Two wattmeters are used to measure the power in a 3 -phase balanced system. What is the power factor of the load when one wattmeter reads twice the other ? 

(a) 0 (b) 0.5 (c) 0.866 (d) 1

1 Answer

Answer :

Two wattmeters are used to measure the power in a 3 -phase balanced system. What is the power factor of the load when one wattmeter reads twice the other ?

 0.866

Related questions

Description : Two wattmeters connected to measure the power input to a balanced three-phase circuit indicate 4.5 KW and 3 KW respectively. Find the power factor of the circuit. A. 0.7 B. 0.8 C. 0.95 D. 0 

Last Answer : Two wattmeters connected to measure the power input to a balanced three-phase circuit indicate 4.5 KW and 3 KW respectively. Find the power factor of the circuit.  0.95

Description : Two wattmeter method is employed to measure power in a 3 -phase balanced system with the current coil connected in the A and C lines. The phase sequence is ABC. If the wattmeter with its current coil in A -phase line reads zero, then the power factor of the 3 -phase load will be

Last Answer : Two wattmeter method is employed to measure power in a 3 -phase balanced system with the current coil connected in the A and C lines. The phase sequence is ABC. If the wattmeter with its current coil in A -phase line reads zero, then the power factor of the 3 -phase load will be 0.5 lagging.

Description : The power delivered to a 3-phase load can be measured by the use of two wattmeters only when the  (a) load is unbalanced (b) load is balanced (c) three phase load is connected to the source through three wires (d) three phase load is connected to the source through four wires

Last Answer : The power delivered to a 3-phase load can be measured by the use of two wattmeters only when the three phase load is connected to the source through three wires 

Description : In a 3-phase power measurement by two wattmeter method, both the watt meters had identical readings. The power factor of the load was?

Last Answer : In a 3-phase power measurement by two wattmeter method, both the watt meters had identical readings. The power factor of the load was unity.

Description : A alternator is delivering power to a balanced load at unit power factor. The phase angle between the line voltage and the line current is? (A) 90° (B) 60° (C) 30° (D) 0° 

Last Answer : A alternator is delivering power to a balanced load at unit power factor. The phase angle between the line voltage and the line current is 30°

Description : The power in a 3phase circuit is measured with the help of 2 wattmeters. The reading of one of wattmeters is positive and that of the others is negative. The magnitude of readings is different. It can be concluded that the ... (A) Unity (B) 2 (lagging) (C) 5 (lagging) (D) Less than 0.5 (lagging)

Last Answer : A

Description : The minimum number of wattmeter(s) required to measure 3-phase, 3-wire balanced or unbalanced power is  A) 1 B) 2 C) 3 D) 4

Last Answer : B

Description : What is the advantage of using in-line wattmeters over output power meters?

Last Answer : Most in-line wattmeters are capable of measuring both forward and reflected power.

Description : In a balanced 3 -phase 200 V circuit, the line current is 115.5 A. When the power is measured by two wattmeter method, one of the wattmeters reads 20 kW and the other one reads zero. What is the power factor of the load ?

Last Answer : In a balanced 3 -phase 200 V circuit, the line current is 115.5 A. When the power is measured by two wattmeter method, one of the wattmeters reads 20 kW and the other one reads zero. What is the power factor of the load ?  0.5

Description : Total instantaneous power supplied by a 3-phase ac supply to a balanced R-L load is

Last Answer : Total instantaneous power supplied by a 3-phase ac supply to a balanced R-L load is constant

Description : What type of device is used to extend the current measuring capability of electrodynamic wattmeters?

Last Answer : Current transformers.

Last Answer : For handling greater currents induction wattmeters are used in conjunction with current transformers.

Description : At a particular instant, the R-phase voltage of a balanced 3-phase system is + 30 V, and the Y-phase voltage is – 90 V. The voltage of B-phase at that instant is (A) + 120 V (B) – 120 V (C) – 60 V (D) + 60 V

Last Answer : At a particular instant, the R-phase voltage of a balanced 3-phase system is + 30 V, and the Y-phase voltage is – 90 V. The voltage of B-phase at that instant is + 60 V

Description : In a three-phase system, when the loads are perfectly balanced, the value of neutral current is equal to: A. Zero B. One-third of the maximum value C. Two -third of the maximum value D. The maximum value

Last Answer : In a three-phase system, when the loads are perfectly balanced, the value of neutral current is equal to: Zero

Description : Define balanced 3 phase load.

Last Answer : Balanced 3 phase Load: Balanced three phase load is defined as star or delta connection of three equal impedances having equal real parts and equal imaginary parts. It takes same current of equal magnitude and equal phase angle.

Description : Define balanced and unbalanced load in three phase circuit.

