A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be 

(A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

1 Answer

Answer :

A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be 15.79 kA

Related questions

Description : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

Last Answer : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is 0.01

Description : A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be  A) 100 MJ B) 400 MJ C) 800 MJ D) 12.5 MJ

Last Answer : 800

Description : A 100 kVA, 415 V(line), star-connected synchronous machine generates rated open circuit voltage of 415 V at a field current of 15 A. The short circuit armature current at a field current of 10 A is equal to the ... unit saturated synchronous reactance is  (A) 1.731 (B) 1.5 (C) 0.666 (D) 0.577

Last Answer : 0.6

Description : The voltage at the two ends of a transmission line are 132 KV and its reactance is 40 ohm. The Capacity of the line is (A) 435.6 MW (B) 217.8 MW (C) 251.5 MW (D) 500 MW

Last Answer : (A) 435.6 MW

Description : Why the earthing transformer primary voltage is 16.5 kV rated in main generator even though actual voltage during the E/F is root 3 times less?

Last Answer : The transformer should not saturate during E/F otherwise it will cause ferroresonance with the GT winding capacitance. Dangerous O/V and neutral shifting will occur. During loss of load or field ... saturation. Saturation can also occur due to point on wave of application causing flux doubling. 

Description : A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is (A) 2/15 p.u. (B) 5/6 p.u. (C) 1.0 p.u. (D) 1.2 p.u.

Last Answer : A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is 5/6 p.u.

Description : A synchronous generator is feeding a zero power factor (lagging) load at rated current. The armature reaction is  (A) magnetizing (B) demagnetizing (C) cross-magnetizing (D) ineffective

Last Answer : A synchronous generator is feeding a zero power factor (lagging) load at rated current. The armature reaction is demagnetizing 

Description : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per ... 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

Last Answer : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained ... load to increase the line-to-line voltage at the load terminals to 11 kV is -10.1 MVAR

Description : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the ... the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

Last Answer : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume ... the shaft. The accelerating torque in the generator in MNm at the time of fault will be 1.018 

Description : In a certain three -wire Y -connected generator, the phase voltages are 2 kV. The magnitudes of the line voltages will be: A. 2,000 V B. 6,000 V C. 666 V D. 3,464 V

Last Answer : In a certain three -wire Y -connected generator, the phase voltages are 2 kV. The magnitudes of the line voltages will be: 3,464 V

Description : A three phase, salient pole synchronous motor is connected to an infinite bus. It is operated at no load a normal excitation. The field excitation of the motor is first reduced to zero ... First increases and then decreases steeply (C) First decreases and then increases steeply (D) Remains constant

Last Answer : B

Description : A hydraulic turbine having rated speed of 250 rpm is connected to a synchronous generator. In order to produce power at 50 Hz, the number of poles required in the generator are (A) 6 (B) 12 (C) 16 (D) 24

Last Answer : A hydraulic turbine having rated speed of 250 rpm is connected to a synchronous generator. In order to produce power at 50 Hz, the number of poles required in the generator are 24

Description : A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is (A) 1500 r.p.m. (B) 1425 r.p.m. (C) 25 r.p.m. (D) 75 r.p.m.

Last Answer : (D) 75 r.p.m.

Description : The active power of a synchronous generator can be varied mainly by (a) changing field excitation (b) changing of prime mover speed (c) both (a) and (b) (d) none of the above

Last Answer : C

Description : A stand alone engine driven synchronous generator is feeding a partly inductive load. A capacitor is now connected across the load to completely nullify the inductive current. For this operating condition.  ... left unaltered (D) the field current has to be reduced and fuel input left unaltered

Last Answer : A stand alone engine driven synchronous generator is feeding a partly inductive load. A capacitor is now connected across the load to completely nullify the inductive current. For this operating condition.  the field current has to be reduced and fuel input left unaltered

Description : The angle δ in the swing equation of a synchronous generator is the  (A) angle between stator voltage and current (B) angular displacement of the rotor with respect to the stator (C) angular ... (D) angular displacement of an axis fixed to the rotor with respect to a synchronously rotating axis

Last Answer : The angle δ in the swing equation of a synchronous generator is the angular displacement of an axis fixed to the rotor with respect to a synchronously rotating axis

Description : For a fault at the terminals of a synchronous generator, the fault current is maximum for a  A) 3-phase fault B) 3-phase to ground fault C) Line to ground fault D) Line to line fault

Last Answer : C) Line to ground fault

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : A 60 Hz, 4 pole turbo generator rated 100 MVA, 13.8 KV has an inertia constant of 10 MJ/MVA. Find the stored energy in the rotor at synchronous speed.  (A) 10 MJ (B) 100 J (C) 1000 J (D) 1000 MJ 

Last Answer : c

Description : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 ... load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

Last Answer : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/ ... MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be 36 

Description : The power factor of an AC generator operating singularly is determined by the __________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: A

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Last Answer : In case one phase of a three-phase synchronous motor is short-circuited the motor will not start.

Description : An unexcited single phase synchronous motor is ?

Last Answer : An unexcited single-phase synchronous motor is reluctance motor.

Description : Three phase synchronous motor will have how many sliprings?

Last Answer : Three phase synchronous motor will have two sliprings.

Description : The maximum possible power of a 3-phase synchronous motor with synchronous reactance 0.8 p.u. connected to a bus-bar of 1.0 p.u. and excitation adjusted to 1.2 p.u. is (A) 0.5 p.u. (B) 0.96 p.u. (C) 1.5 p.u. (D) 1.8 p.u.

Last Answer : The maximum possible power of a 3-phase synchronous motor with synchronous reactance 0.8 p.u. connected to a bus-bar of 1.0 p.u. and excitation adjusted to 1.2 p.u. is 1.5 p.u.

