A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of the alternator is connected to ground through an inductive reactor of j0.05 p.u. The per unit positive-, negative- and zero-sequence impedances of transmission line are j0.1, j0.1 and j0.3, respectively. All per unit values are based on the machine ratings. A solid ground fault occurs at one phase of the far end of the transmission line. The voltage of the alternator neutral with respect to ground during the fault is 

(A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

1 Answer

Answer :

A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of the alternator is connected to ground through an inductive reactor of j0.05 p.u. The per unit positive-, negative- and zero-sequence impedances of transmission line are j0.1, j0.1 and j0.3, respectively. All per unit values are based on the machine ratings. A solid ground fault occurs at one phase of the far end of the transmission line. The voltage of the alternator neutral with respect to ground during the fault is 642.2 V

Related questions

Description : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 ... load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

Last Answer : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/ ... MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be 36 

Description : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is  (A) 1200 A (B) 3600 A (C) 35 kA (D) 104.8 kA

Last Answer : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is 35 kA 

Description : A 800 kV transmission line is having per phase line inductance of 1.1 mH/km and per phase line capacitance of 11.68 nF/km. Ignoring the length of the line, its ideal power transfer capability in MW is (A) 1204 MW (B) 1504 MW (C) 2085 MW (D) 2606 MW

Last Answer : A 800 kV transmission line is having per phase line inductance of 1.1 mH/km and per phase line capacitance of 11.68 nF/km. Ignoring the length of the line, its ideal power transfer capability in MW is 2085 MW

Description : A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is (A) 2/15 p.u. (B) 5/6 p.u. (C) 1.0 p.u. (D) 1.2 p.u.

Last Answer : A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is 5/6 p.u.

Description : The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: A) 400 Mega Joule B) 400 Kilo Joule C) 25 Mega Joule D) 25 Kilo Joule

Last Answer : The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: 400 Mega Joule

Description : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the ... the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

Last Answer : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume ... the shaft. The accelerating torque in the generator in MNm at the time of fault will be 1.018 

Description : A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of

Last Answer : A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of 0.02 P.U

Description : The sending end and receiving end voltages of a three-phase transmission line are 10 kV/ph and 9.5 kV/ph, respectively. If the resistance drop is 150 V/ph and receiving end power factor is 0.8, the sending end power factor is (A) 0.745 lagging (B) 0.775 lagging (C) 0.8 lagging (D) 0.85 lagging

Last Answer : Vscos¢s-Vrcos¢r=IR

Description : The per unit impedance of a circuit element is 0.30. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be:  (A) 0.3 (B) 0.6 (C) 0.003 (D) 0.006 

Last Answer : 3

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be  A) 100 MJ B) 400 MJ C) 800 MJ D) 12.5 MJ

Last Answer : 800

Description : A 3-phase circuit breaker is rated at 1250 A, 2000 MVA, 33 kV, 4s. Its making current capacity will be   (a) 35 kA (b) 89 kA (c) 79 kA (d) 69 kA

Last Answer : 89

Description : An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately (A) P (B) 2P (C) P / 2 (D) P / 4

Last Answer : An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately P / 4

Description : A 100 km long transmission line is loaded at 110 kV.if the loss of line is 5 MW and the load is 150 MVA, the resistance of the line is?

Last Answer : P = I^2  *  R 5*10^6  = [(150*10^6) / (110*10^3)  *  R R = 2.7 ohm/phase

Description : A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 ohm/km. The static transmission capacity of the line, in MW, would be   (a) 240 (b) 132 (c) 416 (d) 720

Last Answer : A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 ohm/km. The static transmission capacity of the line, in MW, would be 240 

Description : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

Last Answer : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is 80 MJ

Description : The per unit impedance ofa circuit element is 0.15. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be?

Last Answer : The per unit impedance ofa circuit element is 0.15. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be 0.30.

