If a magnetic controller contact fails to pick up when the operating coil is energized, one possible cause may be _______________. A. low spring pressure B. low voltage to the coil C. the residual magnetism of the contact faces  D. dirty contact faces

1 Answer

Answer :

Answer: B

Related questions

Description : If a magnetic controller contactor fails to pick up when the coil voltage is applied to the contactor coil, the cause may be _____________. A. overload B. misalignment of the affected contactor contacts C. low spring pressure D. an open contactor coil

Last Answer : Answer: D

Description : If a magnetic controller relay fails to drop out when the coil voltage is removed from the relay, the probable cause may be _____________. A. excessive spring tension B. overvoltage C. excessive current D. welded contacts

Last Answer : Answer: D

Description : When troubleshooting a motor controller, all indications are that a relay coil should be energized. If there were no magnetic pull, with rated voltage measured across the coil, the most probable cause ... open C. auxiliary contact in series with the coil is defective D. relay armature is stuck

Last Answer : Answer: A

Description : Magnetic controller contacts may become welded together during operating conditions as a result of _____________. A. high spring pressure B. high ambient temperature C. an open coil D. low voltage on operating coil

Last Answer : Answer: D

Description : A loud buzzing noise at the contacts of a magnetic controller could indicate _____________. A. weak contact spring pressure B. misalignment of the magnet faces C. excessive line current D. mechanical binding

Last Answer : Answer: B

Description : When troubleshooting a magnetic controller, it is found that the contacts are welded together. The most probable cause is _____________. A. excessive operation at low load B. high ambient temperature C. low voltage on the operating coil D. high voltage on the operating coil

Last Answer : Answer: C

Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown

Last Answer : Answer: B

Description : Magnetic controller contacts may become welded together during operation because of _____________. A. excessive magnetic gap B. low contact pressure C. an open coil D. excessive ambient temperature

Last Answer : Answer: B

Description : Magnetic controller contacts may become welded together during operation due to _____________. A. an open coil B. low contact pressure C. excessive ambient temperature D. excessive magnetic gap

Last Answer : Answer: B

Description : During its operation, loud buzzing and resultant welding of contacts of a magnetic relay may be caused by __________. A. overheating of the contactor coil B. low voltage on the operating coil C. low insulation resistance to ground D. lubrication of the contact bearing points

Last Answer : Answer: B

Description : Insufficient brush pressure on a DC motor may cause _______. A. generator overload B. excess residual magnetism C. water vapor absorption D. sparking of the brushes

Last Answer : Answer: D

Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button

Last Answer : Answer: D

Description : The illustrated motor fails to start and gives a loud hum when the start button is depressed, your first action should be to __________. EL-0007 A. disassemble the motor to fix the centrifical ... D. hold the 'M' contactor closed by hand while wearing electrical safety gloves to get motor started

Last Answer : Answer: B

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : Voltage build up in an isolated induction generator depends on A. Capacitor bank value B. Residual magnetism of the rotor iron C. Residual magnetism of the stator iron a) A, B b) A, B, C c) B d) A, C

Last Answer : Ans: A

Description : The 'safe switch' of the winch controller shown in the illustration is operated _______________. EL-0102 A. through the master switch handle B. when heater circuit current is high C. by contactor coil 'FR' D. manually by the winch operator

Last Answer : Answer: D

Description : A shading coil used in an AC magnetic controller, functions to _____________. A. reduce vibration and noise in the contactor B. prevent flux buildup in the operating coil C. eliminate arcing when the contacts close D. energize the operating coil and 'pull in' the contacts

Last Answer : Answer: A

Description : When the motor shown in the illustration is running and the stop button is pushed, which of the following statements will hold true? EL-0010 A. Coil 'M' will now be energized. B. Coil 'CR' will now be energized. C. Contact 'M' will close as contact 'CR' opens. D. Contacts 'M' and 'CR' will open.

Last Answer : Answer: D

Description : The winch shown in the illustration will not operate in any speed in the lowering direction and at an abnormal speed in 'first point hoist'. The possible cause is that _______________. EL-0102 A. ... '1M' in the power circuit are badly corroded D. master switch contacts 'MS6' have weak springs

Last Answer : Answer: B

Description : If the circuit shown in the illustration were energized and operating properly, which of the devices listed would be open? EL-0007 A. The stop push-button B. The start push-button C. Contact 'Ma' D. Contact 'OL1'

Last Answer : Answer: B

Description : A loud buzzing noise coming from the contacts in a magnetic controller can be caused by ____________. A. excessive current B. excessive magnet gap C. bouncing of contacts D. dirt on magnet faces

Last Answer : Answer: D

Description : If the motor fails to start and a voltmeter reading between 1 and 6, as illustrated, indicates line voltage, your next step should be to ________. EL-0007 A. replace fuse '10a' B. replace or repair contact 'Ma' C. reset and determine the cause of the overload D. check line voltage between L1 and L3

Last Answer : Answer: C

Description : The pitting of controller contacts can be caused by _____________. A. excessive spring pressure B. insufficient contact pressure C. continuous motor overload D. all of the above

Last Answer : Answer: B

Description : The motor starts when the start button in the illustration is pushed, but stops when the button is released the trouble is _________. EL-0007 A. the incorrect thermal overload coil B. a faulty 'M' coil C. a dirty contact on the Disc.Sw. at 'L3' D. a faulty holding relay contact

