The governor control switch of an alternator is moved to the 'raise' position. This action will _____________. A. raise the no-load speed setting of the governor B. raise the percentage of speed droop C. lower the no-load speed setting of the governor D. lower the percentage of speed droop

1 Answer

Answer :

Answer: A

Related questions

Description : Two AC generators of the same capacity are operating in parallel. One with a zero speed droop setting and the other with a 5% speed droop. If its capacity is not exceeded, the unit whose ... B. maintain the frequency of the system C. have poor sensitivity characteristics D. have poor power response

Last Answer : Answer: B

Description : Which of the following will happen to the alternator frequency if the load is removed from a turbogenerator, whose governor has a 3% speed droop? A. It will remain unchanged. B. It will decrease by approximately 3%. C. It will become variable. D. It will increase.

Last Answer : Answer: D

Description : Regarding an AC generator connected to the main electrical bus; as the electric load and power factor vary, a corresponding change is reflected in the generator armature reaction. These changes in ... . governor speed droop setting B. voltage regulator C. balance coil D. phase-balance relay

Last Answer : Answer: B

Description : The frequency of an alternator is controlled from the main switchboard by adjusting the _____________. A. frequency meter B. voltage regulator C. governor control D. sychroscope switch

Last Answer : Answer: C

Description : Which of the following statements is true concerning the operation of two alternators in parallel? A. The cycles per second of each alternator are the same. B. Both alternator governors must be set ... be the same on each alternator. D. The load must always be divided equally between alternators.

Last Answer : Answer: A

Description : The standard method of controlling the output voltage of a 440 volt, 60 Hz, AC generator is accomplished by adjusting the ____________. A. prime mover speed droop B. number of poles C. alternator field excitation D. load on the alternator

Last Answer : Answer: C

Description : If the driving torque, such as that produced by a diesel engine, creates pulsations when coupled with a synchronous generator operating in parallel; the generator rotor may be periodically pulled ... windings B. direct coupling C. increase governor speed droop D. decreasing governor speed droop

Last Answer : Answer: A

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : The load sharing characteristics of two diesel generators operating in parallel are mostly dependent on their governor ____________. A. load limit settings B. idle speed settings C. speed limit settings D. speed droop settings

Last Answer : Answer: D

Description : The load sharing characteristics of two diesel alternators operating in parallel are directly related to the setting of their governors' ____________. A. load limit B. idle speed C. speed limit D. speed droop

Last Answer : Answer: D

Description : The graph shown in the illustration represents the speed droop curves of two equal capacity alternators about to be paralleled. When paralleled, the greater portion of the total load above 60% for each unit will be picked up ... unit 'A' B. by unit 'B' C. equally by each unit D. none of the above

Last Answer : Answer: A

Description : As shown in the illustration, what is responsible for maintaining the "LV" relay energized when the master switch handle is moved away from the "off" position? EL-0102 A. "DBa" contact. B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : The device labeled 'REG SW' in the illustration is used to ___________. EL-0003 A. shift from the automatic voltage regulator to the manual voltage regulator B. shift the governor control from manual to ... device 'REG ADJ' or device 'MAN ADJ' D. supply regulated control power to the switchboard

Last Answer : Answer: A

Description : Equal power factors on paralleled AC generators are maintained by an automatic _____________. A. voltage regulator B. reverse power relay C. reverse current relay D. governor control switch

Last Answer : Answer: A

Description : Complete maintenance of electrical motors should include periodic checks for machine _____________. A. vibration B. watertight integrity C. speed droop D. reactive power

Last Answer : Answer: A

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation of the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. type of alternator

Last Answer : Answer: B

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation to the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. number of field poles per alternator

Last Answer : Answer: B

Description : The output voltage of a 440 volt, 60 hertz, AC generator is controlled by the _____________. A. prime mover speed B. exciter output voltage C. load on the alternator D. number of poles

Last Answer : Answer: B

Description : A turbogenerator has a rated output of 1200 KW at 60 Hertz, with a no load frequency of 61.5 Hertz. What is its speed droop? A. 1.03% B. 1.50% C. 2.44% D. 2.50%

Last Answer : Answer: D

Description : The kilowatt load can be adjusted on a paralleled generator by using the _____________. A. field rheostat B. governor control C. automatic voltage regulators D. hand tachometer

Last Answer : Answer: B

Description : If two AC generators have just been placed in parallel, the true power load is initially distributed evenly by _____________. A. a balance coil B. changing field excitation C. adjusting the governor control settings D. a rheostat

Last Answer : Answer: C

Description : As shown in the illustration, once the "LV" relay is energized for operation, what contacts must remain closed to maintain the "LV" relay energized when the control lever is moved away from the "off" or "stop" ... . B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : If the energy input is significantly reduced to the prime mover of one shipboard alternator operating in parallel with others, that alternator will _____________. A. continue to operate at no load B. lose ... overspeed C. begin to motorize and then trip out D. slow down and operate at reduced load

Last Answer : Answer: C

Description : The voltage of an operating AC turbogenerator is raised or lowered by adjusting the _____________. A. exciter generator governor controls B. synchronizing switch C. phase sequence switch D. generator field exciter

Last Answer : Answer: D

Description : A split-phase induction squirrel-cage motor will not come up to speed, even though the rated voltage, rated frequency, and rated load are applied. The suspected trouble could be due to _____________. A. a faulty centrifugal switch B. broken rotor bars C. worn bearings D. all of the above

Last Answer : Answer: D

Description : If the centrifugal switch or relay used for cutting out the starting winding of a split-phase induction motor fails to open once the motor is in operation, the _____________. A. motor will overspeed B ... C. motor will immediately stall under load D. motor torque will be above normal at rated speed

Last Answer : Answer: B

Description : How can the speed variation be reduced by making a governor droop adjustment?