Description : The p.u. parameter for a 500 MVA machine on its own base are: inertia, M = 20 p.u. ; reactance, X = 2 p.u. The p.u. values of inertia and reactance on 100 MVA common base, respectively, are (A) 4, 0.4 (B) 100, 10 (C) 4, 10 (D) 100, 0.4

Last Answer : The p.u. parameter for a 500 MVA machine on its own base are: inertia, M = 20 p.u. ; reactance, X = 2 p.u. The p.u. values of inertia and reactance on 100 MVA common base, respectively, are 100, 0.4

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer : A. As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer :  As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps

Description : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

Last Answer : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is 0.01

Description : A 60 Hz, 4 pole turbo generator rated 100 MVA, 13.8 KV has an inertia constant of 10 MJ/MVA. Find the stored energy in the rotor at synchronous speed.  (A) 10 MJ (B) 100 J (C) 1000 J (D) 1000 MJ 

Last Answer : c

Description : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per ... 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

Last Answer : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained ... load to increase the line-to-line voltage at the load terminals to 11 kV is -10.1 MVAR

Description : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

Last Answer : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is 1.316.

Description : An alternator has a phase sequence of RYB for its phase voltage. In case the direction of rotation of alternator is reversed, the phase sequence will become?

Last Answer : An alternator has a phase sequence of RYB for its phase voltage. In case the direction of rotation of alternator is reversed, the phase sequence will become RBY.

Description : The corona loss of a 3-phase transmission line is 100 kW at 60 kV/phase and 25 kW at 50 kV/phase. The disruptive critical voltage is (A) 40 kV (B) 43.6 kV (C) 49.6 kV (D) 50 kV

Last Answer : The corona loss of a 3-phase transmission line is 100 kW at 60 kV/phase and 25 kW at 50 kV/phase. The disruptive critical voltage is 40 kV

Description : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

Last Answer : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be 15.79 kA

Description : In a certain three -wire Y -connected generator, the phase voltages are 2 kV. The magnitudes of the line voltages will be: A. 2,000 V B. 6,000 V C. 666 V D. 3,464 V

Last Answer : In a certain three -wire Y -connected generator, the phase voltages are 2 kV. The magnitudes of the line voltages will be: 3,464 V

Description : A voltage of 1000 kV is applied to an overhead line with its receiving end open. If the surge impedance of the line is 500 ohm, then the total surge power in the line ill

Last Answer : A voltage of 1000 kV is applied to an overhead line with its receiving end open. If the surge impedance of the line is 500 ohm, then the total surge power in the line ill 2000 MW .

Description : The X:R ratio of 220 kV line as compared to 400 kV line is?

Last Answer : The X:R ratio of 220 kV line as compared to 400 kV line is smaller.

Description : A three phase overhead transmission line has its conductors horizontally spaced with spacing between adjacent conductors equal to 'd'. if now the conductors of the line are rearranged to form and the equilateral triangle of sides equal to 'd' then?

Last Answer : A three-phase overhead transmission line has its conductors horizontally spaced with spacing between adjacent conductors equal to 'd'. if now the conductors of the line are rearranged to form and an equilateral triangle of sides equal to 'd' then average capacitance and inductance will increase.

Description :  A single-phase transmission line of impedance j 0.8 ohm supplies a resistive load of 500 A at 300 V. The sending end power factor is?

Last Answer :  A single-phase transmission line of impedance j 0.8 ohm supplies a resistive load of 500 A at 300 V. The sending end power factor is 0.6 lagging.

Description : Which of the following statements is incorrect ? (a) Lightning arrestors are used before the switchgear (b) Shunt reactors are used as compensation reactors (c) The peak short current is (1.8 xV2) ... component (d) The MVA at fault is equal to base MVA divided by per unit equivalent fault reactance

Last Answer : (a) Lightning arrestors are used before the switchgear

Description : at the terminal of a three-phase 6.6Kv alternator a load R=200 ohm is connected between two-phase and the third phase is opened. Z1=z2=5 ohm Zo=2 find out the fault current .

Last Answer : 32A

Description : For 11 kV line the capacitance per km per phase will be of the order of:  (A) 1 Farad (B) 0.1 Farad (C) 0.01 Farad (D) 0.01 microF

Last Answer : For 11 kV line the capacitance per km per phase will be of the order of: 0.01 Farad

Description : The voltage at the two ends of a transmission line are 132 KV and its reactance is 40 ohm. The Capacity of the line is (A) 435.6 MW (B) 217.8 MW (C) 251.5 MW (D) 500 MW

Last Answer : (A) 435.6 MW

Description : A alternator is delivering power to a balanced load at unit power factor. The phase angle between the line voltage and the line current is? (A) 90° (B) 60° (C) 30° (D) 0° 

