 'F2' were to open, all lights on branches ____________. EL-0013 A. '1', '2', and '3' would go out B. '1' ... and '3' would burn dimly D. '1' and '3' would go out, while branch '2' would remain lit

Last Answer : Answer: D

Description : Which of the following statements is true concerning the motor controller diagram shown in the illustration? EL-0023 A. Terminal 'T2' is hot only on high speed. B. Both indicating lights will be lit on ... high speed operation only. D. 'L2' is always connected to 'T2' whenever the motor is running.

Last Answer : Answer: D

Description : If you disconnect and arrange both ends of a three conductor cable, without any contact between the individual conductors, an indicated ohmic value between the ends of a single conductor would indicate ... resistance C. the presence of a partial ground D. that the conductor is not short circuited

Last Answer : Answer: A

Description : A capacitor is to be tested with a megohmmeter. If the meter is connected to a shorted capacitor, the meter pointer should _____________. A. immediately swing to the maximum resistance value ... and gradually decrease D. swing to zero then gradually increase with slight pointer movements down scale

Last Answer : Answer: B