Last Answer : If the internal droop setting is increased, the speed variation will reduce.

Description : Moving the rheostat handle shown in the illustration, that is used to control a DC generator, towards the 'raise' direction will increase the _____________. EL-0030 A. field resistance B. armature resistance C. armature speed D. line voltage

Last Answer : Answer: D

Description : A degree of control over the speed of a slip ring induction motor can be obtained by _____________. A. adjusting governor linkage B. changing the number of phases to the motor C. inserting resistance into the stator circuit D. inserting resistance into the rotor circuit

Last Answer : Answer: D

Description : Prior to starting an AC generator prime mover, the voltage regulator cutout switch should be placed in the __________. A. manual position B. bus neutral position C. raise voltage position D. transfer position

Last Answer : Answer: A

Description : The frequency of an AC generator is adjusted by means of the ____________. A. main alternator field rheostat B. exciter field rheostat C. prime mover governor control D. equalizing reactor

Last Answer : Answer: C

Description : The heating of conductors as a result of resistance in a distribution circuit causes a power loss expressed as _____________. A. line droop B. line loss C. IR drop D. hysteresis

Last Answer : Answer: B

Description : Motorization of an alternator is undesirable because _____________. A. the alternator will be damaged B. it puts an additional load on the bus C. high voltage pulses are induced in the bus D. all of the above

Last Answer : Answer: B

Description : If the excitation of an alternator operating in parallel is decreased below normal, its _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. ampere load will be greatly increased D. kilowatt load will be greatly decreased

Last Answer : Answer: B

Description : A three-phase alternator is operating at 450 volts, 250 amps at 0.6 power factor. If the power factor increases to 0.8, the kw load potential will increase by _____________. A. 38.525 kw B. 116.91 kw C. 155.88 kw D. 194.85 kw

Last Answer : Answer: A

Description : If field excitation is suddenly lost to an alternator operating in parallel, that alternator will _____________. A. supply excessive current to the bus B. operate at the same load, but with reduced voltage C. lose its load and tend to overspeed D. become overloaded and slow down

Last Answer : Answer: C

Description : A change in field excitation of an alternator operating in parallel will cause a change in its _____________. A. alternator frequency B. kilowatt load C. voltage output D. all of the above

Last Answer : Answer: C

Description : If the pointer of the synchroscope is rotating in the slow direction when you are preparing to parallel two alternators, the _____________. A. incoming machine is turning faster than the load alternator B ... alternator is ready to split D. incoming machine is beginning to pick up some of the load

Last Answer : Answer: B

Description : When paralleling two AC generators, the frequency of the incoming machine immediately prior to closing its breaker should be ____________. A. controlled by placing the governor switch in the automatic ... regulator C. slightly greater than the bus frequency D. slightly less than the bus frequency

Last Answer : Answer: C

Description : The cycles per second developed by the alternator aboard your vessel is determined by _____________. A. the speed of the engine driving the alternator B. the resistance applied to the field rheostat C. the synchronous speed of induction D. the adjustments made to the voltage regulator

Last Answer : Answer: A

Description : The frequency output of an operating alternator is controlled by the _____________. A. relative speed of the rotor poles B. number of turns of wire in the armature coil C. strength of the magnets used D. output voltage

Last Answer : Answer: A

Description : Equalization of the power factors of two alternators operating in parallel is accomplished _____________. A. manually, by adjusting the governor controls B. automatically, by automatic voltage regulators ... the output of current transformers D. automatically, by the designed action of the governors

Last Answer : Answer: B

Description : The KW load is evenly distributed between two alternators just placed in parallel by adjusting _____________. A. a balance coil B. the governor settings C. the field excitation D. a rheostat

Last Answer : Answer: B

Description : Kilowatt load is divided between two AC generators operating in parallel by _____________. A. adjusting the governor controls B. varying the excitation voltage C. increasing both prime mover speeds simultaneously D. decreasing both prime mover speeds simultaneously

Last Answer : Answer: A

Description : The instantaneous reduction in voltage of an AC generator, resulting from an increase in load, and prior to the automatic voltage regulator correcting the situation, is called voltage ____________. A. droop B. drop C. dip D. regulation

Last Answer : Answer: C

Description : The speed of a wound-rotor induction motor _____________. A. will be fixed by the number of field poles B. can be varied by a rheostat-type control C. can only be synchronous speed at full load D. can only attain synchronous speed at no load

Last Answer : Answer: B