A shading coil used in an AC magnetic controller, functions to _____________. A. reduce vibration and noise in the contactor B. prevent flux buildup in the operating coil C. eliminate arcing when the contacts close D. energize the operating coil and 'pull in' the contacts

1 Answer

Answer :

Answer: A  

Related questions

Description : A loud buzzing noise in an AC controller is probably caused by _____________. A. poor contact with the overload relay B. an incorrectly sized heater C. a broken shading coil D. abnormal starting current

Last Answer : Answer: C

Description : If a magnetic controller contactor fails to pick up when the coil voltage is applied to the contactor coil, the cause may be _____________. A. overload B. misalignment of the affected contactor contacts C. low spring pressure D. an open contactor coil

Last Answer : Answer: D

Description : Shading coils are installed on AC full-voltage starters to _____________. A. eliminate contact chatter B. dissipate opening contact arcs C. delay current build up in the holding coil D. protect the motor windings from momentary starting current overload

Last Answer : Answer: A

Description : Magnetic controller contacts may become welded together during operating conditions as a result of _____________. A. high spring pressure B. high ambient temperature C. an open coil D. low voltage on operating coil

Last Answer : Answer: D

Description : When troubleshooting a magnetic controller, it is found that the contacts are welded together. The most probable cause is _____________. A. excessive operation at low load B. high ambient temperature C. low voltage on the operating coil D. high voltage on the operating coil

Last Answer : Answer: C

Description : In the illustration, the purpose of part B is to _________. EL-0033 A. increase resistance in series with the contacts as they close to prevent arcing B. create a magnetic field in the steel ... event of an overload D. provide ventilation to the contact when the breaker is close to rated capacity

Last Answer : Answer: B

Description : During its operation, loud buzzing and resultant welding of contacts of a magnetic relay may be caused by __________. A. overheating of the contactor coil B. low voltage on the operating coil C. low insulation resistance to ground D. lubrication of the contact bearing points

Last Answer : Answer: B

Description : If the contacts of a motor starter or controller fail to drop out when the 'stop' button is depressed the ____________. A. contacts are carrying excessive current B. contacts have become welded together C. shading coil is broken D. shading coil is loose

Last Answer : Answer: B

Description : Amortisseur windings are installed in a synchronous motor to _____________. A. reduce eddy current losses B. produce a higher power factor C. provide a means for starting D. eliminate arcing between the stator and the rotor

Last Answer : Answer: C

Description : Magnetic controller contacts may become welded together during operation because of _____________. A. excessive magnetic gap B. low contact pressure C. an open coil D. excessive ambient temperature

Last Answer : Answer: B

Description : If a magnetic controller relay fails to drop out when the coil voltage is removed from the relay, the probable cause may be _____________. A. excessive spring tension B. overvoltage C. excessive current D. welded contacts

Last Answer : Answer: D

Description : Magnetic controller contacts may become welded together during operation due to _____________. A. an open coil B. low contact pressure C. excessive ambient temperature D. excessive magnetic gap

Last Answer : Answer: B

Description : A testing device called a 'growler' is being used to locate a shorted coil in the stator of an AC electrical machine. When the 'feeler' is moved over a slot containing the shorted coil _____________. ... . the meter needle will be deflected to zero D. the meter needle will be deflected to full-scale

Last Answer : Answer: A

Description : A loud buzzing noise at the contacts of a magnetic controller could indicate _____________. A. weak contact spring pressure B. misalignment of the magnet faces C. excessive line current D. mechanical binding

Last Answer : Answer: B

Description : Why shading rings provided in armature core of ac contactor. Why not for dc contactor? 

Last Answer : Because the force developed is not steady in ac therefore contacts will chatter but if shading ring is used force developed becomes steady due to splitting of phases of flux, therefore contacts becomes bounce free and humming sound reduces.  

Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button

Last Answer : Answer: D

Description : The purpose of amortisseur windings in a synchronous motor is to ______________. A. reduce eddy current losses B. produce a higher power factor C. provide a means for starting D. eliminate arcing between the stator and the rotor

Last Answer : Answer: C

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : The winch shown in the illustration will not operate in any speed in the lowering direction and at an abnormal speed in 'first point hoist'. The possible cause is that _______________. EL-0102 A. ... '1M' in the power circuit are badly corroded D. master switch contacts 'MS6' have weak springs

Last Answer : Answer: B

Description : The 'safe switch' of the winch controller shown in the illustration is operated _______________. EL-0102 A. through the master switch handle B. when heater circuit current is high C. by contactor coil 'FR' D. manually by the winch operator

Last Answer : Answer: D

Description : Motor starter or controller contacts may become welded together if the contacts _____________. A. open too quickly and arc B. close under excessive pressure C. open or close too quickly D. close under excessive starting current

Last Answer : Answer: D

Description : Motor controller or starter contacts may become pitted and welded together if the contacts _____________. A. open under loaded conditions B. close slowly with light pressure C. open too quickly and arc D. close quickly with proportionate pressure

Last Answer : Answer: B

Description : Which of the following methods should be used to test for an 'open' coil in an AC motor stator? A. Test with an ohmmeter, one test lead on the shaft, and the other test lead to the stator leads ... an open coil. D. Use a growler, listening for noise and vibration to increase when over an open coil.

