The current at which a magnetic-type overload relay tends to trip may be decreased by raising the plunger further into the magnetic circuit of the relay. This action ___________. A. reduces magnetic pull on the plunger and requires more current to trip the relay B. reduces magnetic pull on the plunger and requires less current to trip the relay C. increases magnetic pull on the plunger and requires more current to trip the relay D. increases magnetic pull on the plunger and requires less current to trip the relay

1 Answer

Answer :

Answer: D

Related questions

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : A circuit is protected from overheating by a/an ___________. A. pyrometer B. thermal overload relay C. magnetic contactor D. overload transformer

Last Answer : Answer: B

Description : Protection against sustained overloads occurring in molded-case circuit breakers is provided by a/an __________. A. overvoltage release B. thermal acting trip C. thermal overload relay D. current overload relay

Last Answer : Answer: B

Description : A three-phase, induction-type motor experiences an open in one phase. Which of the listed automatic protective devices will prevent the machine from being damaged? A. Overspeed trip B. Thermal overload relay C. Three-pole safety switch D. Magnetic blowout coil

Last Answer : Answer: B

Description : If a circuit breaker that utilizes built-in, current limiting fuses (CLF's) cannot be closed, the problem may be traced to __________. A. a blown CLF plunger holding the trip bar in the open position B. a missing CLF C. a misaligned limiter housing assembly D. all of the above

Last Answer : Answer: D

Description : The purpose of the reverse power relay, provided on a ship's service alternator panel, is to trip the circuit in the event of ______________. A. main circuit overload B. high power transfer C. generator overspeeding D. alternator motorization

Last Answer : Answer: D

Description : The arc resulting from the tripping of a circuit breaker is prevented from damaging the contacts by _____________. A. designing the contacts to open slowly B. directing the arc into an ... an inverse timed thermal trip for short circuit currents D. instantaneous magnetic trip for overload currents

Last Answer : Answer: B

Description : The purpose of a magnetic relay is to _____________. A. open a circuit only in the event of overload B. remotely open and close contacts C. provide overcurrent protection during starting D. relay voltages at increased power

Last Answer : Answer: B

Description : Fuses placed in series with a thermal trip-type circuit breaker are used for _____________. A. time-delay protection B. short-circuit protection C. short duration surge protection D. sustained overload protection

Last Answer : Answer: B

Description : As shown in the illustration, a 'pitch cutback' feature is incorporated in the system. This circuit reduces pitch amount to prevent engine overload when it senses ____________. EL-0095 A. pitch error of ... servo' C. excessive propeller speed or fuel to either engine D. only one engine on the line

Last Answer : Answer: C

Description : The schematic diagram shown in the illustration uses symbol 'A' to represent a/an _________. EL-0011 A. non-renewable fuse link B. circuit breaker coil C. overload relay coil D. thermal overload heater

Last Answer : Answer: D

Description : The purpose of a main switchboard circuit breaker's reverse-power trip is to _____________. A. prevent main circuit overload B. protect the circuit breaker blowout coil C. prevent alternator motorization D. prevent low voltage tripout

Last Answer : Answer: C

Description : A loud buzzing noise in an AC controller is probably caused by _____________. A. poor contact with the overload relay B. an incorrectly sized heater C. a broken shading coil D. abnormal starting current

Last Answer : Answer: C

Description : If a synchronous motor begins to vibrate severely and pull out of synchronism, the cause may be ____________. A. an overload B. an open in the field coils C. no exciter voltage D. all of the above

Last Answer : Answer: D

Description : When troubleshooting a motor controller, all indications are that a relay coil should be energized. If there were no magnetic pull, with rated voltage measured across the coil, the most probable cause ... open C. auxiliary contact in series with the coil is defective D. relay armature is stuck

Last Answer : Answer: A

Description : Due to circumferential action of the spiral in a spirally reinforced column (A) Capacity of column is decreased (B) Ductility of column reduces (C) Capacity of column is decreased but ductility of column increases (D) Both the capacity of column and ductility of column increase

Last Answer : Answer: Option D

Description : Due to Circumferential action of the spiral reinforcement in a column [ A ] Capacity of column is decreased but ductility of column increases [ B ] Both the capacity of column an ductility of column increases [ C ] Capacity of column increases [ D ] Ductility of the column reduces

Last Answer : [ B ] Both the capacity of column an ductility of column increases

Description : An instantaneous-trip-type fuse will _____________. A. open as soon as the load current exceeds its set point B. allow a preset delay between overcurrent and melting C. open a circuit by using a time delay element with a magnetic trip D. reset itself when the overcurrent is corrected

Last Answer : Answer: A

Description : Low voltage releases as used in some shipboard motor starter and control equipment will have which of the following characteristics? A. They trip circuit contactors when the motor starts to overspeed. B. ... coil of the starter. D. They allow the motor to restart upon restoration of normal voltage.

Last Answer : Answer: D

Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button

Last Answer : Answer: D

Description : Which of the following statements is true concerning a stepdown transformer in an operating AC power circuit? A. Voltage and current will both be increased. B. Voltage and current will both be decreased C. Voltage decreases as current increases. D. Voltage increases as current decreases.

