A 100 kVA, 415 V(line), star-connected synchronous machine generates rated open circuit voltage of 415 V at a field current of 15 A. The short circuit armature current at a field current of 10 A is equal to the rated armature current. The per unit saturated synchronous reactance is 

(A) 1.731 (B) 1.5 (C) 0.666 (D) 0.577

2 Answers

Answer :

A 100 kVA, 415 V(line), star-connected synchronous machine generates rated open circuit voltage of 415 V at a field current of 15 A. The short circuit armature current at a field current of 10 A is equal to the rated armature current. The per unit saturated synchronous reactance is 1.731

Answer :

0.6

Related questions

Description : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

Last Answer : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be 15.79 kA

Description : V - curve of synchronous machine shows the relation between?

Last Answer : V - curve of synchronous machine shows the relation between AC armature current and DC field current.

Description : A synchronous generator is feeding a zero power factor (lagging) load at rated current. The armature reaction is  (A) magnetizing (B) demagnetizing (C) cross-magnetizing (D) ineffective

Last Answer : A synchronous generator is feeding a zero power factor (lagging) load at rated current. The armature reaction is demagnetizing 

Last Answer : A synchronous machine with low value of short-circuit ratio has lower stability limit.

Description : An open shunt field in a direct current machine may be located by connecting the field circuit to an external power source, equal to the rated field voltage or less, and tested with a voltmeter from ... C. any suitable ground to any available line lead D. any field pole to each field coil lead

Last Answer : Answer: A

Description : A three phase, salient pole synchronous motor is connected to an infinite bus. It is operated at no load a normal excitation. The field excitation of the motor is first reduced to zero ... First increases and then decreases steeply (C) First decreases and then increases steeply (D) Remains constant

Last Answer : B

Description : The synchronous reactance of the synchronous machine is ______________. (A) Ratio between open circuit voltage and short circuit current at constant field current (B) Ratio between short circuit ... (D) Ratio between short circuit voltage and open circuit current at different field current

Last Answer : Ans. A The Synchronous reactance of a synchronous machine is a total steady state reactance, presented to applied voltage, when rotor is running synchronously without excitation. Therefore , XS = Ef / IS = Emf of OC for same If / short circuit current

Description : The locked rotor current in a 3-phase, star connected 15 , kW 4 , pole 230 V , 50 Hz induction motor at rated conditions is 50 A. Neglecting losses and magnetizing current, the approximate locked rotor line current drawn when the motor ... Hz supply is  (A) 58.5 A (B) 45.0 A (C) 42.7 A (D) 55.6 A

Last Answer : The locked rotor current in a 3-phase, star connected 15 , kW 4 , pole 230 V , 50 Hz induction motor at rated conditions is 50 A. Neglecting losses and magnetizing current, the approximate locked rotor line current drawn when the motor is connected to a 236 , V 57 Hz supply is 45.0 A 

Last Answer : Synchronsizing power of a synchronous machine is inversely proportional to the synchronous reactance.

Description : If we change the excitation of synchronous machine will it affect on power factor?

Last Answer : Yes, If we change the excitation of synchronous machine it will affect on power factor. If the synchronous motor is overexcited then it will have leading power factor and if the motor is underexcited then it will have lagging power factor.

Description : If we change the excitation of synchronous machine will it affect on motor speed?

Last Answer : No, If we change the excitation of synchronous machine it will not affect on motor speed.

Description : Why synchronous machine is called doubly excited machine?

Last Answer : Armature windings of synchronous machines either deliver 3 phase AC or absorb 3 phase AC source,  whereas field windings are energized from DC source. Thus due to presence of AC on armature and DC on field windings, synchronous machines are often referred as doubly excited machines.

Description : Which machine is the exciter of synchronous machine?

Last Answer : DC shunt machine is the exciter of synchronous machine.

Last Answer : The duration of sudden short-circuit test on a synchronous motor is usually about one second.

Last Answer : If the field winding of an unloaded salient pole synchronous motor is open circuited, the motor will stop.

