An alternator is delivering rated current at rated voltage and 0.8 power-factor lagging. For delivering rated current at rated voltage and 0.8 poWer—factor leading, the required excitation will be: 

(A) less  (B) more (C) more or less (D) the same

1 Answer

Answer :

An alternator is delivering rated current at rated voltage and 0.8 power -factor lagging. For delivering rated current at rated voltage and 0.8 power -factor leading, the required excitation will be: more 

Related questions

Description : An alternator is delivering rated current at rated voltage and 0.8 power-factor lagging case. If it is required to deliver rated current at rated voltage and 0.8 power-factor leading, the required excitation will be (A) less. (B) more. (C) more or less. (D) the same.

Last Answer : Ans: B Over excitation gives leading power factor and under excitation gives lagging p.f .

Description : In an alternator at lagging power factor the generated voltage per phase as compared to that at unity power factor?

Last Answer : In an alternator, at lagging power factor the generated voltage per phase as compared to that at unity power factor must be more than terminal voltage.

Description : When Alternator excitation increases and machine is operating at lagging power factor then a) I increase b) I decreases c) No effect on current d) None

Last Answer : Ans: I increase

Description : In a synchronous generator delivering lagging power factor load  (1) the excitation emf leads terminal voltage by the power angle (2) the excitation emf lags terminal voltage by the power angle (3) ... by the power factor angle (4) excitation emf lags the terminal voltage by the power factor angle

Last Answer : In a synchronous generator delivering lagging power factor load the excitation emf leads terminal voltage by the power angle

Description : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the ... the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

Last Answer : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume ... the shaft. The accelerating torque in the generator in MNm at the time of fault will be 1.018 

Description : A alternator is delivering power to a balanced load at unit power factor. The phase angle between the line voltage and the line current is? (A) 90° (B) 60° (C) 30° (D) 0° 

Last Answer : A alternator is delivering power to a balanced load at unit power factor. The phase angle between the line voltage and the line current is 30°

Description : A synchronous generator is feeding a zero power factor (lagging) load at rated current. The armature reaction is  (A) magnetizing (B) demagnetizing (C) cross-magnetizing (D) ineffective

Last Answer : A synchronous generator is feeding a zero power factor (lagging) load at rated current. The armature reaction is demagnetizing 

Description : If the excitation of an alternator operating in parallel is decreased below normal, its _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. ampere load will be greatly increased D. kilowatt load will be greatly decreased

Last Answer : Answer: B

Description : A three-phase synchronous motor has a terminal voltage of 460 V and a terminal current of 120 A at a power factor of 0.95 lagging, synchronous reactance of 1.68 ohm and the field current is 47 A. The field to armature mutual ... _____________.      (a). 20mH   (b). 16mH   (c). 24mH   (d). 22mH

Last Answer : 22

Description : A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is (A) 1500 r.p.m. (B) 1425 r.p.m. (C) 25 r.p.m. (D) 75 r.p.m.

Last Answer : (D) 75 r.p.m.

Description : When voltage and current developed in an AC circuit reach their peak values at the same time, the power factor is _____________. A. lagging B. leading C. maximum D. minimum

Last Answer : Answer: C

Description : When the voltage and the current developed in an AC circuit reach their peak values at the same time, the power factor is considered to be _____________. A. lagging B. leading C. unity D. infinity

Last Answer : Answer: C

Description : A 400 V, 50 Hz 30 hp, three-phase induction motor is drawing 50 A current at 0.8 power factor lagging. The stator and rotor copper losses are 1.5 kW and 900 W respectively. The friction and windage losses are 1050 W and the ... the motor will be (A) 23.06 kW (B) 24.11 kW (C) 25.01 kW (D) 26.21 kW

Last Answer : A 400 V, 50 Hz 30 hp, three-phase induction motor is drawing 50 A current at 0.8 power factor lagging. The stator and rotor copper losses are 1.5 kW and 900 W respectively. The friction and windage losses are 1050 W and the core losses are 1200 W. The air-gap power of the motor will be 25.01 kW

Description : A three phase transmission line delivers a load of 5 MW at 0.8 power factor lagging. Resistance of each conductor is 0.5 ohm / km. Receiving end voltage is 33 kV. If the line loss is not to exceed 10%, determine the length of the line.  (A) 7 km (B) 27.9 km (C) 56.8 km (D) 13.9 km

Last Answer : B

Description : The input of an A.C. circuit having power factor of 0.8 lagging is 40 kVA The power drawn by the circuit is?