Last Answer : Answer: C

Description : The motor starts when the start button in the illustration is pushed, but stops when the button is released the trouble is _________. EL-0007 A. the incorrect thermal overload coil B. a faulty 'M' coil C. a dirty contact on the Disc.Sw. at 'L3' D. a faulty holding relay contact

Last Answer : Answer: D

Description : 'A-1', as shown in the illustration, is/are ____________. EL-0017 A. normally-closed overload relay contacts B. a double pole knife switch C. normally-open overload relay contacts D. a single pole knife switch

Last Answer : Answer: A

Description : Which of the motors for the devices listed below is fitted with an instantaneous overload relay? A. Fan B. Pump C. Winch D. Machine tool

Last Answer : Answer: C

Description : What are the materials made of thermal overload relay? How OLR are selected?

Last Answer : The bimetallic materials are Invar and brass. These materials having the differential coefficient of expansion. All bimetallic relays incorporate additional built in single phasing protection. The range of the relay provided ... at Centre) except in very minimum loads ranging from 0.1 - 0.16 A. 

Description : What is the difference between an auto reset and manual reset overload relay?

Last Answer : a. Auto reset relay closes its contacts when the bimetallic strip gets cooled. In manual reset relay we have to manually reset the relay because even though bimetallic strip cools its contacts are not ... . Manual over load relay is reseted by pushing the reset button provided on the MCC cell. 

Description : Main function of cutout relay in electrical circuit is A. To prevent the reversal of current flow from the battery when dynamo speed (engine speed) reduces. B. To restrict the maximum output at ... deliver current to the battery or to the lightening and ignition circuit. D. None of the above

Last Answer : A. To prevent the reversal of current flow from the battery when dynamo speed (engine speed) reduces.

Description : If a magnetic controller relay fails to drop out when the coil voltage is removed from the relay, the probable cause may be _____________. A. excessive spring tension B. overvoltage C. excessive current D. welded contacts

Last Answer : Answer: D

Description : If a magnetic controller contactor fails to pick up when the coil voltage is applied to the contactor coil, the cause may be _____________. A. overload B. misalignment of the affected contactor contacts C. low spring pressure D. an open contactor coil

Last Answer : Answer: D

Description : As far as surgical removal of wisdom teeth is concerned which of the following is true? a- Prophylactic prescription of antibiotic reduces dramatically the chances of infection. b- Raising a lingual ... e- The use of vasoconstrictors in local anaesthetics will increase the chances of infection.

Last Answer : b- Raising a lingual flap will increases the incidence of neurapraxia but will reduce the incidence of neurotmesis with respect to the lingual nerve.

Description : As far as surgical removal of wisdom teeth is concerned, which of the following is true?**CHECK A. Prophylactic prescription of antibiotic reduces dramatically the chances of infection B. Raising ... root E. The use of vasoconstrictors in local anaesthetics will increase the chances of infection.

Last Answer : C. Prophylactic prescription of dexamethasone will dramatically reduces post operative swelling

Description : A diesel driven emergency generator is prevented from being paralleled with the ship's service generators by __________. A. an electrical interlock system B. an automatic paralleling trip switch C. the synchronizing oscilloscope D. the reverse current relay

Last Answer : Answer: A

Description : Component F in the illustrated device is for _________. EL-0033 A. short circut protection B. latching the trip unit closed after resetting the breaker C. overload protection D. providing a flexible connection between the input terminal G and the tripping unit E

Last Answer : Answer: C

Description : When power is restored after a complete power failure, a steering gear pump motor will ____________. A. have to be restarted B. have to be reset C. restart automatically D. trip its overload relays

Last Answer : Answer: C

Description : As shown in the illustration, 'S' is the __________. EL-0017 A. safety switch B. overload trip C. start button D. stop button

Last Answer : Answer: D

Description : Inverse definite minimum time lag relay is also called ___________ (A) pilot relay. (B) differential relay. (C) over current relay. (D) directional overcurrent relay.

Last Answer : Ans: B Inverse definite minimum time lag relay characteristic is inverse but minimum time is fixed. The operating time is inversely proportional to the magnitude of actuating quantity.

Description : The 'reset' contacts of the master switch shown in the illustration provides the winch controller with ___________. EL-0102 A. low voltage release B. overload protection C. low voltage protection D. high power factor correction

Last Answer : Answer: C

Description : During maintenance of circuit breakers, _______________. A. always smooth roughened contact surfaces with a file B. never pass more than rated breaker current through the overload heater element C. ... wear and misalignment of main contacts D. assume heater elements installed are of correct size

Last Answer : Answer: C

Description : Would you have any problem sticking your hand in your toilet tank to pull the plunger to flush the toilet?

Last Answer : Nope. Done it many times, for various reasons. It’s sticking my hand in the bowl that I would balk at.

Description : Which device will stop the motor shown in the illustration in case of a short-circuit (high current) motor overload? EL-0080 A. 'F' B. 'G' C. 'H' D. 'I'

Last Answer : Answer: A

Description : In the illustrated circuit, one advantage of the capacitor coupling over direct coupling is ____________. EL-0048 A. as the frequency decreased the capacitive reactance (Xc) increases B. the amplifier becomes ... of the signal while it isolates the biasing of each stage. D. good frequency response.

Last Answer : Answer: C

Description : Magnetic circuit breaker has ______ trip action. (a) delayed (b) instantaneous (c) both of the above (d) none of the above

Last Answer : (b) instantaneous

Last Answer : Magnetic circuit breaker has instantaneous trip action.

Description : Action carried out by the relay and circuit breaker during fault condition?

Last Answer : Answer: After the relay sensing the fault condition, relay operates and close the trip coils. The effect of this will be circuit breaker operate to open the contacts.

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0° prior to closing the circuit breaker. This indicates ___________. A. the frequency of ... be closed after breaker has been reset D. there is an existing cross current between generators

Last Answer : Answer: A