Last Answer : A alternator is delivering power to a balanced load at unit power factor. The phase angle between the line voltage and the line current is 30°

Description : What is the phase coefficient in radians per unit length of a transmission line at the frequency of 10 MHz if the velocity of propagation is 2.5x108 m/s? A. 0.25 B. 2.5 C. 0.35 D. 3.5

Last Answer : A. 0.25

Description : The spacing between phase conductors of a 220 kV line is approximately equal to (a) 2 m (b) 3.5 m (c) 6 m (d) 8.5 m

Last Answer : (c) 6 m

Description : The sequence components of current of a single-phase load connected to a 3-phase system are (A) equal positive and negative sequence components (B) equal positive, negative and zero sequence components (C) vector sum of sequence currents is zero (D) algebraic sum of sequence currents is zero

Last Answer : The sequence components of current of a single-phase load connected to a 3-phase system are equal positive, negative and zero sequence components

Description : For transmission of power over a distance of 500 km, the transmission voltage should be in the range (a) 150 to 220 kV (b) 100 to 120 kV (c) 60 to 100 kV (d) 20 to 50 kV

Last Answer : (a) 150 to 220 kV

Description : Transmission voltage of ll kV is normally used for distances upto (a) 20—25 km (b) 40—50 km (c) 60—70 km (d) 80—100 km

Last Answer : (a) 20—25 km

Description : If voltage at the two ends of a transmission line is 132 kV and its reactance is 40 Ohms, the capacity of the line will be: (A) 435.6 MW (B) 217.8 MW(C) 251.5 MW (D) 500 MW

Last Answer : If voltage at the two ends of a transmission line is 132 kV and its reactance is 40 Ohms, the capacity of the line will be: 435.6 MW

Description : How many insulator disc used for 33 kV transmission voltage line?

Last Answer : 5,As 33kv is Vrms

Description : Why core balance CT is preferred over residual connected CT’s to sense earth fault in 6.6 kV feeders?

Last Answer : a) To avoid relay mal-operation due to CT saturation b) Better sensitivity is got. c) High pickup and TMS avoided in IDMT earth fault relay. 

Description : Choose two appropriate auxiliary components of a HVDC transmission system from the following P. D.C line inductor Q. A.C line inductor R. Reactive power sources S. Distance relays on D.C line T. Series capacitance on A.C. line  (A) P and Q (B) P and R (C) Q and S (D) S and T

Last Answer : Choose two appropriate auxiliary components of a HVDC transmission system from the following P. D.C line inductor Q. A.C line inductor R. Reactive power sources S. Distance relays on D.C line T. Series capacitance on A.C. line  (A) P and Q (B) P and R (C) Q and S (D) S and T

Description : The transmission line distance protection relay having the property of being inherently directional is (A) impedance relay (B) MHO relay (C) OHM relay (D) reactance relay

Last Answer : The transmission line distance protection relay having the property of being inherently directional is MHO relay

Description : An HVDC link consist of rectifier, inverter transmission line and other equipments. Which one of the following is true for this link ?  (A) The transmission line produces/ supplies ... ) Both the converters (rectifier and inverter) consume reactive power from the respective connected AC systems

Last Answer : An HVDC link consist of rectifier, inverter transmission line and other equipments. Which one of the following is true for this link ?  (A) The transmission line produces/ supplies ... ) Both the converters (rectifier and inverter) consume reactive power from the respective connected AC systems

Description : A loss less transmission line having Surge Impedance Loading (SIL) of 2280 MW is provided with a uniformly distributed series capacitive compensation of 30%. Then, SIL of the compensated transmission line will be (A) 1835 MW (B) 2280 MW (C) 2725 MW (D) 3257 MW

Last Answer : A loss less transmission line having Surge Impedance Loading (SIL) of 2280 MW is provided with a uniformly distributed series capacitive compensation of 30%. Then, SIL of the compensated transmission line will be 2280 MW

Description : For enhancing the power transmission in along EHV transmission line, the most preferred method is to connect a  (A) Series inductive compensator in the line (B) Shunt inductive compensator at the ... (C) Series capacitive compensator in the line (D) Shunt capacitive compensator at the sending end

Last Answer : For enhancing the power transmission in along EHV transmission line, the most preferred method is to connect a Series capacitive compensator in the line