Why the earthing transformer primary voltage is 16.5 kV rated in main generator even though actual voltage during the E/F is root 3 times less?

1 Answer

Answer :

The transformer should not saturate during E/F otherwise it will cause ferroresonance with the GT winding capacitance. Dangerous O/V and neutral shifting will occur. During loss of load or field forcing conditions, the transformer voltage increases to cause saturation. Saturation can also occur due to point on wave of application causing flux doubling. 

Related questions

Description : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

Last Answer : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be 15.79 kA

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer : A. As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer :  As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps

Description : A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

Last Answer : 543A

Description : A split-phase induction squirrel-cage motor will not come up to speed, even though the rated voltage, rated frequency, and rated load are applied. The suspected trouble could be due to _____________. A. a faulty centrifugal switch B. broken rotor bars C. worn bearings D. all of the above

Last Answer : Answer: D

Description : The torque produced by a motor when its shaft will not turn, even though rated voltage is applied to the stator, is known as _____________. A. locked-rotor torque B. pullout torque C. breakdown torque D. torque margin

Last Answer : Answer: A

Description : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the ... the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

Last Answer : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume ... the shaft. The accelerating torque in the generator in MNm at the time of fault will be 1.018 

Description : A 60 Hz, 4 pole turbo generator rated 100 MVA, 13.8 KV has an inertia constant of 10 MJ/MVA. Find the stored energy in the rotor at synchronous speed.  (A) 10 MJ (B) 100 J (C) 1000 J (D) 1000 MJ 

Last Answer : c

Description : How main generator earthing is done?

Last Answer : Generator neutral earthing is done through transformer and earth fault current is limited through resistance, which is connected across the secondary of the transformer. Generator 16.5 kV earth fault current is isolated from 220 kV through GT. Only star point of the generator is grounded. 

Description : The power factor of an AC generator operating singularly is determined by the __________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: A

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description : One method of testing for a reversed shunt field coil in a DC generator or motor is by connecting the field to a direct current source, at reduced field rated voltage, and test for ... placed near each field C. test lamp across adjacent fields D. copper jumper across the interpole connections

Last Answer : Answer: B

Description : if the rated voltage from the power lines is applied to the primary of a single-phase transformer which is operated on no-load, then

Last Answer : if the rated voltage from the power lines is applied to the primary of a single-phase transformer which is operated on no-load, then input voltage is sinusoidal and input current is non sinusoidal.

Description : Why the open circuit test on a transformer is conducted at rated voltage?

Last Answer : A:The open circuit on a transformer is conducted at a rated voltage because core loss depends upon the voltage. This open circuit test gives only core loss or iron loss of the transformer.

Description : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 ... load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

Last Answer : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/ ... MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be 36 

Description : A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is (A) 1500 r.p.m. (B) 1425 r.p.m. (C) 25 r.p.m. (D) 75 r.p.m.

Last Answer : (D) 75 r.p.m.

Description : Why we do 2 types of earthing on transformer i.e.: body earthing & neutral earthing, what is function. I am going to install a 5oo kva transformer & 380 kva DG set what should the earthing value?

Last Answer : The two types of earthing are Familiar as Equipment earthing and system earthing. In Equipment earthing: body (non conducting part) of the equipment should be earthed to safeguard the human ... earthing will be further classified into directly earthed, Impedance earthing, resistive (NGRs) earthing.

Description : The electrical schematic illustrated in figure A, depicts a/an _____________. EL-0059 A. autotransformer B. Delta Wye transformer C. primary EMF generator D. potential transformer

Last Answer : Answer: D

Description : A vessel is equipped with two ship's service generators. Generator #1 is rated at 900 kw and generator #2 is rated at 600 kw. During parallel operation, with a hotel load of 1,000 kw, what should be the kw load on generator #2? A. 100 kw B. 400 kw C. 500 kw D. 600 kw

Last Answer : Answer: B

Description : The magnetizing reactance of a 4 kV/ 400 V, 50 Hz single-phase transformer on low voltage side is 35 Ω. The magnetizing reactance on the high voltage side is (A) 0.35 Ω (B) 3.5 Ω (C) 350 Ω (D) 3500 Ω

Last Answer : 3500

Description : Why 6.6 kV transformer is resistance grounded by 10 ohms and current limited to 400 A?

Last Answer : a) To reduce burning and melting in faulted switchgear or machine. b) To reduce mechanical stresses in equipment. c) To reduce the electrical hazards by stray ground fault currents in the ground ... screen in 6.6 kV XLPE (cross-linked polyethylene). Therefore the cost of the cable decreases. 

Description : The voltage applied to the H.V. side of a transformer during S.C. test is 2% of the rated voltage. The core loss as the fraction of its rated core loss is (a) 4% (b) 0.4% (c) 0.25% (d) 0.04%

Last Answer : 0.04%

Description : Which of the following precautions should be taken when a blown fuse, rated at 10 amperes, is replaced? A. Short out the fuse before removing it from the circuit. B. Use needle-nose pliers to ... D. Fuses of 10 ampere rating and less are virtually harmless when energized and may be handled freely.

Last Answer : Answer: C

Description : An open shunt field in a direct current machine may be located by connecting the field circuit to an external power source, equal to the rated field voltage or less, and tested with a voltmeter from ... C. any suitable ground to any available line lead D. any field pole to each field coil lead

Last Answer : Answer: A

Description : An alternator is delivering rated current at rated voltage and 0.8 power-factor lagging case. If it is required to deliver rated current at rated voltage and 0.8 power-factor leading, the required excitation will be (A) less. (B) more. (C) more or less. (D) the same.

