A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of 

 (a) 250A (b) 50 A (c) 150 A (d) 350 A 

1 Answer

Answer :

A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of 250A

Related questions

Description : A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

Last Answer : 543A

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : The low voltage winding of a 400/230 V, 1-phase, 50 Hz transformer is to be connected to a 25 Hz, the supply voltage should be

Last Answer : The low voltage winding of a 400/230 V, 1-phase, 50 Hz transformer is to be connected to a 25 Hz, the supply voltage should be 115 V.

Description : A nichrome heating element connected to a 200 V supply draws an intial current of 2.2 A which settles down after a few seconds to a steady value of 2.

Last Answer : A nichrome heating element connected to a 200 V supply draws an intial current of 2.2 A which settles down after a ... is `1.7xx10^(-4) "per"^(@)C`.

Description : A 220/440 V, 50 Hz, 5 KVA, single phase transformer operates on 220V, 40Hz supply with secondary winding open circuited. Then (A) Both eddy current and hysteresis losses decreases. (B) Both ... same but hysteresis loss increases. (D) Eddy current loss increases but hysteresis loss remains the same.

Last Answer : (A) Both eddy current and hysteresis losses decreases.

Description : A single-phase, 50 kVA, 250 V/500 V two winding transformer has an efficiency of 95% at full load, unity power factor. If it is re-configured as a 500 V/750 V auto-transformer, its efficiency at its new rated load at unity power factor will be  (A) 95.752% (B) 97.851% (C) 98.276% (D) 99.241%

Last Answer : A

Description : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: (A) both the eddy current and the hysteresis losses will decrease ... losses will increase (D) eddy current losses will increase but the hysteresis losses will remain the same

Last Answer : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: both the eddy current and the hysteresis losses will decrease

Description : A 400/200 volts transformer has pu impedance of 0.05. The HV side voltage required to circulate full load current during short circuit test is

Last Answer : A 400/200 volts transformer has pu impedance of 0.05. The HV side voltage required to circulate full load current during short circuit test is 20 V

Description : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Last Answer : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Description :  A single-phase transmission line of impedance j 0.8 ohm supplies a resistive load of 500 A at 300 V. The sending end power factor is?

Last Answer :  A single-phase transmission line of impedance j 0.8 ohm supplies a resistive load of 500 A at 300 V. The sending end power factor is 0.6 lagging.

Description : The magnetizing reactance of a 4 kV/ 400 V, 50 Hz single-phase transformer on low voltage side is 35 Ω. The magnetizing reactance on the high voltage side is (A) 0.35 Ω (B) 3.5 Ω (C) 350 Ω (D) 3500 Ω

Last Answer : 3500

Description : A 230 V, 50 Hz phase controlled single-phase full-controlled SCR bridge converter draws 15 A constant dc current. If the source inductance is 3 mH, the drop in dc output voltage is (A) 4.5 V (B) 6.75 V (C) 9 V (D) 13.5 V

Last Answer : A 230 V, 50 Hz phase controlled single-phase full-controlled SCR bridge converter draws 15 A constant dc current. If the source inductance is 3 mH, the drop in dc output voltage is 9 V

Description : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is

Last Answer : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is 0.707

Description : The hysteresis and eddy current losses of a single phase transformer working on 200 V, 50 Hz supply are Ph and Pe respectively. The percentage decrease in these when operated on a 160 V, 40 Hz supply are   (a) 32, 36 (b) 20, 36 (c) 25, 50 (d) 40, 80 

Last Answer : The hysteresis and eddy current losses of a single phase transformer working on 200 V, 50 Hz supply are Ph and Pe respectively. The percentage decrease in these when operated on a 160 V, 40 Hz supply are 20, 36

Description : A 400V/100 V, 10 KVA two-winding transformer is reconnected as an auto-transformer across a suitable voltage source. The maximum rating of such an arrangement could be  A) 50 KVA B) 15 KVA C) 12.5 KVA D) 8.75 KVA

Last Answer : A 400V/100 V, 10 KVA two-winding transformer is reconnected as an auto-transformer across a suitable voltage source. The maximum rating of such an arrangement could be 50 KVA

Description : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he

Last Answer : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he 0.52

Description : One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

Last Answer : 100

Description : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is  (A) 50.0% (B) 70.7% (C) 141.4% (D) 200.0%

Last Answer : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is 70.7%

Description : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be :  (A) 34.64 kVA (B) 75 kVA (C) 20 kVA (D) None of the above

Last Answer : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be : 34.64 kVA

Description : Calorific value of gobar gas (containing CH4 = 60% , H2 = 10% ; CO2 = 30%) may be about __________ Kcal/Nm3 . (A) 1,800 (B) 3,200 (C) 5,400 (D) 10,200

