What Are The Conditions To Be Satisfied For Parallel Operation Of Dc Generators?

1 Answer

Answer :

The polarities of the generators must be same or the connections must be interchanged till they become same. The voltages of both the generators must be equal. The change of voltage with change of load should be of same character. The prime movers driving the generators should have stable and similar rotational speed characteristics. The positive and negative terminals of generators must be connected properly to the positive and negative of busbar.

Related questions

Description : What Is Basic Principle Of Operation Of Alternators/dc Generators?

Last Answer : They are working on the fundamental principle based on Faraday’s Laws of Electromagnetic Induction. This law states that, When a current carrying conductor moves in magnetic field, it induces an EMF.

Description : Which of the methods listed is used to maintain the division of load between two compound-wound, DC generators operating in parallel? A. The shunt fields are interconnected. B. The shunt ... generators are connected in series. D. The equalizer connection parallels the series fields of all machines.

Last Answer : Answer: D

Description : An equalizing connection between two compound-wound DC generators when paralleled, serves to _____________. A. reverse the polarity of the incoming generator as the series field weakens B. automatically ... the series field of the incoming generator D. parallel the series fields of the generators

Last Answer : Answer: D

Description : Which of the methods listed is used to maintain equal load sharing between two compound wound DC generators operating in parallel? A. The shunt fields are interconnected. B. The shunt field rheostats ... are connected in series. D. The series fields of both generators are connected in parallel.

Last Answer : Answer: D

Description : A vessel is equipped with two ship's service generators. Generator #1 is rated at 900 kw and generator #2 is rated at 600 kw. During parallel operation, with a hotel load of 1,000 kw, what should be the kw load on generator #2? A. 100 kw B. 400 kw C. 500 kw D. 600 kw

Last Answer : Answer: B

Description : In the illustration, the contacts between terminals 26 and 27 should be closed when _________. EL-0046 A. using one generator in isochronous mode only B. using two or more generators in ... through varying loads in parallel or single operation D. the circuit breaker is closed for that generator

Last Answer : Answer: C

Description : A set of processors P1, P2, ......, Pk can execute in parallel if Bernstein's conditions are satisfied on a pair wise basis; that is  P1 || P2 || P3 || ..... || Pk if and only if: (A) Pi || Pj for all i ≠ j (B) Pi || Pj for all i = j+1 (C) Pi || Pj for all i ≤ j (D) Pi || Pj for all i ≥ j

Last Answer : (A) Pi || Pj for all i ≠ j Explanation: Bernstein's Condition: 1. If process Pi writes to a memory cell Mi, then no process Pj can read the cell Mi. 2. If process Pi read from a memory ... Mi. 3. If process Pi writes to a memory cell Mi, then no process Pj can write to the cell Mi.

Description : State the condition to be satisfied before connecting two alternators in parallel

Last Answer : The following are the three conditions to be satisfied by synchronizing the additional Alternator with the existing one or the common bus-bars. · The terminal voltage magnitude of the incoming ... incoming Alternator voltage must be the same as the bus-bar voltage. . Zero phase difference

Description : What are the conditions for parallel operation of two transformers ?

Last Answer : Transformers which are to be operated parallel should have to satisfy the following conditions: Polarities of both the transformers should be same else lead to short circuit Voltage rating of ... Phase displacement of transformers should be same Phase sequence of two transformers should be same

Description : What are the conditions for parallel operation of two transformers ?

Last Answer : Transformers which are to be operated parallel should have to satisfy the following conditions: Polarities of both the transformers should be same else lead to short circuit Voltage rating of ... Phase displacement of transformers should be same Phase sequence of two transformers should be same

Description : What are the Conditions for parallel operation of transformers?

Last Answer : A. a) Same voltage ratio of transformer: If two transformers of different voltage ratio, are connected in parallel with same primary supply voltage, there will be a difference in secondary voltages. If ... not in same phase sequence, during the cycle, each pair of phases will be short circuited.

Description : What are the conditions for parallel operation of transformer?