Description : A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be  A) 100 MJ B) 400 MJ C) 800 MJ D) 12.5 MJ

Last Answer : 800

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : A hydraulic turbine having rated speed of 250 rpm is connected to a synchronous generator. In order to produce power at 50 Hz, the number of poles required in the generator are (A) 6 (B) 12 (C) 16 (D) 24

Last Answer : A hydraulic turbine having rated speed of 250 rpm is connected to a synchronous generator. In order to produce power at 50 Hz, the number of poles required in the generator are 24

Description : A two-phase generator is connected to two 90Ω load resistors. Each coil generates 120 V ac. The value of current flowing through the common neutral line will be: A. 1.33 A B. 1.88 A C. 2.66 A D. 1.77 A

Last Answer : A two-phase generator is connected to two 90Ω load resistors. Each coil generates 120 V ac. The value of current flowing through the common neutral line will be: 1.77 A

Description : Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is: A) 300 kVA B) 75 kVA C) 259 kVA D) 249 kVA

Last Answer : Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is:  259 kVA

Description : If an induction motor were to be operated at 90% rated voltage, _____________. A. there would be an increase in starting torque B. starting current would increase slightly C. synchronous speed would decrease slightly D. the slip would increase

Last Answer : Answer: D

Description : A building intended to be used for commercial purpose will be required to follow Energy conservation building code under Energy Conservation Act, 2001 provided its a) connected load is 120 kW and above b) ... and above c) connected load is100 kW and above or contract demand is 120 kVA and above

Last Answer : c) connected load is100 kW and above or contract demand is 120 kVA and above

Description : A 220/440 V, 50 Hz, 5 KVA, single phase transformer operates on 220V, 40Hz supply with secondary winding open circuited. Then (A) Both eddy current and hysteresis losses decreases. (B) Both ... same but hysteresis loss increases. (D) Eddy current loss increases but hysteresis loss remains the same.

Last Answer : (A) Both eddy current and hysteresis losses decreases.

Description : How do we select a cable for a machine as per standards? Is there is any standard to select a cable as per voltage, or as per KVA and as per amps ratings?

Last Answer : Cable size depends upon current carrying capacity and voltage to withstand, to select cable size we must have knowledge of load of machine and operating voltage

Description : Which of the following statements is true concerning a polyphase synchronous propulsion motor? A. The motor is started as an induction motor. B. Resistance is gradually added to the rotor circuit. C. ... is held below the rated current. D. The field winding is energized for starting purposes only.

Last Answer : Answer: A

Description : Why the open circuit test on a transformer is conducted at rated voltage?

Last Answer : A:The open circuit on a transformer is conducted at a rated voltage because core loss depends upon the voltage. This open circuit test gives only core loss or iron loss of the transformer.

Description : Why alternators are rated in KVA?

Last Answer : The KVA rating of ac machine depends on the power factor of the load. The power factor in turn depends on the operating conditions. The operating conditions differ from place to place. Therefore the KVA rating is specified for all ac machines.

Description : Why are Alternators rated in kVA and not in kW?

Last Answer : The continuous power rating of any machine is generally defined as the power the machine or apparatus can deliver for a continuous period so that the losses incurred in the machine gives rise to a ... generator , the Alternators have only their apparent power in VA/kVA/MVA as their power rating.

Description : why transformers are rated in kVA ?

Last Answer : A:Copper loss of a transformer depends on current and iron loss on voltage . Hence total losses depends on Volt- Ampere and not on the power factor. That is why the rating of transformers are in kVA and not in kW.

Description : [23] Transformers are rated in KVA instead of KW because A. load power factor is often not known B. KVA is fixed whereas KW depends on load power factor C. Total transformer loss depends on volt ampere D. It has become customary

Last Answer : C. Total transformer loss depends on volt ampere

Description : Why are generators rated in kVA not in kW ?

Last Answer : Because It's rating of generator kva is apparent power. Kw is active power which we use. And one is kvar reactive power.

