How CT is connecting in ckt? 

1 Answer

Answer :

If the primary of CT is delta connected load the CT will be in star connection and vice versa. This is because to have square root 3 time compensation. 

Related questions

Description : Mention the precautions to be taken while connecting CT and PT in the circuit. 

Last Answer : Precautions to be taken while using instrument transformers: 1. Secondary of CT is never kept open circuited when it is energized. 2. Secondary of PT is never kept short circuited when it ... of the instrument transformers unless they are properly grounded. 8. Never connect to DC circuits.

Description : Before servicing the device indicated as 'A' in panels #1 and #3 of the illustration, the device labeled 'CT' must __________. EL-0003 A. have the disconnected leads taped to prevent ... D. have one lead grounded to discharge static electricity for the prevention of damage to electronic components

Last Answer : Answer: C

Description : Difference between Current Transformer (CT) and Potential Transformer (PT)

Last Answer : Current Transformers (CT) and Potential Transformers (PT) are used to measure the current and voltage in a circuit of the order of hundreds of amperes and volts respectively. A CT has large number of ... and flux density vary over a wide range whereas in PT, they vary over a limited range only

Description : What are the errors in CT?

Last Answer : (a) Ratio error Percentage ratio error = [(Nominal ratio – Actual ratio)/Actual ratio] x 100 The value of transformation ratio is not equal to the turns ratio. (b) Phase angle error: Phase angle =180/ [(ImCos -I1Sin )/nIs]

Description : Where wound type CT used and where not used?

Last Answer : Used where low CT ratio req. Not used where high short ckt. Current exists.

Description : Give the details of switchyard 220 kV CB, Isolator, CT, CVT and lightning arrestor.  

Last Answer : 220 kV SF6 Circuit Breaker 1. Make - ABB 2. Air pressure blocking a. Close Block - 17.3 bar. b. Open block - 16.7 bar. c. Auto reclose block - 19 bar. 3. SF6 pressure block a. Alarm - 5. ... , storage and erection. Rated voltage : 216 kV rms. Operating voltage : 184 kV rms. 

Description : Why CT operated over load relay is using for loads of high acceleration time upto 30 seconds? How it getting back?

Last Answer : The saturable current transformers linearly transforms the current upto twice the set current, but above this value the transformer core gets saturated and the secondary current is proportionally less. Thus ... overload. When current reduces the core gets de-saturated, as material design is such. 

Description : Why ICT are used?(INTERPOSING CT)

Last Answer : To correct the system primary CT errors in case of high current faults out side CT zone (ICT’s primary CT is 800/1, but in fault current may go to thousands of amps. This ICT will take care of those errors. a) Matching the ratios. b) Matching the phase angle differences. 

Description : Why core balance CT is preferred over residual connected CT’s to sense earth fault in 6.6 kV feeders?

Last Answer : a) To avoid relay mal-operation due to CT saturation b) Better sensitivity is got. c) High pickup and TMS avoided in IDMT earth fault relay. 

Description : What are the checks on CT & PT?

Last Answer : a) Polarity checks b) Insulation checks c) Ratio checks d) Knee point voltage (only for PS class CT)- magnetising characteristic test. 

Description : Where CT secondary of 1A we are using?

Last Answer : For long distance current transmission, to reduce the IR drop.  

Description : What is the purpose of CT & PT?

Last Answer : For transformation of current, voltage to a lower level for the purpose of Measurement, Protection and Control. 

Description : What is the standard CT polarity?

Last Answer : Primary current enters at P1 and secondary current leaves at S2.  

Description : But is it advisable to keep the secondary of CT in open conditions? Will not induce very high voltage?

Last Answer : If the CT has only one secondary winding, we should keep it always short cktd for safety, but if the CT has multiple secondary, then if one secondary voltage is kept limited by suitable loading, then the other secondary voltage is eventually limited proportionately. 

Description : A CT has 2 – secondary windings. If we use only one secondary winding can we keep the unused secondary winding short circuited?

Last Answer : No. If it is short-circuited then the ratio will not get correctly. The turns of primary winding will be shared between 2 secondary windings. So the unused secondary winding should kept open. 

Description : What is over voltage interturn test for CT?

Last Answer : With secondary open, pass rated current in primary for 1 min. Then check secondary for insulation. 

Description : What is the operating point in the Magnetising characteristic of protection CT & measuring CT? 

Last Answer : Protection CT – Operation at ankle point only. Measuring CT – Operation from ankle to knee point 

Description : What are the errors of the following CT’ s 5p. 10p. 15p. At rated current?  

Last Answer : 5p - 1 % Ratio error ± 60 min phase error 10p - 3 % Ratio error ± 60 min phase error 15p - 5 % Ratio error ± 60 min phase error 

Description : What are the specifications of CT? 

Last Answer : Protection CT - Error. Alf. KpV. Metering CT - Error. Burden. Differential CT - Class PS. Core balance or E/F CT - 5-p type. Primary current - Rating of CT - 1. 15 ( full load current ) Short time rating - 1 sec. 

Description : Why CT should not be open circuited?

Last Answer : Very high voltage will be induced in secondary due to less back emf resulting in the failure of the insulation. 

Description : How can you de-saturate the CT? 

Last Answer : Pass ac current through the primary and vary the current from zero to maximum with secondary in shorted condition. Pass dc current in the secondary and vary it from zero to maximum.

Description : What is the problem anticipated due to CT saturation?  

Last Answer : The CT will not be able to drive the current through the circuit causing nonoperation of relays. In some other case when the currents in the two phases are compared for relay operation the relay may operate due to unbalance. 

Description : When will you say that the CT is saturated?

Last Answer : When checking the CT with the secondary injection method a 10% increases in the voltage causes a 50% increase in the current the CT is said to be saturated. 

