A single-phase transformer has a turns ratio of 1 :2 and is connected to a purely resistive load as shown in the figure. The magnetizing current drawn is 1A, and the secondary current is 1A. Ifcore losses and leakage reactances are neglected, the primary current is 

image

A)1.41A B)2A C) 2.24A D)3A

1 Answer

Answer :

A single-phase transformer has a turns ratio of 1 :2 and is connected to a purely resistive load as shown in the figure. The magnetizing current drawn is 1A, and the secondary current is 1A. Ifcore losses and leakage reactances are neglected, the primary current is 2.24A

Related questions

Description : The core flux of a practical transformer with a resistive load  A) Is strictly constant with load changes B) Increases linearly with load C) Increases as the square root of the load D) Decrease with increased load

Last Answer : The core flux of a practical transformer with a resistive load Is strictly constant with load changes

Description : A single-phase, 50 kVA, 250 V/500 V two winding transformer has an efficiency of 95% at full load, unity power factor. If it is re-configured as a 500 V/750 V auto-transformer, its efficiency at its new rated load at unity power factor will be  (A) 95.752% (B) 97.851% (C) 98.276% (D) 99.241%

Last Answer : A

Description : A single-phase transformer has no-load loss of 64 W, as obtained from an open circuit test. When a short-circuit test is performed on it with 90% of the rated currents flowing in its both LV and HV windings, ... .0% of the rated current (C) 80.0% of the rated current (D) 88.8% of the rated current

Last Answer : A single-phase transformer has no-load loss of 64 W, as obtained from an open circuit test. When a short-circuit test is performed on it with 90% of the rated currents flowing in its both ... measured loss is 81 W. The transformer has maximum efficiency when operated at 80.0% of the rated current

Description : A 3-phase voltage source inverter operates in 180° conduction mode with a star connected resistive load. If input dc voltage is 100 V, then the peak to peak output line voltage is :

Last Answer : A 3-phase voltage source inverter operates in 180° conduction mode with a star connected resistive load. If input dc voltage is 100 V, then the peak to peak output line voltage is : 200 V

Description : Figure 'D' of the diagram shown in the illustration has a turns ratio of four to one. If a three-phase 440 volt supply is connected to terminals 'A-B-C', what voltage should develop across terminals 'a-b-c'? EL-0084 A. 64 volts B. 110 volts C. 190 volts D. 762 volts

Last Answer : Answer: A

Description : Figure 'C' of the diagram shown in the illustration has a turns ratio of four to one. If a three-phase 440 volt supply is connected to terminals 'A-B-C', what voltage should develop across terminals 'a-b-c'? EL-0084 A. 64 volts B. 110 volts C. 190 volts D. 762 volts

Last Answer : Answer: C

Description : Figure 'B' of the diagram shown in the illustration has a turns ratio of four to one. If a three-phase 440 volt supply is connected to terminals 'A-B-C', what voltage should develop across terminals 'a-b-c'? EL-0084 A. 64 volts B. 110 volts C. 190 volts D. 762 volts

Last Answer : Answer: B

Description : Figure 'A' of the diagram shown in the illustration has a turns ratio of four to one. If a three-phase 440 volt supply is connected to terminals 'A-B-C', what voltage should develop across terminals 'a-b-c'? EL-0084 A. 64 volts B. 110 volts C. 190 volts D. 762 volts

Last Answer : Answer: B

Description : At ______ frequencies the parallel R-L circuit behaves as purely resistive.

Last Answer : At very high frequencies the parallel R-L circuit behaves as purely resistive.

Description : What is the power factor of purely resistive circuit.

Last Answer : Unity that is 1

Description : When two transformer of different kVA rating are connected in parallel they share the load in proportion to their respective kVA rating only when their:

Last Answer : When two transformer of different kVA rating are connected in parallel they share the load in proportion to their respective kVA rating only when their: P u impedance are equal

Description : Single-phase Midpoint controlled rectifier with Resistive load

Last Answer : Single-phase Midpoint controlled rectifier with Resistive load:  1) During positive half cycle of AC supply, a is positive with respect to b , this makes T1 forward biased and T2 is reverse ... voltage reverses the polarity and T2 is turned off. The operation is as shown in waveforms.

