The load sharing characteristics of two diesel alternators operating in parallel are directly related to the setting of their governors' ____________. A. load limit B. idle speed C. speed limit D. speed droop

1 Answer

Answer :

Answer: D

Related questions

Description : The load sharing characteristics of two diesel generators operating in parallel are mostly dependent on their governor ____________. A. load limit settings B. idle speed settings C. speed limit settings D. speed droop settings

Last Answer : Answer: D

Description : Which of the following statements is true concerning the operation of two alternators in parallel? A. The cycles per second of each alternator are the same. B. Both alternator governors must be set ... be the same on each alternator. D. The load must always be divided equally between alternators.

Last Answer : Answer: A

Description : To equalize the power factor of two alternators operating in parallel, the ____________. A. field excitation of both units is adjusted B. governors of both units are adjusted C. phase sequence is altered D. kilowatt load is evenly divided

Last Answer : Answer: A

Description : Two AC generators of the same capacity are operating in parallel. One with a zero speed droop setting and the other with a 5% speed droop. If its capacity is not exceeded, the unit whose ... B. maintain the frequency of the system C. have poor sensitivity characteristics D. have poor power response

Last Answer : Answer: B

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation of the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. type of alternator

Last Answer : Answer: B

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation to the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. number of field poles per alternator

Last Answer : Answer: B

Description : Equalization of the power factors of two alternators operating in parallel is accomplished _____________. A. manually, by adjusting the governor controls B. automatically, by automatic voltage regulators ... the output of current transformers D. automatically, by the designed action of the governors

Last Answer : Answer: B

Description : If the driving torque, such as that produced by a diesel engine, creates pulsations when coupled with a synchronous generator operating in parallel; the generator rotor may be periodically pulled ... windings B. direct coupling C. increase governor speed droop D. decreasing governor speed droop

Last Answer : Answer: A

Description : As shown in the illustration, when the 'speed control' system is in 'SPLIT' _______________. EL-0096 A. Relays #1, #5 and #8 are not used B. the 'slew rated controller' is grounded through Relay ... E/P converters' are bypassed and air is fed directly to the governors via the 'load sharing valve'

Last Answer : Answer: C

Description : The graph shown in the illustration represents the speed droop curves of two equal capacity alternators about to be paralleled. When paralleled, the greater portion of the total load above 60% for each unit will be picked up ... unit 'A' B. by unit 'B' C. equally by each unit D. none of the above

Last Answer : Answer: A

Description : The division of the kilowatt load between two AC generators operating in parallel is controlled by the settings and characteristics of the _____________. A. voltage regulators B. field rheostats C. reverse power relays D. prime mover governors

Last Answer : Answer: D

Description : The governor control switch of an alternator is moved to the 'raise' position. This action will _____________. A. raise the no-load speed setting of the governor B. raise the percentage of speed droop C. lower the no-load speed setting of the governor D. lower the percentage of speed droop

Last Answer : Answer: A

Description : Regarding an AC generator connected to the main electrical bus; as the electric load and power factor vary, a corresponding change is reflected in the generator armature reaction. These changes in ... . governor speed droop setting B. voltage regulator C. balance coil D. phase-balance relay

Last Answer : Answer: B

Description : The standard method of controlling the output voltage of a 440 volt, 60 Hz, AC generator is accomplished by adjusting the ____________. A. prime mover speed droop B. number of poles C. alternator field excitation D. load on the alternator

Last Answer : Answer: C

Description : If the excitation is increased to one of two alternators operating in parallel, the _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. kilowatt load will be greatly increased D. ampere load will be greatly decreased

Last Answer : Answer: A

Description : The instantaneous reduction in voltage of an AC generator, resulting from an increase in load, and prior to the automatic voltage regulator correcting the situation, is called voltage ____________. A. droop B. drop C. dip D. regulation

Last Answer : Answer: C

Description : The purpose of the bias winding in figure 'B' shown in the illustration is for ____________. EL-0091 A. changing the direction of current in the control winding B. setting the operating point of the ... use of either AC or DC in the load circuit D. changing the direction of current through the load

Last Answer : Answer: B

Description : When two generators are on the line and are sharing the load equally, they are said to be operating in _____________. A. frequency B. series C. parallel D. resonance

Last Answer : Answer: C

Description : Which of the methods listed is used to maintain equal load sharing between two compound wound DC generators operating in parallel? A. The shunt fields are interconnected. B. The shunt field rheostats ... are connected in series. D. The series fields of both generators are connected in parallel.

Last Answer : Answer: D

Description : List the factors that affect the load sharing in parallel operating generators?

Last Answer : The total active and reactive power delivered to the load, connected across the common bus-bars, are shared among Synchronous generators, operating in parallel, based on the following three factors ... characteristic/input · Excitation level and · Percentage synchronous impedance and its R/X ratio

Description : Two alternators rated are 200 KW at 4% regulation, 400 KW 5% regulation operating in parallel at 50HZ , when supply 600 KW the new frequency is a) 50 b) 49 c) 51.3 d) 47.7

Last Answer : Ans: 47.7

Description : Diesel generators #1 and #2 are operating in parallel at near full load capacity. Diesel generator #1 suddenly trips out mechanically due to low lube oil pressure. The reverse power relay functions ... all nonvital circuits. D. Secure alarms, reset reverse power relay, and restart #1 engine.

Last Answer : Answer: C

Description : Two paralleled alternators are operating near rated load. If one trips out mechanically, which of the listed actions should be taken FIRST? A. Restart the tripped machine immediately. B. Strip the board ... circuits. C. Start the emergency generator. D. Transfer all vital loads to the emergency bus.