Description : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

Last Answer : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is 80 MJ

Description : A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

Last Answer : 543A

Description : A 400V/100 V, 10 KVA two-winding transformer is reconnected as an auto-transformer across a suitable voltage source. The maximum rating of such an arrangement could be  A) 50 KVA B) 15 KVA C) 12.5 KVA D) 8.75 KVA

Last Answer : A 400V/100 V, 10 KVA two-winding transformer is reconnected as an auto-transformer across a suitable voltage source. The maximum rating of such an arrangement could be 50 KVA

Description : What is the maximum current allowed to be drawn from the secondary of a 2 KVA step-down transformer with a turns ratio of four to one if connected across a 440 volt line? A. 1.1 amps B. 4.5 amps C. 18.1 amps D. 22.7 amps

Last Answer : Answer: C

Description : What is the maximum allowable primary current of a 2 KVA step-down transformer with a four to one turns ratio if connected across a 440 volt line? A. 1.1 amps B. 4.5 amps C. 18.1 amps D. 27.7 amps

Last Answer : Answer: B

Description : The number of electrical degrees ‘passed through’ in one revolution of a 6-pole synchronous alternator is: A) 360 degree B) 720 degree C) 1080 degree D) 2160 degree

Last Answer : 1080

Description : The active power of a synchronous generator can be varied mainly by (a) changing field excitation (b) changing of prime mover speed (c) both (a) and (b) (d) none of the above

Last Answer : C

Description : A cylindrical rotor synchronous motor is switched on to the supply with its field windings shorted on themselves, the motor will .  A) Not start B) Start but will not run at synchronous speed C) Start as an induction motor and then run as a synchronous motor D) Start and run as a synchronous motor

Last Answer : A cylindrical rotor synchronous motor is switched on to the supply with its field windings shorted on themselves, the motor will Start but will not run at synchronous speed

Description : A stand alone engine driven synchronous generator is feeding a partly inductive load. A capacitor is now connected across the load to completely nullify the inductive current. For this operating condition.  ... left unaltered (D) the field current has to be reduced and fuel input left unaltered

Last Answer : A stand alone engine driven synchronous generator is feeding a partly inductive load. A capacitor is now connected across the load to completely nullify the inductive current. For this operating condition.  the field current has to be reduced and fuel input left unaltered

Description : In relation to the synchronous machines, which on of the following statements is false ?  (A) In salient pole machines, the direct-axis synchronous reactance is greater than the quadrature- ... motor represents the variation in the armature current with field excitation, at a given output power.

Last Answer : In relation to the synchronous machines, which on of the following statements is false ?  (A) In salient pole machines, the direct-axis synchronous reactance is greater than the quadrature- ... motor represents the variation in the armature current with field excitation, at a given output power.

Description : The angle δ in the swing equation of a synchronous generator is the  (A) angle between stator voltage and current (B) angular displacement of the rotor with respect to the stator (C) angular ... (D) angular displacement of an axis fixed to the rotor with respect to a synchronously rotating axis

Last Answer : The angle δ in the swing equation of a synchronous generator is the angular displacement of an axis fixed to the rotor with respect to a synchronously rotating axis

Description : For a fault at the terminals of a synchronous generator, the fault current is maximum for a  A) 3-phase fault B) 3-phase to ground fault C) Line to ground fault D) Line to line fault

Last Answer : C) Line to ground fault

Description : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

Last Answer : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is 0.01

Description : During hunting of synchronous motor  A) Negative phase sequence currents are generated B) Harmonics are developed in the armature current C) Damper bars develop torque D) Field excitation increases 

Last Answer : During hunting of synchronous motor Damper bars develop torque

Last Answer : Slip-rings in a synchronous motor carry direct current.

Last Answer : The efficiency of a properly designed synchronous motor will usually fall in range 85 to 95%.

Description : A synchronous motor has better power factor as compared to that of an equivalent induction motor. This is mainly because?

Last Answer : A synchronous motor has better power factor as compared to that of an equivalent induction motor. This is mainly because stator supply is not required to produce magnetic field.

Last Answer : A synchronous motor running with normal excitation adjusts to load increases essentially by increase in armature current.

Last Answer : The standard full-load power factor ratings for synchronous motors are unity or 0.8 leading.