Description : A simple phase transformer has a maximum efficiency of 90% at full load and unity power factor. Efficiency at half load at the same power factor is  (A) 86.7% (B) 88.26% (C) 88.9% (D) 87.8%

Last Answer : A simple phase transformer has a maximum efficiency of 90% at full load and unity power factor. Efficiency at half load at the same power factor is 87.8%

Description : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is  (A) 50.0% (B) 70.7% (C) 141.4% (D) 200.0%

Last Answer : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is 70.7%

Description : Explain direct loading test on single phase transformer with neat circuit diagram. 

Last Answer : Direct loading test on single phase transformer with neat circuit diagram:   Direct loading test on transformer is carried out to calculate the losses, efficiency and voltage regulation of the ... voltage.  Efficiency and regulation can be calculated by using following formulae:   

Description : Single phase transformer

Last Answer : Single phase Transformer Transformer

Description : Explain construction and working of single phase Auto transformer.

Last Answer : Construction of single phase auto transformer: (i) It has only one winding wound on a laminated circular magnetic core. (ii) The core is made of silicon steel stampings. (iii) The two terminals of the ... help of handle. 5) The same transformer can be used as step-up or step down auto-transformer

Description : The hysteresis and eddy current losses of a single phase transformer working on 200 V, 50 Hz supply are Ph and Pe respectively. The percentage decrease in these when operated on a 160 V, 40 Hz supply are   (a) 32, 36 (b) 20, 36 (c) 25, 50 (d) 40, 80 

Last Answer : The hysteresis and eddy current losses of a single phase transformer working on 200 V, 50 Hz supply are Ph and Pe respectively. The percentage decrease in these when operated on a 160 V, 40 Hz supply are 20, 36

Description : If the secondary turns of a transformer are doubled and at the same time primary voltage is reduced to half then the secondary voltage will

Last Answer : If the secondary turns of a transformer are doubled and at the same time primary voltage is reduced to half then the secondary voltage will not change

Last Answer : High voltage winding in a transformer has more number of turns.

Last Answer : In a power or distribution transformer about 10 percent end turns are heavily insulated to withstand the high voltage drop due to line surge produced by the shunting capacitance of the end turns.

Description : The turns ratio of transformer 'A' shown in the illustration is four to one and all taps are evenly spaced. If 120 volts were applied to terminals 'H1' and 'H3', what would appear at 'X1' and 'X2'? EL-0082 A. 15 volts B. 30 volts C. 480 volts D. 960 volts

Last Answer : Answer: A

Description : Transmission lines when connected to antenna have A. capacitive load B. resistive load whose resistance is less than characteristics impedance C. resistive load at the resonant frequency D. resistive load whose resistance is greater than the characteristic impedance of the line

Last Answer : C. resistive load at the resonant frequency

Description : What is the maximum current allowed to be drawn from the secondary of a 2 KVA step-down transformer with a turns ratio of four to one if connected across a 440 volt line? A. 1.1 amps B. 4.5 amps C. 18.1 amps D. 22.7 amps

Last Answer : Answer: C

Description : What is the maximum allowable primary current of a 2 KVA step-down transformer with a four to one turns ratio if connected across a 440 volt line? A. 1.1 amps B. 4.5 amps C. 18.1 amps D. 27.7 amps

Last Answer : Answer: B

Description : A transformer has a turns ratio of two to one. If a 100 ohm resistor is connected on the high side, its resistance as measured on the low side would be: w) 25 ohms x) 50 ohms y) 100 ohms z) 400 ohms

Last Answer : ANSWER: W -- 25 OHMS

Description : The turns ratio of device 'B' shown in the illustration is two to one (total). If 220 volts were applied to terminals 'H1' & 'H2', what would be indicated across 'X1' & 'X4' with 'X2' & 'X3' connected and isolated? EL-0082 A. 55 volts B. 110 volts C. 220 volts D. 440 volts

Last Answer : Answer: B

Description : The turns ratio of device 'B' shown in the illustration is two to one (total). If 440 volts were applied to terminals 'H1' & 'H2', what would be indicated across 'X1' & 'X4' with 'X2' & 'X3' connected and isolated? EL-0082 A. 110 volts B. 220 volts C. 880 volts D. 1760 volts

Last Answer : Answer: B

Description : The primary turns of a 444 V/222 V, 50 Hz single-phase transformer with a core cross-sectional area of 100 cm2, and a maximum flux density of 1.0 T is (A) 100 (B) 200 (C) 222 (D) 400