Last Answer : The input of an A.C. circuit having power factor of 0.8 lagging is 40 kVA The power drawn by the circuit is 32 kW.

Description : A two-winding single phase transformer has a voltage regulation of 4.5% at full-load and unity power-factor. At full-load and 0.80 power-factor lagging load the voltage regulation will be (A) 4.5%. (B) less than 4.5%. (C) more than 4.5%. (D) 4.5% or more than 4.5%.

Last Answer : (C) more than 4.5%.

Description : A transformer has negative voltage regulation when its load power factor is- (a) Zero (b) Unity (c) Leading (d) Lagging

Last Answer : Ans: C

Description : 51 A transformer has negative voltage regulation when its load power factor is A. Zero B. Unity C. Leading D. Lagging

Last Answer : C. leading

Description : When 220V dc shunt alternator generating the voltage at rated value. If direction of rotation is reversed, then alternator will a) Build up its voltage with same polarity b) Build up its voltage with opposite polarity c) No build up of voltage d) None

Last Answer : Ans: No build up of voltage

Description : A single phase 60 Hz generator supplies an inductive load of 4500kW at a power factor of 0.80 lagging by means of a 20 km long overhead transmission line. The line resistance and inductance are 0.0195 ohm and 0.60 mH ... voltage regulation of the line.  (A) 12.59% (B) 16.34% (C) 32.68% (D) 41.15% 

Last Answer : Answer is C

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation of the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. type of alternator

Last Answer : Answer: B

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation to the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. number of field poles per alternator

Last Answer : Answer: B

Description : Explain lagging quantity and leading quantity, explain this concept with voltage and current waveform

Last Answer : When two alternating quantities attain their respective zero or peak values simultaneously, the quantities are said to be in-phase quantities. When the quantities do not attain their respective zero or ... current is leading the voltage or the voltage is said to be lagging behind the current.

Description : At dead short circuit at terminals of Alternator then the current I is a) ZPF Lag b) ZPF lead c) Unity power factor d) 0.8 Power factor lag

Last Answer : Ans: ZPF Lag

Description : A synchronous motor operates at 0.8 pf lagging. If the field current of the motor is continuously increased  1. The power factor decreases upto a certain value of field current and thereafter it increases.  2. The armature current ... the correct answer is (a) 1, 2 (b) 3, 4 (c) 1, 3 (d) 2, 4

Last Answer : A synchronous motor operates at 0.8 pf lagging. If the field current of the motor is continuously increased  1. The power factor decreases upto a certain value of field current and thereafter it increases.  2. The armature current ... the correct answer is (a) 1, 2 (b) 3, 4 (c) 1, 3 (d) 2, 4

Description : A synchronous motor is operating on no-load at unity power factor. If the field current is increased, power factor will become (A) Leading & current will decrease (B) Lagging & current will increase. (C) Lagging & current will decrease. (D) Leading & current will increase.

Last Answer : Ans: A Initially synchronous motor is operating at no load and unity power factor. When field current increases, the excitation will increase. Therefore, p.f will be leading and current will be I CosΦ < I

Description : If the lagging power factor of the load decreases, the line losses will (A) Decrease (B) Increase (C) Flrst decrease and then Increase (D) Remain same

Last Answer : If the lagging power factor of the load decreases, the line losses will Increase

Description : A circuit breaker for a 300 KW alternator is rated at 470 amperes of full continuous load. The amount of overcurrent allowed is 125%. Which of the following conditions will trip the breaker? A. ... 10 minutes. C. Momentary starting load of 550 amperes. D. Sustained current flow of 590 amperes.

