What is some good advice for specifying allowable pressure drops in shell and tube exchangers for  heavy hydrocarbons?

1 Answer

Answer :

Frequently process engineers specify 5 or 10 PSI for allowable pressure drop inside heat exchanger  tubing. For heavy liquids that have fouling characteristics, this is usually not enough. There are cases  where the fouling excludes using tabulators and using more than the customary tube pressure drop is  cost effective. This is especially true if there is a relatively higher heat transfer coefficient on the outside  of the tubing. The following example illustrates how Allowable pressure drop can have a big effect on  the surface calculation. A propane chiller was cooling a gas treating liquid that had an average viscosity  Of 7.5 cP. The effect on the calculated surface was as follows: Allowable tube pressure drop Exchanger  surface 5 PSI 4012 Sq. Ft. 25 PSI 2104 Sq. Ft. 50 PSI 1419 Sq. Ft. You can see that using 25-PSI pressure  drop reduced the surface by nearly one-half. This would result in a price reduction for the heat  exchanger of approximately 40%. This savings offset the cost of the pumping power

Related questions

Description : Pick out the wrong statement. (A) Superheated steam is preferably not used for process heating because of its low heat transfer film co-efficient (B) In a shell and tube heat exchanger ... surface heat exchangers, when the direction of fluid flow is parallel to the axis of the tube

Last Answer : (C) S.I. unit of fouling factor is Watt/m2 .°K

Description : Pick out the wrong statement. (A) In drying a solid containing moisture above the critical moisture content the number of degrees of freedom is 2 (B) Sherwood number in mass transfer corresponds to ... tube heat exchangers. At higher pressure, however, it is customary to put gas in the tube side

Last Answer : (C) Forced convection is relatively more effective in increasing the rate of mass transfer, if Schmidt number is larger

Description : What is the method of determining maximum differential pressure during hydro testing of shell and tube heat exchangers?

Last Answer : Mr. Richard Lee of Plumlee International Consulting usually heat exchangers have two sets of test pressures per side, one for strength tests, and the other for operating or leak tests. The ... . The acceptability of this lower pressure test will often depend upon the consequences of a leak.

Description : What are some good strategies for curing tube vibration in shell and tube exchangers?

Last Answer : Most flow-induced vibration occurs with the tubes that pass through the baffle window of the inlet zone. The unsupported lengths in the end zones are normally longer than, those in the rest of the ... bundles, this is the best solution. Adding a distributor belt on the shell would be a very

Description : Air is to be heated by condensing steam. Two heat exchangers are available (i) a shell and tube heat exchanger and (ii) a finned tube heat exchanger. Tube side heat transfer area are equal in both ... steam on shell side (D) Shell and tube heat exchanger with air on shell side and steam inside tubes

Last Answer : (B) Finned tube heat exchanger with air outside and steam inside

Description : Is there a difference in MTD (Mean Temperature Difference) between “E” and “J” (Divided Flow) type shell and tube heat exchangers?

Last Answer : Divided flow (shell type J) does not have the same correction as the usual flow pattern (shell type E). Thermal design program make this correction factor mistake. True, there is very little ... for the above examples and it is hard to read in this range. Source: Gulley Computer Associates

Description : Why is a vacuum breaker used on shell and tube heat exchangers that are utilizing steam as the heating utility?

Last Answer : Vacuum breakers are often installed on the shell side (steam side) of shell and tube exchangers to allow air to enter the shell in case of vacuum conditions developing inside the shell. For an ... vacuum in the shell could allow condensate to build in the unit and water hammer may result.

Description : What is the use of shell and tube heat exchangers?