Last Answer : Answer: B

Description : One function of the movable cams in a drum-type motor controller is to _____________. A. regulate the speed of the motor B. maintain resistance contacts in clean condition C. insulate the operating handle D. limit the amount of load put on the motor

Last Answer : Answer: A

Description : A loud buzzing noise coming from the contacts in a magnetic controller can be caused by ____________. A. excessive current B. excessive magnet gap C. bouncing of contacts D. dirt on magnet faces

Last Answer : Answer: D

Description : When troubleshooting a motor controller, all indications are that a relay coil should be energized. If there were no magnetic pull, with rated voltage measured across the coil, the most probable cause ... open C. auxiliary contact in series with the coil is defective D. relay armature is stuck

Last Answer : Answer: A

Description : Burning of controller contacts, when opening, is prevented by _____________. A. coating the contact surfaces lightly with petroleum jelly B. magnetic blowout coils C. an overvoltage release D. an overcurrent release

Last Answer : Answer: B

Description : Excessive humming of AC contactors may be caused by ______________. A. burnt arc shields B. shorted armature coils C. a broken shading coil D. high voltage

Last Answer : Answer: C

Description : As shown in the illustration, which listed action will occur first when push button 'Q' is depressed? EL-0017 A. Contacts 'H-1', 'H-2' and 'H-3' close. B. Contact 'H-4' closes. C. Operating coil 'C' energizes. D. Switch 'R' opens.

Last Answer : Answer: C

Description : If many turns of an alternating current coil for a contactor become short circuited, the coil _____________. A. will continue to operate B. will probably burn out immediately C. will operate on reduced current D. temperature will drop

Last Answer : Answer: B

Description : If many turns of an alternating current coil for a contactor become short circuited, the coil _____________. A. temperature will drop B. will probably burn out immediately C. will continue to operate D. will operate on reduced current

Last Answer : Answer: B

Description : Magnet chatter or 'pumping' occurring in a magnetic contactor can be caused by ______________. A. dirt or grease on pole faces B. mechanical interference in the contacts C. chattering contacts on the control relay D. magnetic lock out of the contacts

Last Answer : Answer: C

Description : If a magnetic controller contact fails to pick up when the operating coil is energized, one possible cause may be _______________. A. low spring pressure B. low voltage to the coil C. the residual magnetism of the contact faces D. dirty contact faces

Last Answer : Answer: B

Description : The purpose of a magnetic relay is to _____________. A. open a circuit only in the event of overload B. remotely open and close contacts C. provide overcurrent protection during starting D. relay voltages at increased power

Last Answer : Answer: B

Description : If you hear a loud buzzing noise coming from a magnetic motor controller, you should ____________. A. assume that the motor is operating at a full load B. assume that the controller is operating normally C. ... of the problem D. feel the outside of the casing with your hand to see if it is hot

Last Answer : Answer: C

Description : The purpose of squirrel-cage windings in a synchronous motor is to ______________. A. provide more precise balancing B. produce a higher power factor C. eliminate arcing between the stator and the frame D. provide a means for starting

Last Answer : Answer: D

Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown

Last Answer : Answer: B

Description : Complete controller maintenance includes _____________. A. periodic testing of protective devices B. checking for loose or worn contacts and weak springs C. maintaining a sufficient supply of spare parts D. all of the above

Last Answer : Answer: D

Description : The pitting of controller contacts can be caused by _____________. A. excessive spring pressure B. insufficient contact pressure C. continuous motor overload D. all of the above

Last Answer : Answer: B

Description : Motor controllers are seldom troubled by grounds because ________________. A. cabinet heaters always keep internal components dry B. special insulation is used on wire for vital circuits C. ... on controller panels greatly reduce vibration D. contactors and relays are mounted on nonconducting panels

Last Answer : Answer: D

Description : When troubleshooting a console circuit card which is suspected of being faulty, the first step would be to _____. A. pull the card and measure the value of all resistors B. check for the ... for burned components D. check for continuity of circuit board traces and then the gain of each transistor

Last Answer : Answer: C

Description : If the line voltage to the controller shown in the illustration is 440 volts, what voltage is applied across the motor when contacts 'S' close? EL-0080 A. 110 volts B. 220 volts C. 440 volts D. 660 volts

Last Answer : Answer: B

Description : A molded-case circuit breaker provides protection against short circuits by using a/an ________________. A. electromagnet B. shading coil C. arc quencher D. burn away strip

Last Answer : Answer: A

Description : A molded-case breaker provides protection against short circuits by using a/an ____________. A. shading coil B. arc quencher C. electromagnet D. holding coil

Last Answer : Answer: C

Description : Can we file the pitted contacts of contactor?

Last Answer : No, use emery paper and etc.  

Description : When the motor shown in the illustration is running and the stop button is pushed, which of the following statements will hold true? EL-0010 A. Coil 'M' will now be energized. B. Coil 'CR' will now be energized. C. Contact 'M' will close as contact 'CR' opens. D. Contacts 'M' and 'CR' will open.

Last Answer : Answer: D