Last Answer : Balanced Load: When all the imedances of 3 phases are equal in magnitude and of same nature then load is said to be balanced.  Unbalanced Load: When all the imedances of 3 phases are not equal in magnitude and of different nature then load is said to be unbalanced.

Description : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Last Answer : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Description : Three equal impedances are first connected in delta across a 3 -phase balanced supply. If the same impedances are connected in star across the same supply then,

Last Answer : A

Description : A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is: (A) 1500 r.p.m. (B) 1425 r.p.m. (C) 25 r.p.m. (D) 75 r.p.m

Last Answer : A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is: 75 r.p.m

Description :  In the measurement of power of balanced load by two wattmeter method in a 3-phase circuit, The readings of the wattmeters are 4 kW and 2 kW respectively, the later is being taken after reversing the connections of current coil. the ... kVAR B) 0.2 & 6 √3 kVAR C) 0.32 & 2 kVAR D) 0.32 & 2 √3 kVAR

Last Answer :  In the measurement of power of balanced load by two wattmeter method in a 3-phase circuit, The readings of the wattmeters are 4 kW and 2 kW respectively, the later is being taken after reversing the ... of current coil. the power factor and reactive power of the load is 0.2 & 6 √3 kVAR

Last Answer : The power measurement in a balanced 3-phase circuit can be done by: One wattmeter method, Two wattmeter method, Three wattmeter method.

Last Answer : A balanced 3-phase system consists of positive sequence currents.

Description : During Phase 2 of action potential in cardiac cell, depolarizing current through calcium channels is balanced by (a) Delayed rectifier potassium current (b) outward chloride channel (c) Both (a) and (b) (d) None of the above

Last Answer : Ans: A

Description : In the phase shift method, How many circuits must be balanced? A. None of these B. 1 C. 4 D. 2

Last Answer : D. 2

Description : A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is (A) 1500 r.p.m. (B) 1425 r.p.m. (C) 25 r.p.m. (D) 75 r.p.m.

Last Answer : (D) 75 r.p.m.

Description : Power (P) in a 3 phase circuit with two watt meters at unity power factor is (W1 & W2 = watt meter readings)

Last Answer : Power (P) in a 3 phase circuit with two watt meters at unity power factor is P = W1 + W2 (W1 & W2 = watt meter readings)

Description : With a neat sketch explain working of 1 phase dynamometer type power factor meter.

Last Answer : Working of 1 phase dynamometer type power factor meter : The current coil is connected in series with load. Two pressure coils marked as A and B are connected across the supply terminals ... becomes stationary and the pointer shows steady deflection corresponding to the power factor of the load. 

Description : What is the power factor when a single phase watt meter operating on 200 V and 5 A for 5 hours makes 2016 revolutions and the meter constant in revolution is 420? A) 0.04 B) 1.04 C) 0.96 D) None of these

Last Answer : What is the power factor when a single phase watt meter operating on 200 V and 5 A for 5 hours makes 2016 revolutions and the meter constant in revolution is 420? A) 0.04 B) 1.04 C) 0.96 D) None of these

Description : A 230 V/460 V single-phase transformer operating at 20 A and unity power factor has primary referred resistance of 0.2 Ω and reactance of 0.5 Ω. The approximate primary induced emf is (A) 216 V (B) 226 V (C) 234 V (D) 236 V

Last Answer : A 230 V/460 V single-phase transformer operating at 20 A and unity power factor has primary referred resistance of 0.2 Ω and reactance of 0.5 Ω. The approximate primary induced emf is 226 V

Description : A three-phase star -connected load is operating at a power factor angle ϕ  with ϕ being the angle between

Last Answer : A three-phase star -connected load is operating at a power factor angle ϕ  with ϕ being the angle between Phase voltage and phase current

Description : A three phase transmission line delivers a load of 5 MW at 0.8 power factor lagging. Resistance of each conductor is 0.5 ohm / km. Receiving end voltage is 33 kV. If the line loss is not to exceed 10%, determine the length of the line.  (A) 7 km (B) 27.9 km (C) 56.8 km (D) 13.9 km

Last Answer : B

Description : A single phase 60 Hz generator supplies an inductive load of 4500kW at a power factor of 0.80 lagging by means of a 20 km long overhead transmission line. The line resistance and inductance are 0.0195 ohm and 0.60 mH ... voltage regulation of the line.  (A) 12.59% (B) 16.34% (C) 32.68% (D) 41.15% 

Last Answer : Answer is C

Description : Illustrate how can you use a single-phase wattmeter to measure 3 phase reactive power in a circuit?