Last Answer : shell and tube heat exchangers are used mostly in the chemical processing industry for heating, cooling, condensing, and evaporating highly corrosive liquids and gases.AMETEK ... fluoropolymer heat exchangers are Hydrochloric, Nitric and Hydrofluoric Acids. Another chemical manufacturing indust

Description : In a shell and tube heat exchanger, (A) The temperature drops in the two fluids and the wall are proportional to individual resistances (B) The temperature drop is inversely proportional to ... ) There is no relationship between temperature drop and resistance (D) The relationship is not generalised

Last Answer : (A) The temperature drops in the two fluids and the wall are proportional to individual resistances

Description : Multipass heat exchangers are used (A) Because of simplicity of fabrication (B) For low heat load (C) To obtain higher heat transfer co-efficient and shorter tube (D) To reduce the pressure drop

Last Answer : (C) To obtain higher heat transfer co-efficient and shorter tube

Description : Which type of heat exchanger is preferred for heavy heat loads? (A) Double pipe (B) Plate fine (C) Series and parallel set of shell and tube (D) None of these

Last Answer : (C) Series and parallel set of shell and tube

Description : Finned tube heat exchangers (A) Give larger area per tube (B) Use metal fins of low thermal conductivity (C) Facilitate very large temperature drop through tube wall (D) Are used for smaller heat load

Last Answer : (A) Give larger area per tube

Description : Pick out the wrong statement. (A) Economy of a multiple effect evaporator is not influenced by the boiling point elevation (B) Two identical cubes of iron and copper will have the same heat ... in the field of refrigeration (D) Finned tube heat exchangers are suitable for heating air by steam

Last Answer : (B) Two identical cubes of iron and copper will have the same heat content under the same conditions of temperature

Description : Condensing film co-efficient for steam on horizontal tubes ranges from 5000 to 15000 Kcal/hr.m2 .°C. Condensation of vapor is carried out inside the tube in a shell and tube heat ... drop through the exchanger is desired (D) Temperature of the incoming vapor is very high

Last Answer : (B) Supersaturated

Description : Pick out the wrong statement. (A) Heat transfer by radiation cannot occur across an absolute volume (B) In case of a shell and tube heat exchanger, the pressure drop through the shell is ... The amount of heat involved in the condensation or vaporisation of 1 kg of a fluid is the same

Last Answer : (A) Heat transfer by radiation cannot occur across an absolute volume

Description : In a multipass shell and tube heat exchanger, tube side return pressure loss is equal to __________ the velocity head. (A) Twice (B) Four times (C) Square root of (D) Square of

Last Answer : (B) Four times

Description : Pick out the wrong statement: (A) The capacity of an evaporator is reduced by the boiling point elevation (B) Corrosive liquid is normally passed through the tubes in a ... recompression evaporator (D) Heat sensitive materials should be concentrated in high pressure evaporators

Last Answer : (D) Heat sensitive materials should be concentrated in high pressure evaporators

Description : Pick out the wrong statement. (A) Orifice baffles are never used in a shell and tube heat exchanger (B) Pressure drop on the shell side of a heat exchanger depends upon tube pitch also

Last Answer : (A) Orifice baffles are never used in a shell and tube heat exchanger

Description : Shell side pressure drop in a shell and tube heat exchanger does not depend upon the (A) Baffle spacing & shell diameter (B) Tube diameter & pitch (C) Viscosity, density & mass velocity of shell side fluid (D) None of these

Last Answer : (D) None of these

Description : Pick out the wrong statement. (A) The controlling resistance in case of heating of air by condensing steam is in the air film (B) The log mean temperature difference (LMTD) for ... a pure fluid at a given pressure from liquid to vapor or vice-versa occurs at saturation temperature

Last Answer : (C) In case of a 1 - 2 shell and tube heat exchanger, the LMTD correction factor value increases sharply, when a temperature cross occurs

Description : Which of the following parameters is increased by use of finned tube in a multipass shell and tube heat exchanger? (A) Tube side pressure drop and the heat transfer rate (B) Convective heat transfer co-efficient (C) Effective tube surface area for convective heat transfer (D) All (A) (B) and (C)

Last Answer : (D) All (A) (B) and (C)

Description : In a gas-liquid shell and tube heat exchanger, the (A) Presence of a non-condensable gas decreases the condensing film co￾efficient (B) Gases under high pressure are routed through the tube side, because high pressure ... water or steam condensate remain localised to the tubes (D) All 'a', 'b' & 'c'

Last Answer : (D) All 'a', 'b' & 'c'

