The purpose of a short circuit forcing module (short time trip) installed in a branch line is to provide ____________. A. high speed clearance of low impedance short circuits in the branch B. continuity of service on main bus under short circuit conditions in a branch C. isolation of short circuits by selective tripping of branch circuit breakers D. all of the above

1 Answer

Answer :

Answer: D

Related questions

Description : Undervoltage trips are frequently installed on switchboard circuit breakers to trip ____________. A. out generators in the event of severe arcing or sparking B. out generators when there is reversal of power ... , but continues to run D. out generators when there is low voltage in the main circuit

Last Answer : Answer: D

Description : Periodic testing of circuit breakers is necessary to assure that a correctly rated and properly installed unit _________________. A. can trip faster as it increases in age B. will continue to provide ... not exceed its interrupting capacity D. be able to withstand at least 125% of applied voltage

Last Answer : Answer: B

Description : . If the power distribution system shown in figure 2-22 uses selective tripping, what is the time delay rating for each of the circuit breakers shown?

Last Answer : CB1-long time delay; CB2, CB3-short time delay; CB4 through

Description : The purpose of a main switchboard circuit breaker's reverse-power trip is to _____________. A. prevent main circuit overload B. protect the circuit breaker blowout coil C. prevent alternator motorization D. prevent low voltage tripout

Last Answer : Answer: C

Description : The arc resulting from the tripping of a circuit breaker is prevented from damaging the contacts by _____________. A. designing the contacts to open slowly B. directing the arc into an ... an inverse timed thermal trip for short circuit currents D. instantaneous magnetic trip for overload currents

Last Answer : Answer: B

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : Why under voltage tripping of motor is incorporated in motor feeder breakers? 

Last Answer : The under voltage can occur in case of bus fault. If the motors are kept connected they will feed the fault which may cause the damage. Due to the back feeding from the motor the motor will slow down ... case pht motor will not rotate for the designed 3 minute period in case of bus under voltage).  

Description : Operational amplifiers, used primarily in analog circuits, are characterized by ____________. A. high input impedance, high gain and low output impedance B. high input impedance, high gain and high output ... gain and high output impedance D. low input impedance, high gain and low output impedance

Last Answer : Answer: A

Description : A reverse-current relay will prevent AC generator motorization by ____________. A. automatically redirecting the load B. automatically speeding up the prime mover C. tripping the panel board main switch D. tripping the generator circuit breaker

Last Answer : Answer: D

Description : During maintenance of circuit breakers, _______________. A. always smooth roughened contact surfaces with a file B. never pass more than rated breaker current through the overload heater element C. ... wear and misalignment of main contacts D. assume heater elements installed are of correct size

Last Answer : Answer: C

Description : Component F in the illustrated device is for _________. EL-0033 A. short circut protection B. latching the trip unit closed after resetting the breaker C. overload protection D. providing a flexible connection between the input terminal G and the tripping unit E

Last Answer : Answer: C

Description : Why Isolation switches are provided along with the circuit breakers?

Last Answer : Isolation switches are provided for separating the disconnected element from the live portion of the system for the purpose of safety

Description : Why we need isolation transformers in power circuit ? why cant we use breakers to isolate?

Last Answer : In Isolation transformer is used, if there is change in parameter values of any side, the other side parameters will remain unchanged.

Description : The purpose of the reverse power relay, provided on a ship's service alternator panel, is to trip the circuit in the event of ______________. A. main circuit overload B. high power transfer C. generator overspeeding D. alternator motorization

Last Answer : Answer: D

Description : Protection against sustained overloads occurring in molded-case circuit breakers is provided by a/an __________. A. overvoltage release B. thermal acting trip C. thermal overload relay D. current overload relay

Last Answer : Answer: B

Description : When an AC or a DC motor fails to start, the FIRST step in troubleshooting should be to check the ____________. A. motor windings for obvious opens B. motor controller leads for continuity C. fuse or circuit breaker D. motor controller leads for grounds

Last Answer : Answer: C

Description : An ohmmeter can be used to measure ____________. A. current flow in a circuit B. voltage between two points in a circuit C. circuit continuity D. power

Last Answer : Answer: C

Description : Multiple grounds have developed and were initialy indicated by the grounddetecting system as one ground. The FIRST step in locating the grounds is to _____________. A. examine the main bus bars ... no longer indicates any grounds C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : Accidental grounds in a shipboard electrical system must be repaired as soon as possible as they will ____________. A. result in immediate power outages B. damage circuit breakers C. appear on the ground detection system D. damage insulation and may cause outages

Last Answer : Answer: D

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Description : A ground in an electrical circuit outside the engine room _____________. A. cannot be detected under normal conditions B. is of no consequence to engineering personnel C. is indicated at the branch circuit breaker panel D. is indicated by the ground detecting lamps on the main switchboard