Description : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is  (A) 1200 A (B) 3600 A (C) 35 kA (D) 104.8 kA

Last Answer : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is 35 kA 

Description : A 3-phase circuit breaker is rated at 1250 A, 2000 MVA, 33 kV, 4s. Its making current capacity will be   (a) 35 kA (b) 89 kA (c) 79 kA (d) 69 kA

Last Answer : 89

Description : A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

Last Answer : 543A

Description : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of ... the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

Last Answer : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, ... line. The voltage of the alternator neutral with respect to ground during the fault is 642.2 V

Description : A three phase transmission line delivers a load of 5 MW at 0.8 power factor lagging. Resistance of each conductor is 0.5 ohm / km. Receiving end voltage is 33 kV. If the line loss is not to exceed 10%, determine the length of the line.  (A) 7 km (B) 27.9 km (C) 56.8 km (D) 13.9 km

Last Answer : B

Description : Two synchronous generators operating in parallel supply a common load of 2.5 MW. The frequency-power characteristics have a common slope of 1 MW/Hz and the no-load frequencies of the generators are 51.5 Hz and 51.0 Hz, ... system frequency is (A) 50 Hz (B) 51 Hz (C) 51.25 Hz (D) 51.5 Hz

Last Answer : Two synchronous generators operating in parallel supply a common load of 2.5 MW. The frequency-power characteristics have a common slope of 1 MW/Hz and the no-load frequencies of the generators are 51.5 Hz and 51.0 Hz, respectively. Then the system frequency is 50 Hz

Description : If an induction motor were to be operated at 90% rated voltage, _____________. A. there would be an increase in starting torque B. starting current would increase slightly C. synchronous speed would decrease slightly D. the slip would increase

Last Answer : Answer: D

Description : For transmission of power over a distance of 500 km, the transmission voltage should be in the range (a) 150 to 220 kV (b) 100 to 120 kV (c) 60 to 100 kV (d) 20 to 50 kV

Last Answer : (a) 150 to 220 kV

Description : A vessel is equipped with two ship's service generators. Generator #1 is rated at 900 kw and generator #2 is rated at 600 kw. During parallel operation, with a hotel load of 1,000 kw, what should be the kw load on generator #2? A. 100 kw B. 400 kw C. 500 kw D. 600 kw

Last Answer : Answer: B

Description : Regarding an AC generator connected to the main electrical bus; as the electric load and power factor vary, a corresponding change is reflected in the generator armature reaction. These changes in ... . governor speed droop setting B. voltage regulator C. balance coil D. phase-balance relay

Last Answer : Answer: B

Description : When a voltage of 115 VDC is applied to the illustrated circuit with a resistance of 470 ohms the current will be _______. EL-0018 A. 244 milliamps B. 4.07 amps C. 5.85 amps D. 19.21 amps

Last Answer : Answer: A

Description : A three-phase cage induction motor is started by direct-on-line (DOL) switching at the rated voltage. If the starting current drawn is 6 times the full load current, and the full load slip is 4%, then ratio of the ... load torque is approximately equal to (A) 0.24 (B) 1.44 (C) 2.40 (D) 6.00

Last Answer : A three-phase cage induction motor is started by direct-on-line (DOL) switching at the rated voltage. If the starting current drawn is 6 times the full load current, and the full load slip is 4%, then ratio of the starting developed torque to the full load torque is approximately equal to 1.44

Description : In a Y -connected circuit, between each line -voltage and the nearest phase - voltage, there is a phase -angle of: A. 0° B. 30° C. 60° D. 120°

Last Answer : B

Description : The number of electrical degrees ‘passed through’ in one revolution of a 6-pole synchronous alternator is: A) 360 degree B) 720 degree C) 1080 degree D) 2160 degree

Last Answer : 1080

Description : A cylindrical rotor synchronous motor is switched on to the supply with its field windings shorted on themselves, the motor will .  A) Not start B) Start but will not run at synchronous speed C) Start as an induction motor and then run as a synchronous motor D) Start and run as a synchronous motor

Last Answer : A cylindrical rotor synchronous motor is switched on to the supply with its field windings shorted on themselves, the motor will Start but will not run at synchronous speed

Description : In relation to the synchronous machines, which on of the following statements is false ?  (A) In salient pole machines, the direct-axis synchronous reactance is greater than the quadrature- ... motor represents the variation in the armature current with field excitation, at a given output power.

Last Answer : In relation to the synchronous machines, which on of the following statements is false ?  (A) In salient pole machines, the direct-axis synchronous reactance is greater than the quadrature- ... motor represents the variation in the armature current with field excitation, at a given output power.

Description : During hunting of synchronous motor  A) Negative phase sequence currents are generated B) Harmonics are developed in the armature current C) Damper bars develop torque D) Field excitation increases 

Last Answer : During hunting of synchronous motor Damper bars develop torque

Last Answer : Slip-rings in a synchronous motor carry direct current.

Last Answer : The efficiency of a properly designed synchronous motor will usually fall in range 85 to 95%.

Description : A synchronous motor has better power factor as compared to that of an equivalent induction motor. This is mainly because?

Last Answer : A synchronous motor has better power factor as compared to that of an equivalent induction motor. This is mainly because stator supply is not required to produce magnetic field.

Last Answer : A synchronous motor running with normal excitation adjusts to load increases essentially by increase in armature current.

Last Answer : The standard full-load power factor ratings for synchronous motors are unity or 0.8 leading.

Last Answer : Synchronsizing power of a synchronous machine is inversely proportional to the synchronous reactance.