During maintenance of circuit breakers, _______________. A. always smooth roughened contact surfaces with a file B. never pass more than rated breaker current through the overload heater element C. inspect for wear and misalignment of main contacts D. assume heater elements installed are of correct size

1 Answer

Answer :

Answer: C

Related questions

Description : In the illustration, the purpose of part B is to _________. EL-0033 A. increase resistance in series with the contacts as they close to prevent arcing B. create a magnetic field in the steel ... event of an overload D. provide ventilation to the contact when the breaker is close to rated capacity

Last Answer : Answer: B

Description : The purpose of a main switchboard circuit breaker's reverse-power trip is to _____________. A. prevent main circuit overload B. protect the circuit breaker blowout coil C. prevent alternator motorization D. prevent low voltage tripout

Last Answer : Answer: C

Description : Undervoltage trips are frequently installed on switchboard circuit breakers to trip ____________. A. out generators in the event of severe arcing or sparking B. out generators when there is reversal of power ... , but continues to run D. out generators when there is low voltage in the main circuit

Last Answer : Answer: D

Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown

Last Answer : Answer: B

Description : If a magnetic controller contactor fails to pick up when the coil voltage is applied to the contactor coil, the cause may be _____________. A. overload B. misalignment of the affected contactor contacts C. low spring pressure D. an open contactor coil

Last Answer : Answer: D

Description : Periodic testing of circuit breakers is necessary to assure that a correctly rated and properly installed unit _________________. A. can trip faster as it increases in age B. will continue to provide ... not exceed its interrupting capacity D. be able to withstand at least 125% of applied voltage

Last Answer : Answer: B

Description : The arc resulting from the tripping of a circuit breaker is prevented from damaging the contacts by _____________. A. designing the contacts to open slowly B. directing the arc into an ... an inverse timed thermal trip for short circuit currents D. instantaneous magnetic trip for overload currents

Last Answer : Answer: B

Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button

Last Answer : Answer: D

Description : The schematic diagram shown in the illustration uses symbol 'A' to represent a/an _________. EL-0011 A. non-renewable fuse link B. circuit breaker coil C. overload relay coil D. thermal overload heater

Last Answer : Answer: D

Description : A loud buzzing noise at the contacts of a magnetic controller could indicate _____________. A. weak contact spring pressure B. misalignment of the magnet faces C. excessive line current D. mechanical binding

Last Answer : Answer: B

Description : In addition to testing the calibration of a circuit breaker, maintenance should include all of the following EXCEPT ______________. A. changing out of magnetic elements and thermal heaters yearly B. ... for loose or missing parts D. making sure foreign matter does not block tripping element

Last Answer : Answer: A

Description : Protection against sustained overloads occurring in molded-case circuit breakers is provided by a/an __________. A. overvoltage release B. thermal acting trip C. thermal overload relay D. current overload relay

Last Answer : Answer: B

Description : Which of the following circuit breakers has high reliability and minimum maintenance ? (a) Air blast circuit breakers (b) Circuit breaker with SF6 gas (c) Vacuum circuit breakers (d) Oil circuit breakers

Last Answer : (b) Circuit breaker with SF6 gas

Description : The 'safe switch' of the winch controller shown in the illustration is operated _______________. EL-0102 A. through the master switch handle B. when heater circuit current is high C. by contactor coil 'FR' D. manually by the winch operator

Last Answer : Answer: D

Description : Shading coils are installed on AC full-voltage starters to _____________. A. eliminate contact chatter B. dissipate opening contact arcs C. delay current build up in the holding coil D. protect the motor windings from momentary starting current overload

Last Answer : Answer: A

Description : The purpose of a short circuit forcing module (short time trip) installed in a branch line is to provide ____________. A. high speed clearance of low impedance short circuits in the branch B. ... C. isolation of short circuits by selective tripping of branch circuit breakers D. all of the above

Last Answer : Answer: D

Description : A loud buzzing noise in an AC controller is probably caused by _____________. A. poor contact with the overload relay B. an incorrectly sized heater C. a broken shading coil D. abnormal starting current

Last Answer : Answer: C

Description : As part of a routine maintenance program for deck machinery, you should ___________. A. inspect electrical wiring and pushbutton switches for evidence of corrosion or burned insulation B. disassemble ... covers and ventilate as weather permits D. Check drum switch contact pressure every three months

Last Answer : Answer: A

Description : Grease coatings on electrical contact surfaces increase contact resistance and should be removed with a/an _______________. A. small wire brush B. compressed air jet C. clean dry cloth D. 10% solution carbon solvent and water

Last Answer : Answer: C

Description : The purpose of the 'heater resistors' for the winch circuit shown in the illustration is to _______________. EL-0102 A. limit the current in the heater circuit B. dispel moisture in the ' ... panel C. keep the winch brake housing below the dew point D. maintain winch motor operating temperature

Last Answer : Answer: B

Description : The purpose of a magnetic relay is to _____________. A. open a circuit only in the event of overload B. remotely open and close contacts C. provide overcurrent protection during starting D. relay voltages at increased power

Last Answer : Answer: B

Description : The pitting of controller contacts can be caused by _____________. A. excessive spring pressure B. insufficient contact pressure C. continuous motor overload D. all of the above

Last Answer : Answer: B

Description : In order that current should flow without causing excessive heating or voltage drop, the relay contacts should (a) have low contact resistance (b) be clean and smooth (c) be of sufficient size and proper shape (d) have all above properties

Last Answer : (d) have all above properties

Description : You can determine if a circuit breaker has tripped by ________________. A. examining the position of the handle B. checking for which of the breakers is warm C. looking for a burned-out link D. all of the above

Last Answer : Answer: A

Description : Burning of controller contacts, when opening, is prevented by _____________. A. coating the contact surfaces lightly with petroleum jelly B. magnetic blowout coils C. an overvoltage release D. an overcurrent release

Last Answer : Answer: B

Description : Which of the following statements is true concerning the cleaning of electrical contacts? A. Compressed air should be used to blow out metallic dust. B. Magnetic brushes should be used to remove ... contact resistance. D. Delicate parts should be cleaned with a brush and an approved safety solvent.