Last Answer : Answer: D

Description : A megohmmeter is connected to each end of an individual motor winding. A low ohm reading indicates ____________. A. an open coil B. a loose coil C. good continuity D. a dirty coil

Last Answer : Answer: C

Description : Under normal conditions, the speed of a two-speed squirrel cage induction motor is changed by varying the ____________. A. frequency of the applied voltage B. resistance in the rotor circuit C. number of field poles D. amplitude of the applied voltage

Last Answer : Answer: C

Description : The opposition to the establishment of magnetic lines of force in a magnetic circuit is called the circuit's _______. A. resistance B. reluctance C. impedance D. inductance

Last Answer : Answer: B

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : Which of the following is/are true concerning electric power operated watertight door systems? A. Each motor driven door must use the main bus as its source of power. B. Each distribution panel for ... to permit quick activation of the system. D. Each system must have a separate branch circuit.

Last Answer : Answer: D

Description : The 'function generator' of the control circuit illustrated _______________. EL-0095 A. can be programmed to produce a non-linear output for a linear input depending on operating conditions B. is used for ... which or how many engines are needed for a required vessel speed D. all of the above

Last Answer : Answer: A

Description : As shown in the illustration, which set of conditions, evident to the operator and the 'setpoint module' respectively, will result in a high exhaust temperature alarm on the 'starboard main engine'? EL-0094 A. 50°F and 3.3 volts B. 180°F and 6.0 volts C. 750°F and 0-10 volts D. 900°F and 7.5 volts

Last Answer : Answer: D

Description : What is the purpose of the 'annunciator module' (6000F35) shown in the illustration? EL-0094 A. Provide an input to the setpoint module. B. Drive the alarm lamp and, through the controller, the horn. ... and +24 volts to their respective power supplies. D. Connect 24 volts to both sides of the horn.

Last Answer : Answer: B

Description : With both ends of a three conductor cable disconnected and arranged without the conductors touching each other, an ohmmeter reading of 'zero' ohms between the ends of one conductor would indicate _____________. A. continuity B. a partial ground C. the resistance is infinite D. a short circuit

Last Answer : Answer: A

Description : Circuit breakers are essentially (a) current carrying contacts called electrodes (b) arc extinguishers (c) circuits to break the system (d) transformers to isolate the two systems (e) any of the above

Last Answer : (a) current carrying contacts called electrodes

Description : A molded-case breaker provides protection against short circuits by using a/an ____________. A. shading coil B. arc quencher C. electromagnet D. holding coil

Last Answer : Answer: C

Description : The purpose of the automatic bus transfer shown in the illustration is to ___________. EL-0014 A. stepdown voltage to the lighting distribution panel B. provide emergency power to ... emergency switchboard from the main switchboard D. provide overcurrent protection to the lighting distribution panel

Last Answer : Answer: B

Description : To conduct an in-circuit test of a transistor, you should use a/an ____________. A. voltmeter or transistor tester B. impedance meter C. ohmmeter or transistor tester D. wattmeter

Last Answer : Answer: A

Description : In order to check the performance of a transistor removed from its circuit, the instrument to be used should be a/an ____________. A. voltmeter or transistor tester B. impedance meter C. ohmmeter or transistor tester D. sensitive potentiometer

Last Answer : Answer: C

Description : What is selective tripping and why is it used?

Last Answer : . It is the use of time delay ratings to cause the circuit breaker closest to the faulty circuit to trip. This isolates the faulty circuit without affecting other circuits.

Description : The operating torque of the upper induction disc-type element, or timer element, of an AC reverse power relay is obtained from ____________. A. the main bus B. a separate battery source C. line voltage D. electromagnets

Last Answer : Answer: D

Description : In electronic circuits, DC voltages can be positive (+) or negative (-) when measured with respect to the _________. A. printed circuit board 'common' trace B. chassis, console frame or hull 'ground' C. analogue or digital circuitry 'common' bus D. all of the above

Last Answer : Answer: D

Description : What FCN was implemented to avoid reactor trip on 220V-DC failure of PHT and PPP breakers?

Last Answer : The breaker close position supervision relay VAA 21 is changed by VAJC type, contacts position do not change if 220V-DC is lost now.

Description : The part of the shipboard electrical system used to control the distribution of power to the branch circuits, is the _____________. A. bridge control panel B. disconnect links C. governor relay box D. main switchboard

Last Answer : Answer: D

Description : A low-voltage protection circuit is used in electric motor starting equipment to _____________. A. trip circuit contactors when the motor overspeeds due to low voltage B. trip circuit ... voltage without manually resetting D. prevent the motor from restarting automatically on restoration of voltage

Last Answer : Answer: D

Description : A ground is indicated by the ground-detecting system on the main electrical switchboard. The FIRST step in locating the actual ground is to _____________. A. close all circuit breakers in ... ground detection system indicates normal C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B