Last Answer : -Equal polarity -Equal turn ratio -percentage impedance should be same -Equal X/R ratio -Equal KVA rating -Equal phase sequence

Last Answer : For the parallel operation of two or more D.C. compound generators, we should ensure that series fields of all generators should be either on positive side or negative side of the armature.

Description : AC and DC generators are similar in that they _____________. A. both generate alternating voltages B. both rectify the voltage before delivery C. are constructed at the same physical size for the same kilowatt rating D. both supply three-phase power

Last Answer : Answer: A

Description : Modern DC generators are fitted with commutating poles to _____________. A. prevent motorizing B. reduce sparking C. reduce the load on the main poles D. reduce spring pressure on the brushes

Last Answer : Answer: B

Description : In a diesel electric plant, raising the generator's field excitation will cause the DC propulsion motor to ________. A. increase in speed B. decrease in speed C. affect generator speed only D. affect main motor speed if done in conjunction with higher generator engine speeds

Last Answer : Answer: A

Description : What Are The Major Parts Of The Dc Generators?

Last Answer : Yoke Poles Field winding Armature Armature winding Commutator brushes

Description : In DC generators, armature reaction is produced actually by (A) Its field current. (B) Armature conductors. (C) Field pole winding. (D) Load current in armature.

Last Answer : Ans: D Because load current in armature gives rise to armature mmf which react with main field mmf.

Description : Transformers are used onboard ships with AC generators to _____________. A. change frequency B. increase power output to modulating frequency controllers C. decrease power output to modulating frequency ... D. permit higher voltage for electric motor operation and low voltage for lighting circuits

Last Answer : Answer: D

Description : Induction generator a) can not work in isolation b) can work in isolation c) should work in parallel with synchronous generators d) any of the mentioned

Last Answer : Ans: C

Description : Diesel generators #1 and #2 are operating in parallel at near full load capacity. Diesel generator #1 suddenly trips out mechanically due to low lube oil pressure. The reverse power relay functions ... all nonvital circuits. D. Secure alarms, reset reverse power relay, and restart #1 engine.

Last Answer : Answer: C

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : If three AC generators are operating in parallel, and one of them were to 'pull out' of synchronism with the other two generators, the ____________. A. normally operating AC generators will ... AC generators will overspeed and unload D. AC generator pulling out of synchronism will become motorized

Last Answer : Answer: B

Description : When two generators are on the line and are sharing the load equally, they are said to be operating in _____________. A. frequency B. series C. parallel D. resonance

Last Answer : Answer: C

Description : Two AC generators of the same capacity are operating in parallel. One with a zero speed droop setting and the other with a 5% speed droop. If its capacity is not exceeded, the unit whose ... B. maintain the frequency of the system C. have poor sensitivity characteristics D. have poor power response

Last Answer : Answer: B

Description : If two AC generators have just been placed in parallel, the true power load is initially distributed evenly by _____________. A. a balance coil B. changing field excitation C. adjusting the governor control settings D. a rheostat

Last Answer : Answer: C

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving fast in the clockwise direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... at any pointer position D. the same as the bus frequency but out of phase with it

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving in the fast direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... the same as the bus frequency and the circuit breaker may be closed at any pointer position

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0° prior to closing the circuit breaker. This indicates ___________. A. the frequency of ... be closed after breaker has been reset D. there is an existing cross current between generators

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer is revolving in the slow direction. This indicates that the frequency of the incoming machine is _____________. A. higher than ... same as the bus frequency, and the circuit breaker may be closed at any pointer position

Last Answer : Answer: B

Description : Which is a function of the voltage regulators used with AC generators? A. To cut out generators when they are no longer required. B. To cut in additional generators automatically as ... between generators operating in parallel. D. To divide reactive current between generators operating in parallel.

