Burning of controller contacts, when opening, is prevented by _____________. A. coating the contact surfaces lightly with petroleum jelly B. magnetic blowout coils C. an overvoltage release D. an overcurrent release

1 Answer

Answer :

Answer: B

Related questions

Description : If a magnetic controller relay fails to drop out when the coil voltage is removed from the relay, the probable cause may be _____________. A. excessive spring tension B. overvoltage C. excessive current D. welded contacts

Last Answer : Answer: D

Description : The purpose of a magnetic relay is to _____________. A. open a circuit only in the event of overload B. remotely open and close contacts C. provide overcurrent protection during starting D. relay voltages at increased power

Last Answer : Answer: B

Description : Refering to the illustrated schematic diagram, which of the following statements is true when the motor is running in the forward direction? EL-0011 A. Normally-open contacts '4-5' are closed. B. Current ... switch. C. Normally-closed contacts 'R' are open. D. The blowout coils must be closed.

Last Answer : Answer: B

Description : A loud buzzing noise at the contacts of a magnetic controller could indicate _____________. A. weak contact spring pressure B. misalignment of the magnet faces C. excessive line current D. mechanical binding

Last Answer : Answer: B

Description : Magnetic controller contacts may become welded together during operation because of _____________. A. excessive magnetic gap B. low contact pressure C. an open coil D. excessive ambient temperature

Last Answer : Answer: B

Description : Magnetic controller contacts may become welded together during operation due to _____________. A. an open coil B. low contact pressure C. excessive ambient temperature D. excessive magnetic gap

Last Answer : Answer: B

Description : Routine maintenance of lead acid batteries should include _____________. A. keeping the terminals clean B. coating cable connections with petroleum jelly C. maintaining a trickle charge D. all of the above

Last Answer : Answer: D

Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button

Last Answer : Answer: D

Description : The arc resulting from the tripping of a circuit breaker is prevented from damaging the contacts by _____________. A. designing the contacts to open slowly B. directing the arc into an ... an inverse timed thermal trip for short circuit currents D. instantaneous magnetic trip for overload currents

Last Answer : Answer: B

Description : Shading coils are installed on AC full-voltage starters to _____________. A. eliminate contact chatter B. dissipate opening contact arcs C. delay current build up in the holding coil D. protect the motor windings from momentary starting current overload

Last Answer : Answer: A

Description : The pitting of controller contacts can be caused by _____________. A. excessive spring pressure B. insufficient contact pressure C. continuous motor overload D. all of the above

Last Answer : Answer: B

Description : Which of the following statements is true concerning the cleaning of electrical contacts? A. Compressed air should be used to blow out metallic dust. B. Magnetic brushes should be used to remove ... contact resistance. D. Delicate parts should be cleaned with a brush and an approved safety solvent.

Last Answer : Answer: D

Description : If a magnetic controller contactor fails to pick up when the coil voltage is applied to the contactor coil, the cause may be _____________. A. overload B. misalignment of the affected contactor contacts C. low spring pressure D. an open contactor coil

Last Answer : Answer: D

Description : Magnetic controller contacts may become welded together during operating conditions as a result of _____________. A. high spring pressure B. high ambient temperature C. an open coil D. low voltage on operating coil

Last Answer : Answer: D

Description : When troubleshooting a magnetic controller, it is found that the contacts are welded together. The most probable cause is _____________. A. excessive operation at low load B. high ambient temperature C. low voltage on the operating coil D. high voltage on the operating coil

Last Answer : Answer: C

Description : A shading coil used in an AC magnetic controller, functions to _____________. A. reduce vibration and noise in the contactor B. prevent flux buildup in the operating coil C. eliminate arcing when the contacts close D. energize the operating coil and 'pull in' the contacts

Last Answer : Answer: A

Description : An instantaneous-trip-type fuse will _____________. A. open as soon as the load current exceeds its set point B. allow a preset delay between overcurrent and melting C. open a circuit by using a time delay element with a magnetic trip D. reset itself when the overcurrent is corrected

Last Answer : Answer: A

Description : In the illustrated schematic diagram, which of the listed devices prevents the forward and reversing coils from being energized simultaneously? EL-0011 A. An 'either-or' interlock B. A mechanical interlock C. Blowout coils D. A stop button

Last Answer : Answer: A

Description : Protection against sustained overloads occurring in molded-case circuit breakers is provided by a/an __________. A. overvoltage release B. thermal acting trip C. thermal overload relay D. current overload relay

Last Answer : Answer: B

Description : During maintenance of circuit breakers, _______________. A. always smooth roughened contact surfaces with a file B. never pass more than rated breaker current through the overload heater element C. ... wear and misalignment of main contacts D. assume heater elements installed are of correct size

Last Answer : Answer: C

Description : The 'reset' contacts of the master switch shown in the illustration provides the winch controller with ___________. EL-0102 A. low voltage release B. overload protection C. low voltage protection D. high power factor correction

Last Answer : Answer: C

Description : Complete controller maintenance includes _____________. A. periodic testing of protective devices B. checking for loose or worn contacts and weak springs C. maintaining a sufficient supply of spare parts D. all of the above

