A turbogenerator has a rated output of 1200 KW at 60 Hertz, with a no load frequency of 61.5 Hertz. What is its speed droop? A. 1.03% B. 1.50%  C. 2.44% D. 2.50%

1 Answer

Answer :

Answer: D

Related questions

Description : Which of the following will happen to the alternator frequency if the load is removed from a turbogenerator, whose governor has a 3% speed droop? A. It will remain unchanged. B. It will decrease by approximately 3%. C. It will become variable. D. It will increase.

Last Answer : Answer: D

Description : The standard method of controlling the output voltage of a 440 volt, 60 Hz, AC generator is accomplished by adjusting the ____________. A. prime mover speed droop B. number of poles C. alternator field excitation D. load on the alternator

Last Answer : Answer: C

Description : The output voltage of a 440 volt, 60 hertz, AC generator is controlled by the _____________. A. prime mover speed B. exciter output voltage C. load on the alternator D. number of poles

Last Answer : Answer: B

Description : A 3-phase 50HZ SCIM takes a power input of 30 KW at its full load speed of 1440 rpm. Total stator losses are 1 KW. The slip and rotor ohmic losses at full load are a) 0.02, 600 W b) 0.04, 580 W c) 0.04, 1160 W d) 0.04, 1200 W

Last Answer : Ans: 0.04, 1160 W

Description : Two AC generators of the same capacity are operating in parallel. One with a zero speed droop setting and the other with a 5% speed droop. If its capacity is not exceeded, the unit whose ... B. maintain the frequency of the system C. have poor sensitivity characteristics D. have poor power response

Last Answer : Answer: B

Description : A four pole turbogenerator is used in conjunction with a 160 pole propulsion motor. If the generator is turning at 3,200 RPM, what is the current speed of the propeller? A. 40 RPM B. 60 RPM C. 80 RPM D. 100 RPM

Last Answer : Answer: C

Description : A four-pole 60-hertz induction motor has a synchronous speed of 1800 RPM and a slip of 4 percent at full load. What will be its full load speed? A. 1728.0 RPM B. 1730.7 RPM C. 1800.0 RPM D. 1872.0 RPM

Last Answer : Answer: A

Description : If there is a reduction in the normally supplied frequency to a 120/240 volt, threephase AC current motor from 60 hertz to 55 hertz, the motor would _____________. A. run at a slower speed B. operate at a lower current C. overheat D. trip off the line

Last Answer : Answer: A

Description : A vessel is equipped with two ship's service generators. Generator #1 is rated at 900 kw and generator #2 is rated at 600 kw. During parallel operation, with a hotel load of 1,000 kw, what should be the kw load on generator #2? A. 100 kw B. 400 kw C. 500 kw D. 600 kw

Last Answer : Answer: B

Description : A circuit breaker for a 300 KW alternator is rated at 470 amperes of full continuous load. The amount of overcurrent allowed is 125%. Which of the following conditions will trip the breaker? A. ... 10 minutes. C. Momentary starting load of 550 amperes. D. Sustained current flow of 590 amperes.

Last Answer : Answer: D

Description : Two alternators rated are 200 KW at 4% regulation, 400 KW 5% regulation operating in parallel at 50HZ , when supply 600 KW the new frequency is a) 50 b) 49 c) 51.3 d) 47.7

Last Answer : Ans: 47.7

Description : The governor control switch of an alternator is moved to the 'raise' position. This action will _____________. A. raise the no-load speed setting of the governor B. raise the percentage of speed droop C. lower the no-load speed setting of the governor D. lower the percentage of speed droop

Last Answer : Answer: A

Description : A 3-phase, 400 votts, 50 Hz, 100 KW, 4 pole squirrel cage induction motor with a rated slip of 2% will have a rotor speed of (A) 1500 rpm (B) 1470 rpm (C) 1530 rpm (D) 1570 rpm

Last Answer : Ans: B N = NS (1-S) and NS =120 f / p =120 x 50 /4 = 1500 rpm ∴N= 1500 (1-0.02) =1470 rpm

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : The graph shown in the illustration represents the speed droop curves of two equal capacity alternators about to be paralleled. When paralleled, the greater portion of the total load above 60% for each unit will be picked up ... unit 'A' B. by unit 'B' C. equally by each unit D. none of the above

Last Answer : Answer: A

Description : The load sharing characteristics of two diesel alternators operating in parallel are directly related to the setting of their governors' ____________. A. load limit B. idle speed C. speed limit D. speed droop

Last Answer : Answer: D

Description : Which of the following statements is true concerning the operation of two alternators in parallel? A. The cycles per second of each alternator are the same. B. Both alternator governors must be set ... be the same on each alternator. D. The load must always be divided equally between alternators.

