Why is it desirable to operate paralleled AC generators at the same power factor? A. Circulating currents are kept to a minimum. B. Field excitation losses are kept to a minimum. C. Generator rotors will have a lesser tendency to hunt. D. Because a power factor increase will decrease kilowatt output.

1 Answer

Answer :

Answer: A

Related questions

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation of the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. type of alternator

Last Answer : Answer: B

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation to the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. number of field poles per alternator

Last Answer : Answer: B

Description : The power factor of an AC generator operating singularly is determined by the __________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: A

Description : In a diesel electric plant, raising the generator's field excitation will cause the DC propulsion motor to ________. A. increase in speed B. decrease in speed C. affect generator speed only D. affect main motor speed if done in conjunction with higher generator engine speeds

Last Answer : Answer: A

Description : Kilowatt load is divided between two AC generators operating in parallel by _____________. A. adjusting the governor controls B. varying the excitation voltage C. increasing both prime mover speeds simultaneously D. decreasing both prime mover speeds simultaneously

Last Answer : Answer: A

Description : The kilowatt load can be adjusted on a paralleled generator by using the _____________. A. field rheostat B. governor control C. automatic voltage regulators D. hand tachometer

Last Answer : Answer: B

Description : When securing an AC generator, you should FIRST ___________. A. open the generator circuit breaker B. switch the voltage regulator to 'manual' C. decrease the field excitation to minimum D. reduce the load on the unit

Last Answer : Answer: D

Description : An equalizing connection between two compound-wound DC generators when paralleled, serves to _____________. A. reverse the polarity of the incoming generator as the series field weakens B. automatically ... the series field of the incoming generator D. parallel the series fields of the generators

Last Answer : Answer: D

Description : Automatic voltage regulators provided on switchboards function to _____________. A. regulate the AC load on the generator B. protect the switchboard from high voltage C. govern prime mover speed to control voltage D. vary the field excitation to the generators

Last Answer : Answer: D

Description : To increase the frequency of an operating AC generator, you should ____________. A. increase the field excitation B. decrease the field excitation C. increase the number of magnetic poles D. increase the speed of the prime mover

Last Answer : Answer: D

Description : The division of the kilowatt load between two AC generators operating in parallel is controlled by the settings and characteristics of the _____________. A. voltage regulators B. field rheostats C. reverse power relays D. prime mover governors

Last Answer : Answer: D

Description : To equalize the power factor of two alternators operating in parallel, the ____________. A. field excitation of both units is adjusted B. governors of both units are adjusted C. phase sequence is altered D. kilowatt load is evenly divided

Last Answer : Answer: A

Description : Equal power factors on paralleled AC generators are maintained by an automatic _____________. A. voltage regulator B. reverse power relay C. reverse current relay D. governor control switch

Last Answer : Answer: A

Description : A change in field excitation of an alternator operating in parallel will cause a change in its _____________. A. alternator frequency B. kilowatt load C. voltage output D. all of the above

Last Answer : Answer: C

Description : When paralleled, AC generators must have the same _________. A. frequency B. number of phases C. phase rotation D. all of the above

Last Answer : Answer: D

Description : On electrical generators one of the bearings is isolated from the bedplate. This insulating block should not be painted and must be kept clean to ___________. A. protect operating personnel from shock ... the prime mover as it warms up D. eliminate shaft currents to prevent damaging the bearings

Last Answer : Answer: D

Description : The standard method of controlling the output voltage of a 440 volt, 60 Hz, AC generator is accomplished by adjusting the ____________. A. prime mover speed droop B. number of poles C. alternator field excitation D. load on the alternator

Last Answer : Answer: C

Description : If two AC generators have just been placed in parallel, the true power load is initially distributed evenly by _____________. A. a balance coil B. changing field excitation C. adjusting the governor control settings D. a rheostat

Last Answer : Answer: C

Description : AC and DC generators are similar in that they _____________. A. both generate alternating voltages B. both rectify the voltage before delivery C. are constructed at the same physical size for the same kilowatt rating D. both supply three-phase power

Last Answer : Answer: A

Description : Transformers are used onboard ships with AC generators to _____________. A. change frequency B. increase power output to modulating frequency controllers C. decrease power output to modulating frequency ... D. permit higher voltage for electric motor operation and low voltage for lighting circuits

Last Answer : Answer: D

Description : A diesel driven emergency generator is prevented from being paralleled with the ship's service generators by __________. A. an electrical interlock system B. an automatic paralleling trip switch C. the synchronizing oscilloscope D. the reverse current relay

Last Answer : Answer: A

Description : The division of the reactive KVA load between paralleled AC generators is initiated by the ______________. A. prime mover governors B. voltage regulators C. phase balance relay D. proportioner

Last Answer : Answer: B

Description : When two AC generators are being paralleled, the breaker should be closed with the synchroscope pointer rotating in the ____________. A. 'slow' direction, just before the 12 o'clock position B. 'fast' ... just before the 12 o'clock position D. 'slow' direction, just after the 12 o'clock position

Last Answer : Answer: C

Description : If the excitation of an alternator operating in parallel is decreased below normal, its _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. ampere load will be greatly increased D. kilowatt load will be greatly decreased

Last Answer : Answer: B

Description : If the excitation is increased to one of two alternators operating in parallel, the _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. kilowatt load will be greatly increased D. ampere load will be greatly decreased