Description : In a shell and tube heat exchanger, square pitch compared to triangular pitch (A) Gives a higher shell side pressure drop (B) Gives a lower shell side pressure drop (C) Can pack more surface area into a shell of given diameter (D) None of these

Last Answer : (A) Gives a higher shell side pressure drop

Description : The advantage of using a 1 - 2 shell and tube heat exchanger over a 1 - 1 shell and tube heat exchanger is (A) Lower tube side pressure drop (B) Lower shell side pressure drop (C) Higher tube side heat transfer co-efficient (D) Higher shell side heat transfer co-efficient

Last Answer : (C) Higher tube side heat transfer co-efficient

Description : Extremely large or small volumes of fluids are generally best routed through the shell side of a shell and tube heat exchanger, because of the (A) Less corrosion problems (B) Flexibility possible in the baffle arrangement (C) Low pressure drop (D) High heat transfer co-efficient

Last Answer : (B) Flexibility possible in the baffle arrangement

Description : Which of the following parameters of the fluid is not very important, while deciding its route in a shell and tube heat exchanger? (A) Corrosiveness & fouling characteristics (B) Pressure (C) Viscosity (D) Density

Last Answer : (D) Density

Description : In a shell and tube heat exchanger, floating head is used for (A) Large temperature differentials (B) High heat transfer co-efficient (C) Low pressure drop (D) Less corrosion of tubes

Last Answer : (A) Large temperature differentials

Description : For the same heat load and mass flow rate in the tube side of a shell and tube heat exchanger, one may use multipass on the tube side, because it (A) Decreases the pressure drop (B) ... the outlet temperature of cooling medium (C) Increases the overall heat transfer coefficient (D) None of these

Last Answer : (C) Increases the overall heat transfer coefficient

Description : What is a good method of minimizing shell side pressure drop in a shell and tube exchanger?

Last Answer : When shell pressure drop is critical and impingement protection is required, use rods or tube protectors in top rows instead of a plate. These create less pressure drop and better distribution ... turn of the shell stream, which causes extra pressure drop. Source: Gulley Computer Associates

Description : Are there any alternatives to scraping a shell and tube if a capacity increase will make the pressure drop across the exchanger too large?

Last Answer : When an increase in capacity will cause excessive pressure drop, you may not have to junk the heat exchangers. A relatively inexpensive alteration is to reduce the number of tube passes. ... the exchangers in parallel or using lowfins or other special tubing. Source: Gulley Computer Associates

Description : An oil fired boiler is retrofitted to fire coconut shell chips. Boiler thermal efficiency drops from 82% to 70%. What will be the percentage change in energy consumption to generate the same output a) 12% increase b) 14.6% increase c) 17.1% decrease d) 17.1% increase

Last Answer : d) 17.1% increase

Description : the fluid flow rate increases, the float of the Rotameter (A) Rises in the tube (B) Rotates at higher speed (C) Rotates at lower speed (D) Drops down in the tube

Last Answer : Option A

Description : When petroleum is refined it is subject to a number of processes including cracking. During the cracking process w) lighter hydrocarbons are combined to form heavier ones x) heavy hydrocarbons ... lighter hydrocarbons are separated by distillation z) oxygen is used to burn the heavier hydrocarbons

Last Answer : ANSWER: X -- HEAVY HYDROCARBONS ARE BROKEN UP INTO LIGHTER ONES

Description : Explain with reason through which side of shell and tube heat exchanges, the following liquids are directed. (i) viscous liquid (ii) high pressure liquid (iii) corrosive liquid

Last Answer : Viscous liquid : Viscous liquid is passed through shell side Reason: because of the presence of baffles in the shell induce turbulence and hence increases heat transfer rate. High pressure liquid: High ... To avoid expensive alloy shells (in order to save the cost of expensive material for shell).

Description : When specifying a cooling tower, should I look up historic wet bulb temperatures for my area or should I take measurements?

Last Answer : If this is a new installation, look up historical wet bulb temperatures for area and be sure to report them to the cooling tower manufacturer as ambient wet bulb temperatures . The ... the tower entrance. The entering wet bulb temperature always higher than the ambient wet bulb temperature.