Description : Show the CT characteristics.

Last Answer : CT characteristics :  

Description : How to reduce the CT error? 

Last Answer : Error reduces if load increases.  

Description : Explain with simple diagram the core balance CT.

Last Answer : In core balance CT all the three phases go through the core and the resultant magnetic flux is zero. Because the flux of three phases cancel each other. So the secondary output of CT is zero and ... energised to trip the circuit. Saturation is no problem because the core size is very big.  

Description : Explain the procedure for finding out the polarity and ratio test in a CT with circuit diagram. 

Last Answer : Polarity test: Connect the circuit as shown in figure with a battery, switch and AVOmeter. Now momentarily close the switch S and see the deflection in the AVOmeter. If it is in the direction as shown in the ... A2. Then see whether it confirms to reading of nameplate. Ratio = A1/A2. 

Description : Define knee point voltage of a CT.

Last Answer : When the primary of a CT is open circuited and supply (variable) of system frequency is given to secondary, then a 10% increase in voltage constitutes 50% increase in current. That voltage is the knee point ... Above kpv the ratio of transformer will not be applicable. kpv = RCT + RLEADS + RRELAY  

Description : Where core balance CT is used?

Last Answer : Core balance CT is used in earth fault protection.  

Description : Draw a neat sketch and explain the use of CT and PT for measurement of power in a single-phase circuit?

Last Answer : If wattmeter of proper range is not available or if voltage and current ranges are high we can usr CT and PT of suitable ratio. Connect the CT and PT as shown in figure. The reading of wattmeter can be multiplied by the ratio to get the actual power.   

Description : The boundary of the protective zone is determined by the (A) Location of CT (B) sensitivity of relay used (C) Location of PT (D) None of these

Last Answer : Ans: B The boundary of the protective zone is determined by the sensitivity of relay used. If the relay is more sensitive, the protective zone will be increased.

Description : Which of the following statements is/are true regarding requirements for receptacle outlets aboard vessels? A. Each receptacle outlet operating at 100 volts or more must have a grounding pole. B. Outlets ... machinery with a portable light having a 50 foot flexible cord. D. All of the above.

Last Answer : Answer: A

Description : An open shunt field in a direct current machine may be located by connecting the field circuit to an external power source, equal to the rated field voltage or less, and tested with a voltmeter from ... C. any suitable ground to any available line lead D. any field pole to each field coil lead

Last Answer : Answer: A

Description : The proper method of connecting an ammeter in a circuit is demonstrated by which of the diagrams shown in the illustration? EL-0041 A. A B. B C. C D. All of the above

Last Answer : Answer: D

Description : The vertical dotted line connecting the small circular symbols at coordinates '05L', '09L', '13L', '21L', '25L', etc., shown in the illustration, indicate that all _______________. EL-0100 A. contacts are ... board 'TB2' C. wires are grounded at both ends of the line D. wires have a common shield

Last Answer : Answer: B

Description : Temporary repairs to an open DC propulsion armature coil can be made by _____________. A. connecting the coil ends directly to a pair of negative brushes B. disconnecting coil ends, insulating ... C. grounding the coil ends and short circuiting the commutator bar D. removing the sparking brushes

Last Answer : Answer: B

Description : Which of the following statements represents the correct method of connecting the shunt of an ammeter prior to taking a reading? A. In series with the load and in series with the meter movement. B. In ... with the meter movement. D. In parallel with the load and in parallel with the meter movement.

Last Answer : Answer: B

Description : The device in figure 'B' shown in the illustration can be used to control an AC load yet maintain its high gain by ______________. EL-0091 A. connecting the load to the output side of the ... connecting the load to the input side of the bridge D. reversing the current flow through the bias winding

Last Answer : Answer: C

Description : Handheld phase sequence indicators are useful when ________. A. preparing to parallel alternators B. connecting lighting branch circuits C. troubleshooting DC motors D. connecting shore power lines to the ship

Last Answer : Answer: D

Description : One method of testing for a reversed shunt field coil in a DC generator or motor is by connecting the field to a direct current source, at reduced field rated voltage, and test for ... placed near each field C. test lamp across adjacent fields D. copper jumper across the interpole connections

Last Answer : Answer: B

Description : State the condition to be satisfied before connecting two alternators in parallel

Last Answer : The following are the three conditions to be satisfied by synchronizing the additional Alternator with the existing one or the common bus-bars. · The terminal voltage magnitude of the incoming ... incoming Alternator voltage must be the same as the bus-bar voltage. . Zero phase difference

Description : What is the purpose of connecting external resistors to slip ring Induction motor?

Last Answer : It increases starting torque and decreases starting current.

Description : What is purpose of connecting thyristor bridges in parallel?

Last Answer : Thyristor bridges are connected in parallel to improve current rating.  

Description : What are the methods of connecting 3-phase windings?

Last Answer : There are two methods. a. Star or wye (Y) connection. b. Delta or mesh connection.

Description : Can I get an MRI for a cardiac calcium score rather than a CT?

Last Answer : Check with your cardiologist to be sure. I listen to the medical channel on SirisuXM (#110) - they had a session on this about a month ago. I don't recall all the details, but I do ... of anything. It's more of a general guidepost than anything that is actionable. You have probably seen this

Description : Can a CT colonography show cancer in organs surrounding the bowel?

Last Answer : answer:What are you trying to say? A colonography a year ago and that showed I had a kidney stone has nothing to do with a tumor in my stomach . Comments you have before show you ... able to found in your stomach. GERD is treatable-take an antacid or Prilosec (omeprazole) for Heartburn relief.

Description : Why is the CT colonography prep so damn dangerous?

Last Answer : Yes I did it. I was put under and had no side effects. Drinking that liquid was hard.