Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is: A) 300 kVA B) 75 kVA C) 259 kVA D) 249 kVA

1 Answer

Answer :

Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is:  259 kVA

Related questions

Description : A three-phase transformer, connected in star-delta, is composed of three single-phase transformers, each rated 127/ 13.2 kV. The line-to-line voltage ratio for the three-phase transformer is: A) 220 / 13.2 kV B) 127 / 13.2 kV C) 127 / 220 kV D) 220 / 220 kV

Last Answer : A three-phase transformer, connected in star-delta, is composed of three single-phase transformers, each rated 127/ 13.2 kV. The line-to-line voltage ratio for the three-phase transformer is: 220 / 13.2 kV 

Description : [23] Transformers are rated in KVA instead of KW because A. load power factor is often not known B. KVA is fixed whereas KW depends on load power factor C. Total transformer loss depends on volt ampere D. It has become customary

Last Answer : C. Total transformer loss depends on volt ampere

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : What is the maximum current allowed to be drawn from the secondary of a 2 KVA step-down transformer with a turns ratio of four to one if connected across a 440 volt line? A. 1.1 amps B. 4.5 amps C. 18.1 amps D. 22.7 amps

Last Answer : Answer: C

Description : What is the maximum allowable primary current of a 2 KVA step-down transformer with a four to one turns ratio if connected across a 440 volt line? A. 1.1 amps B. 4.5 amps C. 18.1 amps D. 27.7 amps

Last Answer : Answer: B

Description : Ships’ generators produce 450-volt, three-phase, ac power; however, most equipment uses 117-volt, single-phase power What transformers and connections are used to convert 450- volt, threephase power to 117-volt, single-phase power?

Last Answer : A method of generating oscillations, a method of turning the oscillations on and off (keying), and an antenna to radiate the energy.

Description : Consider the following statements regarding three-phase transformers in Open -Delta (V -V) connections :  1. Being a temporary remedy when one transformer forms of Delta -Delta system is &imaged, and removed from service.  ... and 2 only (b) 1 and 3 only (c) 2 and 3 only (d) 1, 2 and 3

Last Answer : Consider the following statements regarding three-phase transformers in Open -Delta (V -V) connections :  1. Being a temporary remedy when one transformer forms of Delta -Delta system is &imaged, and removed from service.  ... and 2 only (b) 1 and 3 only (c) 2 and 3 only (d) 1, 2 and 3

Description : [75] Two transformers are connected in parallel. These transformers do not have equal percentage impedance which results A. Short-circuiting of the secondaries B. Power factor of one of the ... have negligible core losses D. Loading of the transformers not in proportion to their kVA ratings.

Last Answer : D. Loading of the transformers not in proportion to their kVA ratings

Description : The magnetizing reactance of a 4 kV/ 400 V, 50 Hz single-phase transformer on low voltage side is 35 Ω. The magnetizing reactance on the high voltage side is (A) 0.35 Ω (B) 3.5 Ω (C) 350 Ω (D) 3500 Ω

Last Answer : 3500

Description : A single phase transformer is designed to operate from 50 Hz, 1100 V supply and to have an output voltage of 240 V at no load. The core has mean area of 30 cm2 and the flux density has not to exceed 1.3T. The number of secondary turns will be (a) 1270 (b) 1017 (c) 768 (d) 277  

Last Answer : E2=e2=4.44*flux*N2*f=240 V Flux=Flux density* Area Area=30 cm2  =30*10-4 m2 Flux= 1.3*30*10-4  Wb=39*10-4 Wb E=240= 4.44*39*10-4 *N2*50      N2=277.

Description : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is  (A) 50.0% (B) 70.7% (C) 141.4% (D) 200.0%

Last Answer : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is 70.7%

Description : A 220/440 V, 50 Hz, 5 KVA, single phase transformer operates on 220V, 40Hz supply with secondary winding open circuited. Then (A) Both eddy current and hysteresis losses decreases. (B) Both ... same but hysteresis loss increases. (D) Eddy current loss increases but hysteresis loss remains the same.

Last Answer : (A) Both eddy current and hysteresis losses decreases.

Description : In a three-phase, open-delta connected transformer, the line current is equal to _____________. A. the phase current B. three times the phase current C. the sum of any two phase currents D. the difference of any two phase currents

Last Answer : Answer: A

Description : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is 500 kVA and its pu ... its pu leakage impedance is  (A) 0.20 (B) 0.10 (C) 0.05 (D) 0.025

Last Answer : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is ... .05 pu. If the rating of second transformer is 250 kVA, its pu leakage impedance is 0.10

Description : Can Transformers be Reconnected as Autotransformers to Increase Their KVA Rating?