Last Answer : The primary turns of a 444 V/222 V, 50 Hz single-phase transformer with a core cross-sectional area of 100 cm2, and a maximum flux density of 1.0 T is 200

Description : In a three phase half wave rectifier feeding resistive load, if the input source is a three phase 4 wire system and line to line voltage is 100 V. The supply frequency is 400 Hz. The ripple frequency at the output is: (1) 400 Hz (2) 800 Hz (3) 1200 Hz (4) None of these

Last Answer : In a three phase half wave rectifier feeding resistive load, if the input source is a three phase 4 wire system and line to line voltage is 100 V. The supply frequency is 400 Hz. The ripple frequency at the output is: 1200 Hz

Description :  A single-phase transmission line of impedance j 0.8 ohm supplies a resistive load of 500 A at 300 V. The sending end power factor is?

Last Answer :  A single-phase transmission line of impedance j 0.8 ohm supplies a resistive load of 500 A at 300 V. The sending end power factor is 0.6 lagging.

Description : The standing wave ratio of a 75 Ω transmission line used to feed a 300 Ω resistive load will be _____.

Last Answer : The standing wave ratio of a 75 Ω transmission line used to feed a 300 Ω resistive load will be 4.

Description : Full load copper loss in a transformer is 1600 watts. At half load the copper loss will be: A) 6400 watt B) 1600 watt C) 800 watt D) 400 watt

Last Answer :  Full load cupper loss in a transformer is 1600 watts. At half load the cupper loss will be: 400 watt

Description : Which losses in a transformer varies significantly with load  a. Hysteresis losses b. Eddy current losses c. Copper losses d. Core losses 

Last Answer : Which losses in a transformer varies significantly with load Copper losses

Description : For a constant load current, transformer maximum efficiency occurs at   (a) any power factor (b) zero power factor leading (c) zero power factor lagging (d) unity power factor 

Last Answer : For a constant load current, transformer maximum efficiency occurs at unity power factor 

Description : In a transformer, zero voltage regulation at full load is   (a)Not possible   (b) Possible at unity power factor load   (c) Possible at leading power factor load   (d) Possible at lagging power factor load

Last Answer : In a transformer, zero voltage regulation at full load is Possible at leading power factor load 

Description :  The no-load current drawn by transformer is usually what per cent of the full-load current ?

Last Answer : 5 to 8 percentage of full load current

Last Answer : No-load current in a transformer lags behind the voltage by about 75°.

Last Answer : The no load current in a transformer lags behind the applied voltage by an angle of about 75°.

Last Answer : No-load current of a transformer has small magnitude and low power factor.

Last Answer : The full-load copper loss of a trans¬former is 1600 W. At half-load, the copper loss will be 400 W.

Description : In an actual transformer the iron loss remains practically constant from no load to full load because?

Last Answer : In an actual transformer the iron loss remains practically constant from no load to full load because core flux remains practically constant.

Last Answer : An ideal transformer will have maximum efficiency at a load such that copper loss equal to iron loss.

Description : In a given transformer for a given applied voltage, losses which remain constant irrespective of load changes are?

Last Answer : In a given transformer for a given applied voltage, losses which remain constant irrespective of load changes are hysteresis and eddy current losses.

Description : For a transformer, operating at constant load current, maximum efficiency will occur at?

Last Answer : For a transformer, operating at constant load current, maximum efficiency will occur at unity power factor.

Description : The maximum load that a power transformer can carry is limited by its?

Last Answer : The maximum load that a power transformer can carry is limited by its voltage ratio.

Description : A no-load test is performed on a transformer to determine?

Last Answer : A no-load test is performed on a transformer to determine magnetizing current and loss.

Description : In a step-down transformer, there is a change of 15 A in the load current. This results in change of supply current of?

Last Answer : In a step-down transformer, there is a change of 15 A in the load current. This results in change of supply current of less than 15A.

Description : Why phasing out and polarity test is carried out on three phase transformer?

Last Answer : The phasing out test is carried out to identify the windings (primary and secondary) of corresponding phase of the three phase transformer. The polarity test is carried out to identify the ... identical polarity of the primary and secondary windings of each phase of the three phase transformer.