Last Answer : Answer: D

Description : In the illustration, the contacts between terminals 26 and 27 should be closed when _________. EL-0046 A. using one generator in isochronous mode only B. using two or more generators in ... through varying loads in parallel or single operation D. the circuit breaker is closed for that generator

Last Answer : Answer: C

Description : A circuit breaker for a 300 KW alternator is rated at 470 amperes of full continuous load. The amount of overcurrent allowed is 125%. Which of the following conditions will trip the breaker? A. ... 10 minutes. C. Momentary starting load of 550 amperes. D. Sustained current flow of 590 amperes.

Last Answer : Answer: D

Description : Before reassembling any machinery, you should _____________. A. replace all bearings regardless of length of service B. apply a heavy coat of oil to all mating surfaces C. clean any corroded surfaces and file all burrs smooth D. coat all parts with alemite grease

Last Answer : Answer: C

Description : Fuses placed in series with a thermal trip-type circuit breaker are used for _____________. A. time-delay protection B. short-circuit protection C. short duration surge protection D. sustained overload protection

Last Answer : Answer: B

Description : Humming or buzzing of electric contacts is a symptom of ____________. A. low voltage on the operating coil B. power failure to the operating coil C. a control circuit ground D. a control circuit overload

Last Answer : Answer: A

Description : The winch shown in the illustration will not operate in any speed in the lowering direction and at an abnormal speed in 'first point hoist'. The possible cause is that _______________. EL-0102 A. ... '1M' in the power circuit are badly corroded D. master switch contacts 'MS6' have weak springs

Last Answer : Answer: B

Description : The 'function generator' of the control circuit illustrated _______________. EL-0095 A. can be programmed to produce a non-linear output for a linear input depending on operating conditions B. is used for ... which or how many engines are needed for a required vessel speed D. all of the above

Last Answer : Answer: A

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : Circuit breakers are essentially (a) current carrying contacts called electrodes (b) arc extinguishers (c) circuits to break the system (d) transformers to isolate the two systems (e) any of the above

Last Answer : (a) current carrying contacts called electrodes

Description : The main purpose of an electric space heater installed in a large AC generator is to _____________. A. prevent the windings from becoming brittle B. prevent moisture from condensing in the windings during ... C. prevent acidic pitting of the slip rings D. keep the lube oil warm for quick starting

Last Answer : Answer: B

Description : As shown in the illustration, when the 'speed control' system is in 'SPLIT' _______________. EL-0096 A. Relays #1, #5 and #8 are not used B. the 'slew rated controller' is grounded through Relay ... E/P converters' are bypassed and air is fed directly to the governors via the 'load sharing valve'

Last Answer : Answer: C

Description : The air gap in an induction motor should be periodically checked with a feeler gage to prevent possible ___________. A. rotor contact with the stator B. axial misalignment of the rotor C. damage to the motor bearings D. electrical damage to the bearings

Last Answer : Answer: A

Description : The main purpose of an electric space heater installed in a large AC generator is to _____________. A. keep the lube oil warm for quick starting B. prevent moisture from condensing in the ... is shutdown C. prevent the windings from becoming brittle D. prevent acidic pitting of the slip rings

Last Answer : Answer: B

Description : When replacing fuses, always make sure _______________. A. to stand on a rubber mat and use rubber gloves B. to use insulated pliers or screwdriver C. the fuse clips are straight, tight, and in good contact D. to increase the fuse rating 10% to guard against 'nuisance blowing'

Last Answer : Answer: C

Description : Low voltage circuit breakers have rated voltage of less than___________-. A. 220 V B. 400V C. 1000 V D. 10,000 V.

Last Answer : Low voltage circuit breakers have rated voltage of less than 1000 V.

Description : A slow continual loss of electrolyte level from one cell of a storage battery could be due to _______________. A. a cracked casing B. too low a charging rate C. the specific gravity being higher than normal D. one filler cap installed too tightly

Last Answer : Answer: A

Description : Which of the following statements, concerning the general maintenance of a brushless generator, is correct? A. Paint should be applied to insulating surfaces on an annual basis. B. Alcohol should be used to ... . D. Accessible generator parts should be wiped with a clean dry rag on a periodic basis.

Last Answer : Answer: D

Description : For a traction transformer circuit breaker state: 1) Rated current and rupturing capacity 2) Any two tests it should be capable of withstanding 3) Overall tripping time and relay time.

Last Answer : Ans: 1) Rated current --- 750 A and Rupturing capacity --- 500 MVA  2) Any two tests it should be capable of withstanding --- Breaking test , Reclosing test , Endurance test ( any two )  3) Overall tripping time --- 0.14 sec and Relay time --- 0.04 sec