Last Answer : (C) 5,400

Description : A final amplifier of a radio transmitter draws 250 mA of plate current when the plate supply voltage is 1400 volts. If the plate circuit efficiency is 80% and the transmitter is connected to an antenna having a feed impedance of 70 ohms, ... at the feed-point? A. 4.0 A B. 2.2 A C. 1.25 A D. 2.0 A

Last Answer : D. 2.0 A

Description : [75] Two transformers are connected in parallel. These transformers do not have equal percentage impedance which results A. Short-circuiting of the secondaries B. Power factor of one of the ... have negligible core losses D. Loading of the transformers not in proportion to their kVA ratings.

Last Answer : D. Loading of the transformers not in proportion to their kVA ratings

Description : A load of 200 ohm is used to match 300 ohm transmission line to achieve SWR=1. Find out the required characteristic impedance of a quarter of a quarter wave transformer connected directly to the load.

Last Answer : Solution :

Description : Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is: A) 300 kVA B) 75 kVA C) 259 kVA D) 249 kVA

Last Answer : Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is:  259 kVA

Description : The voltage of the single phase supply to residential consumers is (a) 110 V (b) 210 V (c) 230 V (d) 400 V

Last Answer : (c) 230 V

Description : The voltage of the single phase supply to residential consumers is (a) 110 V (b) 210 V (c) 230 V (d) 400 V

Last Answer : (c) 230 V

Description : The meter constant of a single-phase 230 V induction watt hour meter is 400 revolutions per kWh. The speed of the meter disc for a current of 10 A of 0.9 pf lagging will be

Last Answer : The meter constant of a single-phase 230 V induction watt hour meter is 400 revolutions per kWh. The speed of the meter disc for a current of 10 A of 0.9 pf lagging will be 13.80 rpm

Description : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

Last Answer : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is 1.316.

Description : The conductor of a 10 km long, single phase, two wire line are separated by a distance of 1.5 m. The diameter of each conductor is 1 cm, If the conductors are of copper, the inductance of the circuit is

Last Answer : The conductor of a 10 km long, single phase, two wire line are separated by a distance of 1.5 m. The diameter of each conductor is 1 cm, If the conductors are of copper, the inductance of the circuit is 23.8 mH.

Description : A single phase transformer is designed to operate from 50 Hz, 1100 V supply and to have an output voltage of 240 V at no load. The core has mean area of 30 cm2 and the flux density has not to exceed 1.3T. The number of secondary turns will be (a) 1270 (b) 1017 (c) 768 (d) 277  

Last Answer : E2=e2=4.44*flux*N2*f=240 V Flux=Flux density* Area Area=30 cm2  =30*10-4 m2 Flux= 1.3*30*10-4  Wb=39*10-4 Wb E=240= 4.44*39*10-4 *N2*50      N2=277.

Description : A single-phase, 230 V, 50 Hz ac mains fed step down transformer (4:1) is supplying power to a half-wave uncontrolled ac-dc converter used for charging a battery (12 V dc) with the series current limiting resistor being 19.04 Ohm. The charging current is  (A) 2.43 A (B) 1.65 A (C) 1.22 A (D) 1.0 A

Last Answer : A single-phase, 230 V, 50 Hz ac mains fed step down transformer (4:1) is supplying power to a half-wave uncontrolled ac-dc converter used for charging a battery (12 V dc) with the series current limiting resistor being 19.04 Ohm. The charging current is 1.0 A

Description : A 230 V/460 V single-phase transformer operating at 20 A and unity power factor has primary referred resistance of 0.2 Ω and reactance of 0.5 Ω. The approximate primary induced emf is (A) 216 V (B) 226 V (C) 234 V (D) 236 V

Last Answer : A 230 V/460 V single-phase transformer operating at 20 A and unity power factor has primary referred resistance of 0.2 Ω and reactance of 0.5 Ω. The approximate primary induced emf is 226 V

Description : The primary turns of a 444 V/222 V, 50 Hz single-phase transformer with a core cross-sectional area of 100 cm2, and a maximum flux density of 1.0 T is (A) 100 (B) 200 (C) 222 (D) 400

Last Answer : The primary turns of a 444 V/222 V, 50 Hz single-phase transformer with a core cross-sectional area of 100 cm2, and a maximum flux density of 1.0 T is 200

Description : What is the power factor when a single phase watt meter operating on 200 V and 5 A for 5 hours makes 2016 revolutions and the meter constant in revolution is 420? A) 0.04 B) 1.04 C) 0.96 D) None of these