Last Answer : ANSWER: Several of standard single phase transformers can be connected as autotransformers. The KVA capacity will be greatly increased when used as an Autotransformer, in comparison to the ... This voltage is normally used for operating fluorescent lamps or similar devices requiring 277 volts

Description : why transformers are rated in kVA ?

Last Answer : A:Copper loss of a transformer depends on current and iron loss on voltage . Hence total losses depends on Volt- Ampere and not on the power factor. That is why the rating of transformers are in kVA and not in kW.

Description : 47 Cross over windings are used in A. Low voltage side of high kVA rating transformers B. Current transformers C. High voltage side of high kVA rating transformers D. High voltage side of low kVA rating transformers

Last Answer : D. High voltage side of low kVA rating transformers

Description : 4 Helical coils can be used on A. Low voltage side of high kVA transformers B. High frequency transformers C. High voltage side of small capacity transformers D. High voltage side of high kVA rating transformers

Last Answer : A) low voltage side of high KVA transformer

Description : The heat dissipating capability of transformers of ratings higher than 30 kVA in increased by providing which of the following ? (a) Corrugations (b) Fins (c) Tubes (d) Radiator tanks (e) All of the above

Last Answer : (e) All of the above

Description : Power transformers have rating (a) equal to 50 kVA (6) equal to 100 kVA (c) above 200 kVA (d) none of the above

Last Answer : (c) above 200 kVA

Description : A 100 kVA, 415 V(line), star-connected synchronous machine generates rated open circuit voltage of 415 V at a field current of 15 A. The short circuit armature current at a field current of 10 A is equal to the ... unit saturated synchronous reactance is  (A) 1.731 (B) 1.5 (C) 0.666 (D) 0.577

Last Answer : 0.6

Description : Figure 'D' of the diagram shown in the illustration has a turns ratio of four to one. If a three-phase 440 volt supply is connected to terminals 'A-B-C', what voltage should develop across terminals 'a-b-c'? EL-0084 A. 64 volts B. 110 volts C. 190 volts D. 762 volts

Last Answer : Answer: A

Description : Figure 'C' of the diagram shown in the illustration has a turns ratio of four to one. If a three-phase 440 volt supply is connected to terminals 'A-B-C', what voltage should develop across terminals 'a-b-c'? EL-0084 A. 64 volts B. 110 volts C. 190 volts D. 762 volts

Last Answer : Answer: C

Description : Figure 'B' of the diagram shown in the illustration has a turns ratio of four to one. If a three-phase 440 volt supply is connected to terminals 'A-B-C', what voltage should develop across terminals 'a-b-c'? EL-0084 A. 64 volts B. 110 volts C. 190 volts D. 762 volts

Last Answer : Answer: B

Description : Figure 'A' of the diagram shown in the illustration has a turns ratio of four to one. If a three-phase 440 volt supply is connected to terminals 'A-B-C', what voltage should develop across terminals 'a-b-c'? EL-0084 A. 64 volts B. 110 volts C. 190 volts D. 762 volts

Last Answer : Answer: B

Description : A single-phase, 50 kVA, 250 V/500 V two winding transformer has an efficiency of 95% at full load, unity power factor. If it is re-configured as a 500 V/750 V auto-transformer, its efficiency at its new rated load at unity power factor will be  (A) 95.752% (B) 97.851% (C) 98.276% (D) 99.241%

Last Answer : A

Description : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: (A) both the eddy current and the hysteresis losses will decrease ... losses will increase (D) eddy current losses will increase but the hysteresis losses will remain the same

Last Answer : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: both the eddy current and the hysteresis losses will decrease

Description : A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

Last Answer : 543A

Description : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of   (a) 250A (b) 50 A (c) 150 A (d) 350 A 

Last Answer : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of 250A

Description : In a three phase transformer, if the primary side is connected in star and secondary side is connected in delta, what is the angle difference between phase voltage in the two cases. (A) delta side lags by -30°. (B) star side lags by -30°. (C) delta side leads by 30°. (D) star side leads by -30°.

Last Answer : Ans: C This is vector group and has +30° displacement. Therefore, delta side leads by +30°.