Last Answer : We can measure reactive power of 3 phase circuit by dingle phase wattmeter by connecting the current coil in series with a line or load and connecting the pressure coil across the other two lines.  Reactive power = 3√ V * I * sinϕ Watts. 

Last Answer : In the case of power measurement by two wattmeter method in a balanced 3Φ system with a pure inductive load both the Wattmeter will indicate the same but of opposite sign.

Description : What is a system in which the power of one branch of government are balanced by the powers of another?

Last Answer : Need answer

Description : Measurement of power and power factor of a 3-phase system by two wattmeter method can be obtained in case of  1. Balanced load and balanced source  2. Balanced source with 3-phase 3-wire unbalanced load  3. Unbalanced source with 3-phase 3 ... b) 2, 3 and 5 (c) 1, 2, 3, 4 and 5 (d) 1, 2, 3 and 5 

Last Answer : Measurement of power and power factor of a 3-phase system by two wattmeter method can be obtained in case of  1. Balanced load and balanced source  2. Balanced source with 3-phase 3-wire unbalanced load  3. Unbalanced source with 3- ... b) 2, 3 and 5 (c) 1, 2, 3, 4 and 5 (d) 1, 2, 3 and 5 

Description : A figure of merit used to measure the performance of a radiation detector. A. Noise equivalent power B. Ripple factor C. Safe factor D. Quality factor

Last Answer : A. Noise equivalent power

Description : How do you measure power factor?

Last Answer : P= 1.83*V*I*COS@ where P is power           V is voltage            I is current           COS @ is P.F COS@= P/(1.83*V*I)  in other way cos @ = true power/apparent power

Description : Which of the following statements is true concerning all three-phase alternators? A. Each has three separate but identical armature windings acted on by one system of rotating magnets. B. Each has one ... The three phases always provide power to the load through three sets of slip rings and brushes.

Last Answer : Answer: A

Description : The transformer which transforms unbalanced line to a balanced line is better known as  (A) Impedance transformer (B) Amplifier (C) Balun (D) Oscillator

Last Answer : The transformer which transforms unbalanced line to a balanced line is better known as Balun 

Description : (a) Define permeability. (b) Define MMF. (c) Define form factor of an alternating quantity. (d) Define frequency and time period of an alternating quality. (e) Define transformation ratio of transformer. ... and state the meaning of each term used. (g) Give two applications of single phase motors. 

Last Answer : Permeability : It is the ability of a magnetic/Non magnetic material to allow setting up of flux in it.  MMF : The magneto motive force (MMF) is the force required to setup flux in a magnetic / ... applications of single phase motors : Water pumps, ceiling fan, lathe machine

Description : The power consumed by a balanced 3-ph load is measured by two-wattmeter method. The meter readings are 8 kW and 4 kW. The power factor of the load is (A) zero (B) 0.5 (C) between zero and 0.5 (D) between 0.5 and unity

Last Answer : The power consumed by a balanced 3-ph load is measured by two-wattmeter method. The meter readings are 8 kW and 4 kW. The power factor of the load is between 0.5 and unity

Description : To equalize the power factor of two alternators operating in parallel, the ____________. A. field excitation of both units is adjusted B. governors of both units are adjusted C. phase sequence is altered D. kilowatt load is evenly divided

Last Answer : Answer: A

Description : A two-winding single phase transformer has a voltage regulation of 4.5% at full-load and unity power-factor. At full-load and 0.80 power-factor lagging load the voltage regulation will be (A) 4.5%. (B) less than 4.5%. (C) more than 4.5%. (D) 4.5% or more than 4.5%.

Last Answer : (C) more than 4.5%.

Description : For power measurement of three phase circuit by two wattmeter method, when the value of power factor is less than 0.5 lagging:

Last Answer : For power measurement of three phase circuit by two wattmeter method, when the value of power factor is less than 0.5 lagging: One of the wattmeter connections will have to be reversed

Last Answer : In a dynamometer 3-phase power factor meter, the planes of the two moving coils are at 120°.

Last Answer : In a single phase power factor meter the phase difference between the currents in the two pressure coils is exactly 90°.

Last Answer : The two pressure coils of a single phase power factor meter have the same dimensions and the same number of turns.

Description : A three-phase alternator is operating at 450 volts, 250 amps at 0.6 power factor. If the power factor increases to 0.8, the kw load potential will increase by _____________. A. 38.525 kw B. 116.91 kw C. 155.88 kw D. 194.85 kw

Last Answer : Answer: A

Description : A three-phase alternator operates at 450 volts with a power factor of 0.8. If the ammeter indicates 250 amperes, what should be the KW meter reading? A. 90.00 KW B. 127.27 KW C. 155.70 KW D. 194.85 KW

Last Answer : Answer: C