Last Answer : Answer: A

Description : The load sharing characteristics of two diesel generators operating in parallel are mostly dependent on their governor ____________. A. load limit settings B. idle speed settings C. speed limit settings D. speed droop settings

Last Answer : Answer: D

Description : Regarding an AC generator connected to the main electrical bus; as the electric load and power factor vary, a corresponding change is reflected in the generator armature reaction. These changes in ... . governor speed droop setting B. voltage regulator C. balance coil D. phase-balance relay

Last Answer : Answer: B

Description : What will be the frequency of a three-phase, six pole, AC generator operating at 1800 revolutions per minute? A. 60 hertz B. 90 hertz C. 120 hertz D. 180 hertz

Last Answer : Answer: B

Description : An alternator is being paralleled with one on the line. At the INSTANT the circuit breaker is closed, the frequency of the incoming alternator will normally _____________. A. increase B. not change C. decrease D. be exactly 60 hertz

Last Answer : Answer: C

Description : A split-phase induction squirrel-cage motor will not come up to speed, even though the rated voltage, rated frequency, and rated load are applied. The suspected trouble could be due to _____________. A. a faulty centrifugal switch B. broken rotor bars C. worn bearings D. all of the above

Last Answer : Answer: D

Description : The full load torque of an electric motor is the __________. A. minimum torque developed by the motor accelerating from stop to full speed B. turning moment exerted by the motor at rated load ... and frequency D. turning moment exerted by the motor from any rotor angular position at any load

Last Answer : Answer: B

Description : In the illustration, the component labeled 'EXC' is _______. EL-0003 A. a separate class II regulated DC generator for critical direct current loads B. a generator feeding the FLD ... to drive the governor for turbogenerator speed. D. the electronic driver for the switchboard metering circuits

Last Answer : Answer: B

Description : A d.c. shunt motor runs at no load speed of 1140 r.p.m. At full load, armature reaction weakens the main flux by 5% whereas the armature circuit voltage drops by 10%. The motor full load speed in r.p.m. is (A) 1080 (B) 1203 (C) 1000 (D) 1200

Last Answer : (A) 1080

Description : A 40 kW engine has a mechanical efficiency of 80 %. If the frictional power is assumed to be constant with load, what is the approximate value of the mechanical efficiency at 50 % of the rated load? (a) 45% (b) 55 % (c) 65% (d) 75%

Last Answer : Ans :c

Description : [23] Transformers are rated in KVA instead of KW because A. load power factor is often not known B. KVA is fixed whereas KW depends on load power factor C. Total transformer loss depends on volt ampere D. It has become customary

Last Answer : C. Total transformer loss depends on volt ampere

Description : An AC generator produces 60 Hz at 1800 RPM. If the generator speed is increased to 1830 RPM, the cycles will _____________. A. remain at 60 Hz B. increase to 61 Hz C. decrease to 59 Hz D. increase to 63 Hz

Last Answer : Answer: B

Description : Why are Alternators rated in kVA and not in kW?

Last Answer : The continuous power rating of any machine is generally defined as the power the machine or apparatus can deliver for a continuous period so that the losses incurred in the machine gives rise to a ... generator , the Alternators have only their apparent power in VA/kVA/MVA as their power rating.

Description : The instantaneous reduction in voltage of an AC generator, resulting from an increase in load, and prior to the automatic voltage regulator correcting the situation, is called voltage ____________. A. droop B. drop C. dip D. regulation

Last Answer : Answer: C

Description : A 50 kW dc shunt is loaded to draw rated armature current at any given speed. When driven  (i) at half the rated speed by armature voltage control and (ii) at 1.5 times the rated speed by field control, the respective output powers ... kW in (i) and 75 kW in (ii) (D) 50 kW in (i) and 50 kW in (ii)

Last Answer : A 50 kW dc shunt is loaded to draw rated armature current at any given speed. When driven  (i) at half the rated speed by armature voltage control and (ii) at 1.5 times the rated speed by field control, the respective output ... kW in (i) and 75 kW in (ii) (D) 50 kW in (i) and 50 kW in (ii)

Description : The speed of a d.c. shunt motor at no-load is (A) 5 to 10% (B) 15 to 20% (C) 25 to 30% (D) 35 to 40% higher than its speed at rated load.