Last Answer : What is the power factor when a single phase watt meter operating on 200 V and 5 A for 5 hours makes 2016 revolutions and the meter constant in revolution is 420? A) 0.04 B) 1.04 C) 0.96 D) None of these

Description : A single-phase ac voltage source has 200 V rms and a system connected consumes an active power of 300 W. What is the reactive power consumed by the system if 2.5 A rms current is drawn ?  (a) 100 VAR (b) 200 VAR (c) 300 VAR (d) 400 VAR

Last Answer : A single-phase ac voltage source has 200 V rms and a system connected consumes an active power of 300 W. What is the reactive power consumed by the system if 2.5 A rms current is drawn ? 400 VAR

Description : A loss less transmission line having Surge Impedance Loading (SIL) of 2280 MW is provided with a uniformly distributed series capacitive compensation of 30%. Then, SIL of the compensated transmission line will be (A) 1835 MW (B) 2280 MW (C) 2725 MW (D) 3257 MW

Last Answer : A loss less transmission line having Surge Impedance Loading (SIL) of 2280 MW is provided with a uniformly distributed series capacitive compensation of 30%. Then, SIL of the compensated transmission line will be 2280 MW

Description : A loss less line terminated with its surge impedance has

Last Answer : A loss less line terminated with its surge impedance has flat voltage profile.

Description : A lossless radial transmission line with surge impedance loading?

Last Answer : A lossless radial transmission line with surge impedance loading takes negative VAr at sending end and zero VAr at receiving end.

Description : The per unit impedance ofa circuit element is 0.15. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be?

Last Answer : The per unit impedance ofa circuit element is 0.15. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be 0.30.

Description : The impedance of a circuit is given by z=3+j4. Its conductance will be?

Last Answer : The impedance of a circuit is given by z=3+j4. Its conductance will be 3/25.

Description : A cylinder rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load voltage is 1.5 pu and the infinite bus voltage is 1 pu. The ... fault at the generator terminal is  (A) 53.5 (B) 60.2 (C) 70.8 (D) 79.6

Last Answer : A cylinder rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load voltage is 1.5 pu and the ... clearing angle, in degrees, for a three-phase dead short circuit fault at the generator terminal is 79.6

Description : The steady state stability of the power system can be improved by (A) using machines of high impedance (B) connecting transmission lines in series. (C) connecting lines in parallel. (D) reducing, the excitation of the machines.

Last Answer : The steady state stability of the power system can be improved by connecting lines in parallel.

Description : The steady state stability limit as compared to the transient state stability limit is always

Last Answer : The steady state stability limit as compared to the transient state stability limit is always Greater

Description : CG Co manufactures a single product T. Budgeted production output of product T during June is  200 units. Each unit of product T requires 6 labour hours for completion and CG Co anticipates 20 per  cent idle time. Labour is paid at ... for March is (a) Rs 6,720 (b) 8,400 (c) 10,080 (d) 10,500

Last Answer : (d) 10,500

Description : A large transformer operating at no load draws an exciting current Io of 5A, when the primary is connected to a 120 V, 60 Hz source. From a wattmeter test, it is known that iron losses are equal to 180 W. Calculate ... power absorbed by the core.  (A) 600 var (B) 572 var (C) 180 var (D) 360 var 

Last Answer : 572var

Description : What is the maximum current allowed to be drawn from the secondary of a 2 KVA step-down transformer with a turns ratio of four to one if connected across a 440 volt line? A. 1.1 amps B. 4.5 amps C. 18.1 amps D. 22.7 amps

Last Answer : Answer: C

Description : What is the maximum allowable primary current of a 2 KVA step-down transformer with a four to one turns ratio if connected across a 440 volt line? A. 1.1 amps B. 4.5 amps C. 18.1 amps D. 27.7 amps

Last Answer : Answer: B

Description : Why we do 2 types of earthing on transformer i.e.: body earthing & neutral earthing, what is function. I am going to install a 5oo kva transformer & 380 kva DG set what should the earthing value?

Last Answer : The two types of earthing are Familiar as Equipment earthing and system earthing. In Equipment earthing: body (non conducting part) of the equipment should be earthed to safeguard the human ... earthing will be further classified into directly earthed, Impedance earthing, resistive (NGRs) earthing.

Description : For which of the following ratings of the transformer differential protection is recommended ? (a) above 30 kVA. (b) equal to and above 5 MVA (c) equal to and above 25 MVA (d) none of the above

Last Answer : (b) equal to and above 5 MVA

Description : Why are motor ratings given in KW and that of alternator and transformer given in KVA?

Last Answer : kW is the output mechanical power of a motor and is expressed in kW. kVA is the net (apparent) power input to the transformer. This input power is the output + losses. kW = kVA x system power factor