Last Answer : Answer: D

Description : The division of the kilowatt load between two AC generators operating in parallel is controlled by the settings and characteristics of the _____________. A. voltage regulators B. field rheostats C. reverse power relays D. prime mover governors

Last Answer : Answer: D

Description : Kilowatt load is divided between two AC generators operating in parallel by _____________. A. adjusting the governor controls B. varying the excitation voltage C. increasing both prime mover speeds simultaneously D. decreasing both prime mover speeds simultaneously

Last Answer : Answer: A

Description : The load sharing characteristics of two diesel generators operating in parallel are mostly dependent on their governor ____________. A. load limit settings B. idle speed settings C. speed limit settings D. speed droop settings

Last Answer : Answer: D

Description : List the factors that affect the load sharing in parallel operating generators?

Last Answer : The total active and reactive power delivered to the load, connected across the common bus-bars, are shared among Synchronous generators, operating in parallel, based on the following three factors ... characteristic/input · Excitation level and · Percentage synchronous impedance and its R/X ratio

Description : 54. A constraint in an LP model becomes redundant because a. Two iso-profits may be parallel to each other b. The solution is unbounded c. This constraint is not satisfied by the solution values d. None of the above

Last Answer : d. None of the above

Description : In the impact problems the following conditions must always be satisfied a.The total kinetic energy remains unchanged b.The total linear momentum remains unchanged c.The magnitude of the total linear ... is reduced by a factor proportional to the coefficient of restitution e.None of the above

Last Answer : b. The total linear momentum remains unchanged

Description : The Tyndall effect is observed only when following conditions are satisfied : (a) The diameter of the dispersed particles is much smaller than the wav

Last Answer : The Tyndall effect is observed only when following conditions are satisfied : (a) The diameter of the dispersed particles ... ) and (c) D. (a) and (d)

Description : The shafts will have same strength on the basis of torsional rigidity, if (A) Diameter and length of both shafts is same (B) Material of both shafts is same (C) Angle of twist for both shafts is same (D) All of above conditions are satisfied

Last Answer : (D) All of above conditions are satisfied

Description : Which of the following conditions must be satisfied for lift force to be developed? (A) The body should be bluff body (B) The body should be stream lined (C) Circulation around the body is essentially required (D) The main stream velocity must approach the velocity of sound in that fluid medium

Last Answer : (C) Circulation around the body is essentially required

Description : Which of the following conditions is to be satisfied both in elastic and plastic analyses? (a) Equilibrium condition (b) Yield condition (c ) Plastic moment condition (d) Mechanism condition

Last Answer : (a) Equilibrium condition

Description : The shafts will have same strength on the basis of torsional rigidity, if (a) diameter and length of both shafts is same (b) material of both shafts is same (c) angle of twist for both shafts is same (d) all of above conditions are satisfied

Last Answer : (d) all of above conditions are satisfied

Description : What is known about the native population of New Zealand at present? (A) The natives are quite satisfied with their living conditions. (B) The natives live on good lands. (C) Both in the cities ... of the European New Zealanders. (D) The natives are never at peace with the other New Zealanders. 

Last Answer : (C) Both in the cities and in the rural areas, the life of the natives is worse than that of the European New Zealanders.

Description : An open armature connection in a DC propulsion motor could be caused by ____________. A. low-load operation B. clogged ventilation ducts C. sparking at the brushes D. a grounded shunt field coil

Last Answer : Answer: B

Description : The relative speed between the magnetic fields of stator and rotor under steady state operation is zero for a (A) dc machine. (B) 3 phase induction machine. (C) synchronous machine. (D) single phase induction machine.

Last Answer : Ans: all options are correct

Description : State any two conditions for parallel operation of 3-phase transformer.

Last Answer : Conditions for Parallel operation of 3 phase transformer 1) Voltage ratings of both the transformers must be identical. 2) Percentage or p.u. impedance should be equal in magnitude. 3) X/R ratio ... between primary & secondary voltages must be same. 6) Phase sequence on both sides must be same.

Description : List the conditions for parallel operation of three phase transformer.

Last Answer : Conditions for Parallel operation of 3 phase transformer: 1) Voltage ratings of both the transformers must be identical. 2) Percentage / p.u. impedances should be equal in magnitude. 3) X/R ratio of ... between primary & secondary voltages must be same. 6) Phase sequence of both must be same.