Description : Which of the listed figures shown in the illustration represents devices connected in a three-phase delta-delta arrangement? EL-0084 A. A B. B C. C D. D

Last Answer : Answer: A

Description : Which of the listed figures shown in the illustration represents devices connected in a three-phase delta-wye arrangement? EL-0084 A. A B. B C. C D. D

Last Answer : Answer: C

Description : Which of the listed figures shown in the illustration represents devices connected in a three-phase wye-delta arrangement? EL-0084 A. A B. B C. C D. D

Last Answer : Answer: D

Description : Three equal impedances are first connected in delta across a 3 -phase balanced supply. If the same impedances are connected in star across the same supply then,

Last Answer : A

Description : Explain Three Phase Bidirectional Delta Connected Controller.

Last Answer : Three Phase Bidirectional Delta Connected Controller:

Description : The electrical schematic shown in the illustration indicates the lighting feeder circuit is _____________. EL-0014 A. three phase, 450 volt, and 60 cycle B. three phase, 120 volt, and 60 cycle C. single phase, 120 volt, and 60 cycle D. not specified

Last Answer : Answer: A

Description : Can Single Phase Transformers be used for Three Phase applications?

Last Answer : A. Yes. Three phase transformers are sometimes not readily available whereas single phase transformers can generally be found in stock. Three single phase transformers can be used in delta connected primary and ... K VA single phase transformers can be used to accommodate a 30 KVA three phase load.

Description : Can Transformers develop Three Phase power from a Single Phase source?

Last Answer : A. NO. Phase converters or phase shifting devices such as reactors and capacitors are required to convert single phase power to three phase.

Description : Can Transformers develop Three Phase power from a Single Phase source?

Last Answer : No. Phase converters or phase shifting devices such as reactors and capacitors are required to convert single phase power to three phase. 

Description : An additional condition for parallel operation of three-phase transformers over single-phase transformers is that

Last Answer : An additional condition for parallel operation of three-phase transformers over single-phase transformers is that the transformers should belong to the same vector group

Description : KVA of an Auto-transformer of V1/V2 = 220/150 for a load of 100KVA is: a. 100KVA b. 50KVA c. 33.3KVA d. 20KVA 

Last Answer : KVA of an Auto-transformer of V1/V2 = 220/150 for a load of 100KVA is: a. 100KVA b. 50KVA c. 33.3KVA d. 20KVA 

Description : In testing a three-phase delta winding for an open circuit using a megohmmeter, you must ______________. A. test each phase with all connections intact B. measure the voltage across the open ... groups to avoid short circuiting D. open the delta-connections to avoid shunting the phase being tested

Last Answer : Answer: D

Description : Which of the following statements regarding cash flow patterns (for time periods 0, 1, 2, 3, and 4) is correct? A. The sequence of -Rs.100, Rs.50, Rs.40, Rs.60, and Rs.50 is a non-conventional cash ... -Rs.50, Rs.50, Rs.70, Rs.60, and -Rs.150 potentially has at most two internal rates of return.

Last Answer : B. The sequence of -Rs.100, Rs.600, -Rs.1,100, Rs.600, and Rs.20 potentially has a maximum of two internal rates of return.

Description : The 28 days cube strength of mass concrete using aggregates of maximum size 5 cm for gravity dams should be (A) Between 150 to 300 kg/cm2 (B) Between 350 to 600 kg/cm2 (C) Between 150 to 500 kg/cm2 (D) Below 200 kg/cm2

Last Answer : Answer: Option D

Description : A cantilever beam of span 3m carries a point load 100 N at the free end. The maximum B.M in the beam will be (a) 100 N-m (b) 300 N-m (c) 150 N-m (d) 600 N-m

Last Answer : (b) 300 N-m

Description : A cantilever beam of length of 2m carries a U.D.L. of 150 N/m over its whole span. The maximum shear force in the beam will be (a) 150 N (b) 300 N (c) 150 N-m (d) 600 N-m

Last Answer : (b) 300 N

Description : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Last Answer : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Description : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be :  (A) 34.64 kVA (B) 75 kVA (C) 20 kVA (D) None of the above

Last Answer : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be : 34.64 kVA

Description : One important difference between wye-connected and delta-connected generators is that delta connections have ____________. A. line voltages equal to the vector sum of the phase voltages B. phase voltages 90° ... C. line current equal to the phase current D. line voltage equal to the phase voltage

Last Answer : Answer: D

Description : What is the impedance per phase of delta connected motor?

Last Answer : 1.5 times the total impedance.