Last Answer : Answer: D

Description : In the illustrated test, if the lamp fails to light on any of the three windings then _________. EL-0027 A. all three windings are grounded and the motor should be sent out for repair B. ... the motor controller and the controller should be checked D. the test should be redone at a higher voltage

Last Answer : Answer: C

Description : If the illustrated motor fails to start and gives a loud hum when the start button is pushed, the problem is ________. EL-0007 A. one of the phases to the motor is not energized because of ... electrical distribution system D. 'OL1' is open because of 'T1' overload causing the motor to single phase

Last Answer : Answer: A

Description : Excessive heat in an operating motor controller can result from _____________. A. a closed starter contact B. loose connections C. missing arc chutes D. low motor starting torque

Last Answer : Answer: B

Description : If a D.C. motor hums, but does not run when energized, which of the listed conditions could exist? A. Incorrect lead connections B. Incorrect brush setting C. A dirty commutator D. All of the above are correct.

Last Answer : Answer: D

Description : When troubleshooting motor controllers, a shorted relay or contactor coil is often indicated by _______________. A. a resistance reading of 'infinity' on an ohmmeter B. charred insulation and/or a blown ... of the coil's leads to ground D. a higher-than-normal voltage reading across the winding

Last Answer : Answer: B

Description : In an AC circuit, the inductive reactance of a coil varies with the _______________. A. resistance of the circuit B. frequency of the circuit C. voltage of the circuit D. current of the circuit

Last Answer : Answer: B

Description : If overloading a DC machine becomes necessary in an emergency, you should ____________. A. cool the machine with portable blowers and fans B. hold thermal overload relays open with blocks of ... the windings for cooling D. increase the residual magnetism value of windings to reduce eddy currents

Last Answer : Answer: A

Description : The insulation of electric generators during short idle periods should be _____________. A. allowed to cool slowly to ambient temperatures B. flashed with direct current to remove any residual ... using strip or space heaters D. relieved of all capacitive charge by grounding the conductors

Last Answer : Answer: C

Description : Which of the methods listed is used to start a AC generator turning? A. Residual magnetism remaining in the field poles. B. Residual magnetism remaining in the field coils. C. Residual magnetism remaining in the armature. D. Rotation by a mechanical prime mover.

Last Answer : Answer: D

Description : In replacing a defective transformer with a new one, which of the following actions must be carried out to insure proper operation of the equipment it serves? A. The secondary leads must be grounded ... magnetize it. D. The iron core must be grounded for 10 minutes to remove any residual magnetism.

Last Answer : Answer: B

Description : One of the generator bearing shells is generally insulated from the end housing in order to prevent _____________. A. rapid brush wear B. residual magnetism leak off C. excessive field winding heat D. circulation of shaft currents

Last Answer : Answer: D

Description : Loss of or weak residual magnetism in an alternator or generator can be corrected for by _________________. A. running the rotor in the opposite direction for 5 minutes B. allowing the generator ... rheostat fully counterclockwise D. using a storage battery or battery charger to 'flash' the field

Last Answer : Answer: D

Description : The greatest detrimental effect on idle electrical equipment, such as cargo pump motors, is the _____________. A. loss of residual magnetism B. absorption of moisture in the insulation C. insulation varnish flaking D. dirt collecting on the windings

Last Answer : Answer: B

Description : The amount of voltage induced in the windings of an AC generator depends mainly on _____________. A. the number of field poles energized B. the speed at which the stator windings rotate through the magnetic field C. the strength of the magnetic field D. all of the above

Last Answer : Answer: C

Description : A loud buzzing noise in an AC controller is probably caused by _____________. A. poor contact with the overload relay B. an incorrectly sized heater C. a broken shading coil D. abnormal starting current

Last Answer : Answer: C

Description : To stop the electric motor shown in the illustration, the stop button is depressed, causing ____________. EL-0012 A. coil 'MS' to become de-energized B. contacts 'CR1' and 'MR4' to open C. contacts 'MR1', 'MR2', and 'MR3' to open D. contacts 'MS1', 'MS2', and 'MS3' to open

Last Answer : Answer: C

Description : To test fuses in an energized circuit, you should use a ____________. A. low voltage light bulb B. megohmmeter C. voltmeter D. resistance meter

Last Answer : Answer: C

Description : Humming or buzzing of electric contacts is a symptom of ____________. A. low voltage on the operating coil B. power failure to the operating coil C. a control circuit ground D. a control circuit overload

Last Answer : Answer: A

Description : Which of the following precautions should be taken when a blown fuse, rated at 10 amperes, is replaced? A. Short out the fuse before removing it from the circuit. B. Use needle-nose pliers to ... D. Fuses of 10 ampere rating and less are virtually harmless when energized and may be handled freely.

Last Answer : Answer: C

Description : A megohmmeter is connected to each end of an individual motor winding. A low ohm reading indicates ____________. A. an open coil B. a loose coil C. good continuity D. a dirty coil

Last Answer : Answer: C

Description : The winch shown in the illustration operates in any of the positions with the master switch in the 'lower' direction, but will not 'hoist' in any of the master switch hoist positions. Which of the listed faults ... '2M' in the power circuit may be badly corroded. D. Series relay 'FR' may be open.

Last Answer : Answer: A

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : As shown in the illustration, when the 'speed control' system is in 'SPLIT' _______________. EL-0096 A. Relays #1, #5 and #8 are not used B. the 'slew rated controller' is grounded through Relay ... E/P converters' are bypassed and air is fed directly to the governors via the 'load sharing valve'

Last Answer : Answer: C