What is the difference between an auto reset and manual reset overload relay?

1 Answer

Answer :

a. Auto reset relay closes its contacts when the bimetallic strip gets cooled. In manual reset relay we have to manually reset the relay because even though bimetallic strip cools its contacts are not closing without manual reset. L & T type OLR have only manual reset and siemens type has both manual and auto facility. 

b. Auto reset over load relay is reset by switching OFF the respective had switch and again switching it ON. 

c. Manual over load relay is reseted by pushing the reset button provided on the MCC cell. 

Related questions

Description : The illustrated motor fails to start and gives a loud hum when the start button is depressed, your first action should be to __________. EL-0007 A. disassemble the motor to fix the centrifical ... D. hold the 'M' contactor closed by hand while wearing electrical safety gloves to get motor started

Last Answer : Answer: B

Description : The 'reset' contacts of the master switch shown in the illustration provides the winch controller with ___________. EL-0102 A. low voltage release B. overload protection C. low voltage protection D. high power factor correction

Last Answer : Answer: C

Description : If the motor fails to start and a voltmeter reading between 1 and 6, as illustrated, indicates line voltage, your next step should be to ________. EL-0007 A. replace fuse '10a' B. replace or repair contact 'Ma' C. reset and determine the cause of the overload D. check line voltage between L1 and L3

Last Answer : Answer: C

Description : When power is restored after a complete power failure, a steering gear pump motor will ____________. A. have to be restarted B. have to be reset C. restart automatically D. trip its overload relays

Last Answer : Answer: C

Description : The schematic diagram shown in the illustration uses symbol 'A' to represent a/an _________. EL-0011 A. non-renewable fuse link B. circuit breaker coil C. overload relay coil D. thermal overload heater

Last Answer : Answer: D

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : The motor starts when the start button in the illustration is pushed, but stops when the button is released the trouble is _________. EL-0007 A. the incorrect thermal overload coil B. a faulty 'M' coil C. a dirty contact on the Disc.Sw. at 'L3' D. a faulty holding relay contact

Last Answer : Answer: D

Description : The purpose of the reverse power relay, provided on a ship's service alternator panel, is to trip the circuit in the event of ______________. A. main circuit overload B. high power transfer C. generator overspeeding D. alternator motorization

Last Answer : Answer: D

Description : 'A-1', as shown in the illustration, is/are ____________. EL-0017 A. normally-closed overload relay contacts B. a double pole knife switch C. normally-open overload relay contacts D. a single pole knife switch

Last Answer : Answer: A

Description : A loud buzzing noise in an AC controller is probably caused by _____________. A. poor contact with the overload relay B. an incorrectly sized heater C. a broken shading coil D. abnormal starting current

Last Answer : Answer: C

Description : The purpose of a magnetic relay is to _____________. A. open a circuit only in the event of overload B. remotely open and close contacts C. provide overcurrent protection during starting D. relay voltages at increased power

Last Answer : Answer: B

Description : A circuit is protected from overheating by a/an ___________. A. pyrometer B. thermal overload relay C. magnetic contactor D. overload transformer

Last Answer : Answer: B

Description : A three-phase, induction-type motor experiences an open in one phase. Which of the listed automatic protective devices will prevent the machine from being damaged? A. Overspeed trip B. Thermal overload relay C. Three-pole safety switch D. Magnetic blowout coil

Last Answer : Answer: B

Description : Protection against sustained overloads occurring in molded-case circuit breakers is provided by a/an __________. A. overvoltage release B. thermal acting trip C. thermal overload relay D. current overload relay

Last Answer : Answer: B

Description : Which of the motors for the devices listed below is fitted with an instantaneous overload relay? A. Fan B. Pump C. Winch D. Machine tool

Last Answer : Answer: C

Description : What are the materials made of thermal overload relay? How OLR are selected?

Last Answer : The bimetallic materials are Invar and brass. These materials having the differential coefficient of expansion. All bimetallic relays incorporate additional built in single phasing protection. The range of the relay provided ... at Centre) except in very minimum loads ranging from 0.1 - 0.16 A. 

Description : As shown in the illustration, once the "LV" relay is energized for operation, what contacts must remain closed to maintain the "LV" relay energized when the control lever is moved away from the "off" or "stop" ... . B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : Diesel generators #1 and #2 are operating in parallel at near full load capacity. Diesel generator #1 suddenly trips out mechanically due to low lube oil pressure. The reverse power relay functions ... all nonvital circuits. D. Secure alarms, reset reverse power relay, and restart #1 engine.

Last Answer : Answer: C

Description : As shown in the illustration, what is responsible for maintaining the "LV" relay energized when the master switch handle is moved away from the "off" position? EL-0102 A. "DBa" contact. B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : Low voltage releases as used in some shipboard motor starter and control equipment will have which of the following characteristics? A. They trip circuit contactors when the motor starts to overspeed. B. ... coil of the starter. D. They allow the motor to restart upon restoration of normal voltage.

Last Answer : Answer: D

Description : What are the protective parameters to changeover AVR auto to manual? 

Last Answer : a. PT supply fail. b. Auto pulse fail. c. Supply of limiter fail. d. Supply of auto channel fail. e. Regulated supply fail. f. High auto reference. 