Description : The deficiency in rain catch due to vertical acceleration of air forced upward over the gauge, is (A) Greater for heavy rain (B) Greater for lighter rain (C) Greater for large drops (D) Lesser for small rain drops

Last Answer : Answer: Option B

Description : Are some heat transfer services more prone to tube vibration that others for a shell and tube exchanger?

Last Answer : Bundle vibration can cause leaks due to tubes being cut at the baffle holes or tubes being loosened at the tubesheet joint. There are services that are more likely to cause bundle vibration ... if the baffle spacing is greater than 18 inches and single segmental. Source: Gulley Computer Associates

Description : In a 1-1 concurrent heat exchanger, if the tube side fluid outlet temperature is equal to the shell side fluid outlet temperature, then the LMTD is (A) ∞ (B) 0 ... temperature (D) Equal to the difference between hot fluid inlet temperature and cold fluid outlet temperature

Last Answer : (B) 0

Description : Fouling factor' used in the design of a multipass shell and tube heat exchanger is a (A) Non-dimensional factor (B) Factor of safety

Last Answer : (B) Factor of safety

Description : . In a shell and tube heat exchanger, the tube side heat transfer co￾efficient just at the entrance of the tube is (A) Infinity (B) Zero (C) Same as average heat transfer co-efficient for tube side (D) None of these

Last Answer : (A) Infinity

Description : In case of a multipass shell and tube heat exchanger, providing a baffle on the shell side __________ the heat transfer rate. (A) Increases (B) Decreases (C) Does not affect (D) May increase or decrease, depends on the type of baffle

Last Answer : (A) Increases

Description : __________ heat exchanger is the most suitable, when the temperature of shell side fluid is much higher than that of tube side. (A) Single pass, fixed tube sheet (B) U-tube (C) Three pass, fixed tube sheet (D) None of these

Last Answer : (B) U-tube

Description : If the baffle spacing in a shell and tube heat exchanger increases, then the Reynolds number of the shell side fluid (A) Remains unchanged (B) Increases (C) Increases or decreases depending on number of shell passes (D) Decreases

Last Answer : (D) Decreases

Description : In a shell and tube heat exchanger, the height of 25 percent cut baffles is equal to (where, D = inside diameter of shell). (A) 0.25 D (B) 0.50 D (C) 0.75 D

Last Answer : (C) 0.75 D

Description : Steam is to be condensed in a shell and tube heat exchanger, 5 m long with a shell diameter of 1 m. Cooling water is to be used for removing the heat. Heat transfer co-efficient ... ) Horizontal heat exchanger with steam on tube side (D) Horizontal heat exchanger with steam on shell side

Last Answer : (B) Vertical heat exchanger with steam on shell side

Description : For shell and tube heat exchanger, with increasing heat transfer area, the purchased cost per unit heat transfer area (A) Increases (B) Decreases (C) Remain constant (D) Passes through a maxima

Last Answer : (D) Passes through a maxima

Description : Air is best heated with steam in a heat exchanger of (A) Plate type (B) Double pipe type with fin on steam side (C) Double pipe type with fin on air side (D) Shell and tube type

Last Answer : (C) Double pipe type with fin on air side

Description : The main function of baffles provided in a shell and tube heat exchanger is to (A) Facilitate the cleaning of outer tube surface (B) Enhance turbulence (C) Hold the tubes in position (D) All 'a', 'b' & 'c'

Last Answer : (B) Enhance turbulence

Description : Baffles in the shell side of a shell and tube heat exchanger (A) Increase the cross-section of the shell side liquid (B) Force the liquid to flow parallel to the bank (C) Increase the shell side heat transfer co-efficient (D) Decrease the shell side heat transfer co-efficient

Last Answer : (C) Increase the shell side heat transfer co-efficient

Description : Vibrations in the tubes of a shell and tube heat exchanger is induced due to the (A) Flow of fluid on the tube and shell sides (B) Oscillations in the flow of shell/tube sides fluid (C) Vibrations ... piping and/or supports due to external reasons (D) All (A), (B) and (C)

Last Answer : (D) All (A), (B) and (C)