Last Answer : Answer: B

Description : A turbogenerator has a rated output of 1200 KW at 60 Hertz, with a no load frequency of 61.5 Hertz. What is its speed droop? A. 1.03% B. 1.50% C. 2.44% D. 2.50%

Last Answer : Answer: D

Description : Which of the following will happen to the alternator frequency if the load is removed from a turbogenerator, whose governor has a 3% speed droop? A. It will remain unchanged. B. It will decrease by approximately 3%. C. It will become variable. D. It will increase.

Last Answer : Answer: D

Description : After closing the circuit breaker to place two similar alternators in parallel, the NEXT step is to balance the _____________. A. power factor B. voltage load C. kilowatt load D. ampere load

Last Answer : Answer: C

Description : The KW load is evenly distributed between two alternators just placed in parallel by adjusting _____________. A. a balance coil B. the governor settings C. the field excitation D. a rheostat

Last Answer : Answer: B

Description : If the pointer of the synchroscope is rotating in the slow direction when you are preparing to parallel two alternators, the _____________. A. incoming machine is turning faster than the load alternator B ... alternator is ready to split D. incoming machine is beginning to pick up some of the load

Last Answer : Answer: B

Description : onstant speed governors are used on ∙ Tractor engine diesel ∙ Stationary diesel engine ∙ Petrol engine ∙ None of the above

Last Answer : Stationary diesel engine

Description : variable speed governors are used on ∙ Tractor engine(diesel) ∙ Stationary engine (diesel) ∙ Petrol engine ∙ None of the above

Last Answer : ∙ Tractor engine(diesel)

Description : One function of the movable cams in a drum-type motor controller is to _____________. A. regulate the speed of the motor B. maintain resistance contacts in clean condition C. insulate the operating handle D. limit the amount of load put on the motor

Last Answer : Answer: A

Description : When paralleling two alternators the synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates the ____________. A. alternator voltages ... alternator is in phase with the bus voltage D. synchroscope pointer is defective or broken

Last Answer : Answer: C

Description : You are paralleling two alternators. The synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates that the ____________. A. alternator ... be closed C. incoming alternator is running too slowly D. synchroscope is defective or broken

Last Answer : Answer: B

Description : When two alternators are operating in parallel, the cause for circulating current is (A) increase in the excitation of one machine (B) increase in the driving torque of one machine (C) reduction in angular velocity of one machine (D) identical speed/load characteristics of both machines

Last Answer : When two alternators are operating in parallel, the cause for circulating current is (A) increase in the excitation of one machine (B) increase in the driving torque of one machine ... reduction in angular velocity of one machine (D) identical speed/load characteristics of both machines

Description : If the excitation of an alternator operating in parallel with other alternators decreased, its: (1) Power factor becomes more leading (2) Output Kw will change (3) Power factor becomes more lagging (4) Power factor becomes unity

Last Answer : If the excitation of an alternator operating in parallel with other alternators decreased, its: Power factor becomes more leading

Description : Which of the following statements is true concerning the operating characteristics of a squirrel-cage motor? A. Rotor slip is dependent upon the motor load. B. An increase in motor load results in ... results in less generated current. D. A decrease in rotor speed produces a weaker magnetic field.

Last Answer : Answer: A

Description : What generator characteristics must be considered when alternators are synchronized for parallel operation?

Last Answer : Output voltage, frequency, and phase relationships.

Description : If the driving torque, such as that produced by a diesel engine, creates pulsations when coupled with a synchronous generator operating in parallel; the generator rotor may be periodically pulled ahead or behind ... as it rotates. This co A. hunting B. direct coupling C. peaking D. harmonic coupling

Last Answer : Answer: A

Description : The division of the reactive KVA load between paralleled AC generators is initiated by the ______________. A. prime mover governors B. voltage regulators C. phase balance relay D. proportioner

Last Answer : Answer: B

Description : Two transformers of identical voltages but different capacities are operated in parallel, for satisfactory load sharing: a) Impedances should be equal b) Per unit impedance must be equal c) per unit impedance and X/R ratio must be equal d) Impedance and X/R ratio must be equal

Last Answer : Ans: C

Description : If three AC generators are operating in parallel, and one of them were to 'pull out' of synchronism with the other two generators, the ____________. A. normally operating AC generators will ... AC generators will overspeed and unload D. AC generator pulling out of synchronism will become motorized

Last Answer : Answer: B

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : Complete maintenance of electrical motors should include periodic checks for machine _____________. A. vibration B. watertight integrity C. speed droop D. reactive power

Last Answer : Answer: A

Description : State the condition to be satisfied before connecting two alternators in parallel

Last Answer : The following are the three conditions to be satisfied by synchronizing the additional Alternator with the existing one or the common bus-bars. · The terminal voltage magnitude of the incoming ... incoming Alternator voltage must be the same as the bus-bar voltage. . Zero phase difference

Description : Which of the following problems will occur if the circuit breaker of the incoming alternator is closed and it is 180° out of phase with the loaded alternator when paralleling? A. The rotor of the ... The rotor of the incoming alternator will stop. D. Both alternators will parallel 180° out of phase.

Last Answer : Answer: B

Description : Handheld phase sequence indicators are useful when ________. A. preparing to parallel alternators B. connecting lighting branch circuits C. troubleshooting DC motors D. connecting shore power lines to the ship

Last Answer : Answer: D

Description : What is need of parallel operation of alternators?

Last Answer : 1. Optimum utilization of alternators as most of the power stations are interconnected by grid. 2. Reduced operating cost: number of alternators operating at a time can be changed depending on ... demands. 3. Easy maintenance: Alternator may be shut down for maintenance 4. Continuity and reliability