Last Answer : Answer: A

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : The most practical way to control the voltage output of an AC generator is to vary the _____________. A. number of windings B. speed of the rotating field C. strength of the rotating magnetic field D. power factor of the load

Last Answer : Answer: C

Description : The voltage developed by an AC generator is controlled by varying the ____________. A. speed of the prime mover B. AC excitation to the field C. DC excitation to the field D. DC excitation of the voltage regulator

Last Answer : Answer: C

Description : As load is added to an AC generator provided with constant field excitation, the prime mover slows down with the effect of ____________. A. lowering frequency and lowering generated ... C. increasing frequency and lowering generated voltage D. lowering frequency and increasing generated voltage

Last Answer : Answer: A

Description : A shore power circuit breaker should be closed only _____________. A. when the ship's generators have been directly paralleled to those on shore B. in a shipyard C. if a quick disconnect coupling is used D. when the ship's generators have been removed from the bus

Last Answer : Answer: D

Description : When shore power is being connected to a ship in dry dock, _____________. A. the ship's generators are paralleled with the shore power to provide continuous power B. proper phase sequence must be ... 450 volts must be supplied from the shore D. exactly 60 Hz must be provided by the terminal

Last Answer : Answer: B

Description : The effect of carrying field excitation excessively high on a synchronous motor will result in a _____________. A. tendency for the motor to fall out of step B. tendency for the motor to overspeed C. tendency for the motor to overheat D. loss of motor speed regulation

Last Answer : Answer: C

Description : If field excitation is suddenly lost to an alternator operating in parallel, that alternator will _____________. A. supply excessive current to the bus B. operate at the same load, but with reduced voltage C. lose its load and tend to overspeed D. become overloaded and slow down

Last Answer : Answer: C

Description : An alternator is being paralleled with one on the line. At the INSTANT the circuit breaker is closed, the frequency of the incoming alternator will normally _____________. A. increase B. not change C. decrease D. be exactly 60 hertz

Last Answer : Answer: C

Description : Attempting to parallel an AC generator which is out of phase with the bus will result in which of the following problems? A. The breaker should trip. B. The KVA will decrease. C. The synchronizing lamps will burn out. D. The power factor will be unitized.

Last Answer : Answer: A

Description : When paralleling two AC generators, the frequency (cycles) of the incoming generator, just prior to closing the circuit breaker, should be _____________. A. slightly less than the frequency of the generator on ... C. slightly more than the frequency of the generator on the line D. all of the above

Last Answer : Answer: C

Description : When paralleling two AC generators, the frequency of the machine coming online, immediately prior to closing its breaker, should be ____________. A. slightly less than the oncoming generator frequency B. the ... bus frequency C. slightly greater than the bus frequency D. the same as the bus voltage

Last Answer : Answer: C

Description : The purpose of DC generator brushes is to _____________. A. neutralize armature reaction B. conduct electric current to an outside circuit C. convert DC current to AC current D. provide excitation to a DC generator

Last Answer : Answer: B

Description : The most common source of excitation for synchronous motors is a/an _____________. A. low voltage battery B. motor attenuator set C. DC exciter generator D. AC supply

Last Answer : Answer: C

Description : The removal of paint from electrical equipment, such as generators, should be cautiously undertaken because ____________. A. the mechanical shock of paint removal lessens the dielectric strength ... phase windings frequently become isolated from each other due to dust interference at the terminals

Last Answer : Answer: B

Description : Which of the following statement(s) is/are true concerning protein/amino acid metabolism in man? a. The major source of amino acids is breakdown of circulating proteins b. The recommended daily ... balance refers to a decrease in nitrogen taken into the body versus the amount of nitrogen lost

Last Answer : Answer: b, d About 15% of the total body weight is made up of proteins, about half of which are intracellular and half extracellular. In man and other animals, dietary protein is the source of ... is exceeded by the amount of nitrogen lost in the urine, stool, skin, wounds, and fistula drainage

Description : If three AC generators are operating in parallel, and one of them were to 'pull out' of synchronism with the other two generators, the ____________. A. normally operating AC generators will ... AC generators will overspeed and unload D. AC generator pulling out of synchronism will become motorized

Last Answer : Answer: B

Description : When paralleling two AC generators, the synchroscope selector switch and frequency meter switch should be set up to sense the frequency of the _____________. A. bus B. generator on the line C. oncoming generator D. bus transfer relay

Last Answer : Answer: C

Description : Two paralleled alternators are operating near rated load. If one trips out mechanically, which of the listed actions should be taken FIRST? A. Restart the tripped machine immediately. B. Strip the board ... circuits. C. Start the emergency generator. D. Transfer all vital loads to the emergency bus.

Last Answer : Answer: B

Description : An AC generator produces 60 Hz at 1800 RPM. If the generator speed is increased to 1830 RPM, the cycles will _____________. A. remain at 60 Hz B. increase to 61 Hz C. decrease to 59 Hz D. increase to 63 Hz

Last Answer : Answer: B

Description : Which of the following problems will occur if the circuit breaker of the incoming alternator is closed and it is 180° out of phase with the loaded alternator when paralleling? A. The rotor of the ... The rotor of the incoming alternator will stop. D. Both alternators will parallel 180° out of phase.

Last Answer : Answer: B