Last Answer : Answer: D

Description : To remove an alternator operating in parallel with another unit from the main electrical bus, you must FIRST _________. A. adjust the power factor on both units B. set the desired voltage on ... C. open the circuit breaker on the outgoing alternator D. remove the load from the outgoing alternator

Last Answer : Answer: D

Description : The arc voltage produced in A.C. circuit breaker is always (a) in phase with the arc current (b) lagging the arc current by 90" (c) leading the arc current by 90° (d) none of the above

Last Answer : (a) in phase with the arc current

Description : A three-phase alternator is operating at 450 volts, 250 amps at 0.6 power factor. If the power factor increases to 0.8, the kw load potential will increase by _____________. A. 38.525 kw B. 116.91 kw C. 155.88 kw D. 194.85 kw

Last Answer : Answer: A

Description : A three-phase alternator operates at 450 volts with a power factor of 0.8. If the ammeter indicates 250 amperes, what should be the KW meter reading? A. 90.00 KW B. 127.27 KW C. 155.70 KW D. 194.85 KW

Last Answer : Answer: C

Description : A three-phase alternator is developing 300 amps, with a 0.8 power factor, at 450 volts. The true indicated power on the kilowatt meter, located on the main switchboard, will be ____________. A. 133 kw B. 155 kw C. 187 kw D. 212 kw

Last Answer : Answer: C

Description : A three-phase alternator is operating at 450 volts with the switchboard ammeter indicating 300 amps. The kw meter currently indicates 163.6 KW, with a power factor of 0.7. If the power factor increases to 0.8, the KW meter would then read ____________. A. 181.4 KW B. 186.8 KW C. 194.2 KW D. 201.4 KW

Last Answer : Answer: B

Description : A three-phase alternator is operating at 450 volts with the switchboard ammeter indicating 300 amps. The kw meter currently indicates 163.6 KW, with a power factor of 0.7. If the power factor increases to 0.8, the KW meter reading would increase by ___ A. 17.8 KW B. 23.2 KW C. 30.6 KW D. 37.8 KW

Last Answer : Answer: B

Description : A dc shunt generator has a speed of 800 rpm when delivering 20 A to the load at the terminal voltage of 220V. If the same machine is run as a motor it takes a line current of 20A from 220V supply. The speed of ... . (B) more than 800 rpm. (C) less than 800 rpm. (D) both higher or lower than 800 rpm.

Last Answer : (C) less than 800 rpm.

Description : The power factor of an AC generator operating singularly is determined by the __________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: A

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description : What is Lagging Power Factor ?

Last Answer : When the inductive load of an AC circuit exceeds the capacitive load , the pf of the circuit is called lagging pf .

Description : What is lagging power factor ?

Last Answer : When the amount of inductive load is greater than the capacitive load in a circuit then the power factor of that circuit is called lagging power factor.

Description : What is lagging power factor ?

Last Answer : The cosine value of the phase angle between current and voltage in an inductive circuit is called lagging power factor.

Description : When is the power factor lagging , leading , unity ?

Last Answer : Power factor lagging in inductive load. Power factor leading in capacitive load is power factor unity in resistive load.

Last Answer : a . C. _ On the circuit Capacitive Of load Than Inductive Load More If so , the current Of voltage Later Location By , of the circuit This In condition Power To the factor Lagging Power Factor Says. This To the circuit Inductive Circuit Says.

Description : If the excitation is increased to one of two alternators operating in parallel, the _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. kilowatt load will be greatly increased D. ampere load will be greatly decreased

Last Answer : Answer: A

Description : The power factor of industrial loads is generally (a) unity (b) lagging (c) leading (d) zero

Last Answer : (b) lagging

Description : [75] Two transformers are connected in parallel. These transformers do not have equal percentage impedance which results A. Short-circuiting of the secondaries B. Power factor of one of the ... have negligible core losses D. Loading of the transformers not in proportion to their kVA ratings.

Last Answer : D. Loading of the transformers not in proportion to their kVA ratings

Description : ___________ is device that measures the internal open circuit voltage of an equivalent noise generator having an impedance of 600Ω and delivering noise power to a 600 Ω load. A. Psophometer B. Barometer C. Reflectometer D. Voltmeter

Last Answer : A. Psophometer

Description : What is the pitch factor of a 4 pole alternator having 36 slots and a coil span of 1 to 8?  (A) 140° (B) 80° (C) 20° (D) 40°

Last Answer : C

Description : One factor that determines the frequency of an alternator is the ____________. A. number of turns of wire in the armature coil B. number of magnetic poles C. strength of the magnets used D. output voltage

Last Answer : Answer: B

Description : A 200 V, 50 Hz inductive circuit takes a current of 10 A at 30 degree lagging pf, what is the inductive reactance of the circuit?  (A) 17.8 Ω (B) 100 Ω (C) 178 Ω (D) 10 Ω 

Last Answer : D