Description : If Relay #5 changed contact position grounding the 'auto' input to the 'pitch controller module', pitch control would be effected by the _________________. EL-0095 A. pitch feedback potentiometer B. Engine room thrust split potentiometer C. Engine room thrust lever only D. Bridge thrust lever only

Last Answer : Answer: B

Description : What is an overload relay?*

Last Answer : What is an overload relay?*

Description : How does a thermal overload relay work?

Last Answer : The bi-metallic strip in the relay heats up by the over load current and the movement in the bi-metallic strip causes the breaker to trip. The breaker has to be reset (turn off) before turning on ... delay for the bi-metallic strip to cool down after which the breaker can be reset and switched on.

Description : Explain the construction and working of electronic overload relay.

Last Answer : Electronic overload relay consists of a solid state circuit that operates the electromagnetic switching device to protect the load from overload. The load current is sensed by using a current ... sections. The output of relay driver section sends trip signal to electromagnetic switching device.

Description : A relay used for protection of motors against overload is :  (A) Impedance relay (B) Electromagnetic attraction type (C) Thermal relay (D) Buchholz's relay

Last Answer : D

Description : how do I reset the horn relay on a 2006 Chrysler 300 V6

Last Answer : Need Answer

Description : Define the following terms with respect to protective relays i) Relay time ii) Reset current iii) Plug setting multiplier and iv) Time setting multiplier

Last Answer : 1) Relay Time: The time interval between occurrence of fault and closure of relay contacts.  2) Reset Current: The value of current below which the relay resets and comes back to ... The adjustment arrangement provided for setting the operation time of relay is known as Time setting multiplier. 

Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button

Last Answer : Answer: D

Description : The rated temperature rise of an electric motor is the _____________. A. average temperature at any given latitude B. normal temperature rise above the standard ambient temperature at rated load ... D. permissible difference in the ambient temperature of the motor due to existing weather conditions

Last Answer : Answer: B

Description : In your opinion, why are auto makers phasing out the manual transmission on a lot of their vehicles?

Last Answer : I know a few people will turn their nose up and huff, by saying automatic transmissions are now just as economical as a manual so why bother with a manual. BUT, that doesn’t really answer the question, are they scaling back or phasing out because people have lost the skill, or are to lazy?

Description : Where automatic restart does not present a hazard after a power failure, Coast Guard Regulations (46 CFR) require motor controllers for auxiliaries vital to the propelling equipment to be provided ... overload protection B. low voltage protection C. low voltage release D. reverse current protection

Last Answer : Answer: C

Description : If overloading a DC machine becomes necessary in an emergency, you should ____________. A. cool the machine with portable blowers and fans B. hold thermal overload relays open with blocks of ... the windings for cooling D. increase the residual magnetism value of windings to reduce eddy currents

Last Answer : Answer: A

Description : Which of the following statements is true concerning the motor controller diagram shown in the illustration? EL-0023 A. Terminal 'T2' is hot only on high speed. B. Both indicating lights will be lit on ... high speed operation only. D. 'L2' is always connected to 'T2' whenever the motor is running.

Last Answer : Answer: D

Description : If a DC motor runs faster than designed, with all other conditions being normal, the possible cause could be a/an ______________. A. shorted shunt field coil B. open armature coil C. reversed commutating pole D. overload

Last Answer : Answer: A

Description : Component F in the illustrated device is for _________. EL-0033 A. short circut protection B. latching the trip unit closed after resetting the breaker C. overload protection D. providing a flexible connection between the input terminal G and the tripping unit E

Last Answer : Answer: C

Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown

Last Answer : Answer: B

Description : In the illustration if the compressor fails to start but the condenser fan motor is running the problem is _______. EL-0042 A. no power between L1 and L2 B. the yellow wire is open at the freezer temperature control switch C. the overload is open D. the blue wire from the defrost heater is open

Last Answer : Answer: C

Description : If a synchronous motor begins to vibrate severely and pull out of synchronism, the cause may be ____________. A. an overload B. an open in the field coils C. no exciter voltage D. all of the above

Last Answer : Answer: D

Description : An overload in which of the listed motors will result in the illumination of an indicating light at the propulsion control station alarm panel? A. Fuel pump motor B. Steering motor C. Condensate pump motor D. Forced draft blower motor

Last Answer : Answer: B

Description : In the illustration if the compressor fails to start but the condenser fan motor is running the problem is _______. EL-0043 A. no power between L1 and L2 B. the yellow wire is open at the freezer temperature control switch C. the overload is open D. the blue wire from the defrost heater is open

Last Answer : Answer: C

Description : In the illustration, the purpose of part B is to _________. EL-0033 A. increase resistance in series with the contacts as they close to prevent arcing B. create a magnetic field in the steel ... event of an overload D. provide ventilation to the contact when the breaker is close to rated capacity

Last Answer : Answer: B

Description : During maintenance of circuit breakers, _______________. A. always smooth roughened contact surfaces with a file B. never pass more than rated breaker current through the overload heater element C. ... wear and misalignment of main contacts D. assume heater elements installed are of correct size

Last Answer : Answer: C

Description : In the illustration, 'D' is the symbol for a/an __________. EL-0005 A. thermal overload heater B. portable cable C. fuse D. indicating lamp

Last Answer : Answer: C

Description : As shown in the illustration, 'S' is the __________. EL-0017 A. safety switch B. overload trip C. start button D. stop button

Last Answer : Answer: D