Last Answer : Answer: D

Description : Motor starter or controller contacts may become welded together if the contacts _____________. A. open too quickly and arc B. close under excessive pressure C. open or close too quickly D. close under excessive starting current

Last Answer : Answer: D

Description : Motor controller or starter contacts may become pitted and welded together if the contacts _____________. A. open under loaded conditions B. close slowly with light pressure C. open too quickly and arc D. close quickly with proportionate pressure

Last Answer : Answer: B

Description : One function of the movable cams in a drum-type motor controller is to _____________. A. regulate the speed of the motor B. maintain resistance contacts in clean condition C. insulate the operating handle D. limit the amount of load put on the motor

Last Answer : Answer: A

Description : The purpose of a main switchboard circuit breaker's reverse-power trip is to _____________. A. prevent main circuit overload B. protect the circuit breaker blowout coil C. prevent alternator motorization D. prevent low voltage tripout

Last Answer : Answer: C

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown

Last Answer : Answer: B

Description : A loud buzzing noise coming from the contacts in a magnetic controller can be caused by ____________. A. excessive current B. excessive magnet gap C. bouncing of contacts D. dirt on magnet faces

Last Answer : Answer: D

Description : Interruption of large currents by relay requires (a) arc suppressing blow out coils (b) wide separation of the opened contacts (c) high speed opening of contacts (d) all of the above

Last Answer : (d) all of the above

Description : A three-phase, induction-type motor experiences an open in one phase. Which of the listed automatic protective devices will prevent the machine from being damaged? A. Overspeed trip B. Thermal overload relay C. Three-pole safety switch D. Magnetic blowout coil

Last Answer : Answer: B

Description : A loud buzzing noise in an AC controller is probably caused by _____________. A. poor contact with the overload relay B. an incorrectly sized heater C. a broken shading coil D. abnormal starting current

Last Answer : Answer: C

Description : Excessive heat in an operating motor controller can result from _____________. A. a closed starter contact B. loose connections C. missing arc chutes D. low motor starting torque

Last Answer : Answer: B

Description : Pick up the correct statement from the following: (A) Air bubbles in casting produce a dull sound by tapping their surfaces lightly with a hammer (B) Cupola furnace is used for the manufacture of cast iron (C) Red short iron is of no value for welding purpose (D) All the above

Last Answer : Answer: Option D

Description : In the illustration, the purpose of part B is to _________. EL-0033 A. increase resistance in series with the contacts as they close to prevent arcing B. create a magnetic field in the steel ... event of an overload D. provide ventilation to the contact when the breaker is close to rated capacity

Last Answer : Answer: B

Description : During its operation, loud buzzing and resultant welding of contacts of a magnetic relay may be caused by __________. A. overheating of the contactor coil B. low voltage on the operating coil C. low insulation resistance to ground D. lubrication of the contact bearing points

Last Answer : Answer: B

Description : When troubleshooting a motor controller, all indications are that a relay coil should be energized. If there were no magnetic pull, with rated voltage measured across the coil, the most probable cause ... open C. auxiliary contact in series with the coil is defective D. relay armature is stuck

Last Answer : Answer: A

Description : If a magnetic controller contact fails to pick up when the operating coil is energized, one possible cause may be _______________. A. low spring pressure B. low voltage to the coil C. the residual magnetism of the contact faces D. dirty contact faces

Last Answer : Answer: B

Description : As shown in the illustration, all 'MS' contacts are opened and closed by means of ________. EL-0073 A. operating coils B. magnets C. manual operation of the master switches D. solenoid switches

Last Answer : Answer: C

Description : If deck machinery is expected to be idle for an extended period of time you should____________. A. have electrical safety gloves available in case of electrical shock before running B. perform ... run at regular intervals to inusre correct operation and to renew the internal coating of lubrication

Last Answer : Answer: D

Description : Proper storage battery maintenance includes ____________. A. keeping connections tight and casing surfaces clean B. making sure electrolyte level is below the separator plates C. insulating the terminals with naval jelly D. maintaining a high charging rate at all times

Last Answer : Answer: A

Description : Frequent urination and burning sensation to urinate and defecate for about 3 years ? I am 18 years old. Frequent urination and burning sensation started from three years ago. After a while, burning started in the toilet ... . I would like to see a doctor now and who is his best in Rajshahi ... ???

Last Answer : It causes burning sensation in the urine due to your urinary tract infection. But itching or burning in the anus can be due to various reasons. The most common causes of this problem are high humidity , mild ... of water , do not eat fried or televaja food. Do not eat stale food in the market.

Description : Controller contacts should be routinely cleaned by ________. A. blowing with compressed air B. filing with a bastard file C. wiping with a clean dry cloth D. dressing with crocus cloth

Last Answer : Answer: C

Description : If the contacts of a motor starter or controller fail to drop out when the 'stop' button is depressed the ____________. A. contacts are carrying excessive current B. contacts have become welded together C. shading coil is broken D. shading coil is loose

Last Answer : Answer: B

Description : If the line voltage to the controller shown in the illustration is 440 volts, what voltage is applied across the motor when contacts 'S' close? EL-0080 A. 110 volts B. 220 volts C. 440 volts D. 660 volts

Last Answer : Answer: B