Last Answer : (A) 5 to 10%

Description : The synchronous speed for a 3 phase 6-pole induction motor is 1200 rpm. If the number of poles is now reduced to 4 with the frequency remaining constant, the rotor speed with a slip of 5% will be _________. (A) 1690 rpm (B) 1750 rpm (C) 1500 rpm (D) 1710 rpm

Last Answer : (D) 1710 rpm

Description : The output voltage of a 440 volt, 60 Hz AC generator is controlled by the ______________. A. load on the alternator B. load on the prime mover C. speed of the prime mover D. exciter output voltage

Last Answer : Answer: D

Description : As shown in the illustration, when the 'speed control' system is in 'SPLIT' _______________. EL-0096 A. Relays #1, #5 and #8 are not used B. the 'slew rated controller' is grounded through Relay ... E/P converters' are bypassed and air is fed directly to the governors via the 'load sharing valve'

Last Answer : Answer: C

Description : If the driving torque, such as that produced by a diesel engine, creates pulsations when coupled with a synchronous generator operating in parallel; the generator rotor may be periodically pulled ... windings B. direct coupling C. increase governor speed droop D. decreasing governor speed droop

Last Answer : Answer: A

Description : Complete maintenance of electrical motors should include periodic checks for machine _____________. A. vibration B. watertight integrity C. speed droop D. reactive power

Last Answer : Answer: A

Description : The source of emergency lighting and power at loss of normal ship's power on a cargo vessel should be obtained from the ______________. A. emergency generator supply to the emergency ... switchboard C. battery supply to the main switchboard D. turbogenerator supply to the emergency switchboard

Last Answer : Answer: A

Description : The voltage of an operating AC turbogenerator is raised or lowered by adjusting the _____________. A. exciter generator governor controls B. synchronizing switch C. phase sequence switch D. generator field exciter

Last Answer : Answer: D

Description : The thermal radiative flux from a surface of emissivity = 0.4 is 22.68 kW/m2 . The approximate surface temperature (K) is (Stefan-Boltzmann constant = 5.67 × 10 -8 W/m2 .K4 ) (A) 1000 (B) 727 (C) 800 (D) 1200

Last Answer : (A) 1000

Description : A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is (A) 1500 r.p.m. (B) 1425 r.p.m. (C) 25 r.p.m. (D) 75 r.p.m.

Last Answer : (D) 75 r.p.m.

Description : An electrical component is connected across a 120 volt 60 hertz AC supply. What is the current drawn by the component if the impedance is 200 ohms? A. 0.01 amperes B. 0.60 amperes C. 1.67 amperes D. 100 amperes

Last Answer : Answer: B

Description : Which is a function of the voltage regulators used with AC generators? A. To cut out generators when they are no longer required. B. To cut in additional generators automatically as ... between generators operating in parallel. D. To divide reactive current between generators operating in parallel.

Last Answer : Answer: D

Description : If the centrifugal switch or relay used for cutting out the starting winding of a split-phase induction motor fails to open once the motor is in operation, the _____________. A. motor will overspeed B ... C. motor will immediately stall under load D. motor torque will be above normal at rated speed

Last Answer : Answer: B

Description : The power factor of an AC generator operating singularly is determined by the __________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: A

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description : A dc cumulatively compounded motor delivers rated load torque at rated speed. If series field is short circuited, then the armature current and speed will a) Both increases b) Both decreases c) Increases and decreases d) Decreases and increases

Last Answer : Ans: Both increases

Description : A 400 V, 15 kW, 4-pole, 50 Hz, Y-connected induction motor has full load slip of 4%. The output torque of the machine at full load is  (A) 1.66 Nm (B) 95.50 Nm (C) 99.47 Nm (D) 624.73 Nm

Last Answer : A 400 V, 15 kW, 4-pole, 50 Hz, Y-connected induction motor has full load slip of 4%. The output torque of the machine at full load is 99.47 Nm