Last Answer : Ans: B Over excitation gives leading power factor and under excitation gives lagging p.f .

Description : As shown in the illustration, when the 'speed control' system is in 'SPLIT' _______________. EL-0096 A. Relays #1, #5 and #8 are not used B. the 'slew rated controller' is grounded through Relay ... E/P converters' are bypassed and air is fed directly to the governors via the 'load sharing valve'

Last Answer : Answer: C

Description : Why 100% winding protection is felt essential for main generator stator E/F protection? (Used in NAPS onwards?)  

Last Answer : At MAPS 4% of winding is not protected. Earlier felt that the Electro magnetic stress due high external fault currents near 4% of neutral may not be high to cause E/F here. But now felt that the mechanical stress can leads to E/F. 

Description : The voltage at the two ends of a transmission line are 132 KV and its reactance is 40 ohm. The Capacity of the line is (A) 435.6 MW (B) 217.8 MW (C) 251.5 MW (D) 500 MW

Last Answer : (A) 435.6 MW

Description : In a transformer the voltage regulation will be zero when it operates at (A) unity p.f. (B) leading p.f. (C) lagging p.f. (D) zero p.f. leading.

Last Answer : (B) leading p.f.

Description : A load with an impedance of 440 ohms is connected across the secondary of the transformer illustrated. If the input voltage is 110 VAC and the step-up ratio is 10 to 1, what will be the primary current? EL-0055 A. 2.5 amps B. 25 amps C. 250 amps D. current cannot be determined with information given

Last Answer : Answer: B

Description : The primary winding of a 220/6 V, 50 Hz transformer is energised from 110 V, 60 Hz supply. The secondary output voltage will be (A) 3.6 V. (B) 2.5 V. (C) 3.0 V. (D) 6.0 V.

Last Answer : (C) 3.0 V.

Description : If the no load voltage of a certain generator is 220V and the rated load voltage is 200V, then the voltage regulation is: a. 1% b. 10% c. 20V d. 9%

Last Answer : If the no load voltage of a certain generator is 220V and the rated load voltage is 200V, then the voltage regulation is: a. 1% b. 10% c. 20V d. 9%

Description : What is the minimum voltage required for starting of 6.6 kV motors?

Last Answer : Minimum 80% of rated voltage.

Description : The generation voltage is usually (A) between 11 KV and 33 KV. (B) between 132 KV and 400 KV. (C) between 400 KV and 700 KV. (D) None of the above.

Last Answer : (A) between 11 KV and 33 KV.

Description : Two paralleled alternators are operating near rated load. If one trips out mechanically, which of the listed actions should be taken FIRST? A. Restart the tripped machine immediately. B. Strip the board ... circuits. C. Start the emergency generator. D. Transfer all vital loads to the emergency bus.

Last Answer : Answer: B

Description : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is  (A) 1200 A (B) 3600 A (C) 35 kA (D) 104.8 kA

Last Answer : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is 35 kA 

Description : The number of insulator discs (each rated 11 kV) required in a suspension type insulator string of 220 kV line is 

Last Answer : The number of insulator discs (each rated 11kV) required in a suspension type insulator string of 220 kV line is 16

Description : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

Last Answer : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is 80 MJ

Description : A 3-phase circuit breaker is rated at 1250 A, 2000 MVA, 33 kV, 4s. Its making current capacity will be   (a) 35 kA (b) 89 kA (c) 79 kA (d) 69 kA

Last Answer : 89

Description : A load is connected to the secondary of the transformer illustrated and the current through the load is 10 amps. If the step-up ratio is 10 to 1 and the input voltage is 110 VAC, what will be the current flow through the primary? EL-0055 A. 1 amp B. 10 amps C. 100 amps D. 1000 amps

Last Answer : Answer: C

Description : Which of the following statements is true concerning stepdown transformer operation? A. The inductance on the primary side is the same as the inductance on the secondary side. B. The voltage to the primary ... . D. The voltage to the primary side is greater than the voltage from the secondary side.

Last Answer : Answer: D

Description : When a low input voltage is imparted to a device which then delivers a high output voltage, the device is known as a _____________. A. primary transformer B. secondary transformer C. stepdown transformer D. stepup transformer

Last Answer : Answer: D

Description : When a transformer is used to step down voltage, the low voltage winding is _____________. A. part of the core B. the primary coil C. not insulated D. the secondary coil

Last Answer : Answer: D

Description : Increasing the load to the secondary windings of a transformer will cause a/an ____________. A. decrease in the primary voltage B. increase in the primary voltage C. decrease in the primary current D. increase in the primary current

Last Answer : Answer: D

Description : In a three phase transformer, if the primary side is connected in star and secondary side is connected in delta, what is the angle difference between phase voltage in the two cases. (A) delta side lags by -30°. (B) star side lags by -30°. (C) delta side leads by 30°. (D) star side leads by -30°.

Last Answer : Ans: C This is vector group and has +30° displacement. Therefore, delta side leads by +30°.

Description : If a transformer primary is energised from a square wave voltage source, its output voltage will be (A) A square wave. (B) A sine wave. (C) A triangular wave. (D) A pulse wave.

Last Answer : (A) A square wave.

Last Answer : When a given transformer is run at its rated voltage but reduced frequency, its core flux density is increased.

Description : If a transformer is switched on to a voltage more than the rated voltage?

Last Answer : If a transformer is switched on to a voltage more than the rated voltage its power factor will deteriorate.