Description : If three AC generators are operating in parallel, and one of them were to 'pull out' of synchronism with the other two generators, the ____________. A. normally operating AC generators will ... AC generators will overspeed and unload D. AC generator pulling out of synchronism will become motorized
Last Answer : Answer: B
Description : An alternator operating in parallel begins to vibrate severely and eventually trips out on the reverse power relay. The cause of the vibration was a result of ______________________. A. the ... C. the alternator was operating out of synchronism D. flashover at the alternator collector rings
Last Answer : Answer: C
Description : A synchronous motor maintains synchronism with the rotating field because _____________. A. field strength varies directly with rotor slip B. DC current applied to the rotor coils causes the rotor ... the flux created by the excitation current D. the stator flux rotates in the opposite direction
Description : The rotor of a synchronous motor operates in synchronism with the rotating field because ______________. A. of the amortisseur windings B. the rotor is magnetically locked into step with the ... field strength varies directly with rotor slip D. the stator flux rotates in the opposite direction
Description : The maximum constant load torque under which a synchronous motor will pull into synchronism at rated rotor supply voltage and frequency is known as?
Last Answer : The maximum constant load torque under which a synchronous motor will pull into synchronism at rated rotor supply voltage and frequency is known as pull-in torque.
Description : The most common source of excitation for synchronous motors is a/an _____________. A. low voltage battery B. motor attenuator set C. DC exciter generator D. AC supply
Description : Shading coils are installed on AC full-voltage starters to _____________. A. eliminate contact chatter B. dissipate opening contact arcs C. delay current build up in the holding coil D. protect the motor windings from momentary starting current overload
Last Answer : Answer: A
Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed
Description : If a DC motor runs faster than designed, with all other conditions being normal, the possible cause could be a/an ______________. A. shorted shunt field coil B. open armature coil C. reversed commutating pole D. overload
Description : Which of the following precautions should be taken when troubleshooting various power circuits using a common solenoid-type mechanical voltage tester (wiggins)? A. Never use this tester on circuits greater ... voltage expected in the circuit in order to prevent damage from an off-scale reading.
Description : When troubleshooting a motor controller, all indications are that a relay coil should be energized. If there were no magnetic pull, with rated voltage measured across the coil, the most probable cause ... open C. auxiliary contact in series with the coil is defective D. relay armature is stuck
Description : If a magnetic controller contactor fails to pick up when the coil voltage is applied to the contactor coil, the cause may be _____________. A. overload B. misalignment of the affected contactor contacts C. low spring pressure D. an open contactor coil
Last Answer : Answer: D
Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed
Description : When troubleshooting AC motors, a portable growler can be used for locating ____________. A. open field coils B. grounded field coils C. grounded stator coils D. shorted stator coils
Description : The frequency of an AC generator is adjusted by means of the ____________. A. main alternator field rheostat B. exciter field rheostat C. prime mover governor control D. equalizing reactor
Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown
Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button
Description : If the motor fails to start and a voltmeter reading between 1 and 6, as illustrated, indicates line voltage, your next step should be to ________. EL-0007 A. replace fuse '10a' B. replace or repair contact 'Ma' C. reset and determine the cause of the overload D. check line voltage between L1 and L3
Description : A megohmmeter can be used to test for ____________. A. an open field coil B. synchronous speed C. undercut mica D. reversed polarity
Description : Moisture accumulating in electric motors and generator windings having a cold insulation resistance greater than 50,000 ohms may be baked out with internal heat. This heat can be developed by ____________. ... an electric welder and feeding it into the armature while running the motor at full speed
Description : When the series field relay "FR" of the winch circuit shown in the illustration is energized during dynamic braking the _______________. EL-0102 A. shunt Field Relay "FR-B.O." is de-energized and contacts ... . shunt Field Relay "FR-B.O." opposes the series coil's flux and sets the mechanical brake
Description : As shown in the illustration, the motor generator(M-G) set's three-phase motor drives the ______________. EL-0101 A. motor and the generator B. motor and the exciter C. generator and the exciter D. main field and the interpole field
Description : As shown in the illustration, the M-G set's three-phase motor drives the ______________. EL-0101 A. motor and the generator B. motor and the exciter C. generator and the exciter D. main field and the interpole field
Description : The voltage of an operating AC turbogenerator is raised or lowered by adjusting the _____________. A. exciter generator governor controls B. synchronizing switch C. phase sequence switch D. generator field exciter
Description : The simplest method of controlling the terminal voltage of compound-wound DC generator is with a _____________. A. hand-operated field rheostat connected in series with the shunt field circuit B. ... in series with the load D. balance coil diverting neutral current through the shunt field
Description : The circuit shown in the illustration represents a ________. EL-0090 A. battery charging circuit B. synchronous exciter C. depth sounding unit D. cathodic protection system
Description : In the illustration, the purpose of part B is to _________. EL-0033 A. increase resistance in series with the contacts as they close to prevent arcing B. create a magnetic field in the steel ... event of an overload D. provide ventilation to the contact when the breaker is close to rated capacity
Description : When power is restored after a complete power failure, a steering gear pump motor will ____________. A. have to be restarted B. have to be reset C. restart automatically D. trip its overload relays
Description : Humming or buzzing of electric contacts is a symptom of ____________. A. low voltage on the operating coil B. power failure to the operating coil C. a control circuit ground D. a control circuit overload
Description : If a three-phase induction motor is operated under a light load and it develops an open in one of its supply lines, the motor will _____________. A. continue to run, but will vibrate and have reduced ... speed up due to the reduced number of poles C. run cooler due to reduced current flow D. stop
Description : Insufficient brush pressure on a DC motor may cause _______. A. generator overload B. excess residual magnetism C. water vapor absorption D. sparking of the brushes
Description : The current at which a magnetic-type overload relay tends to trip may be decreased by raising the plunger further into the magnetic circuit of the relay. This action ___________. A. reduces magnetic ... the relay D. increases magnetic pull on the plunger and requires less current to trip the relay
Description : If coil 'R1-R2' on the transmitter in figure 'A' shown in the illustration is turned 30 degrees clockwise, corresponding coil 'R1-R2' on the receiver should ____________. EL-0092 A. make coils 'S1 ... a higher voltage depending on the turns ratio D. align itself to the same position if free to move
Description : If overloading a DC machine becomes necessary in an emergency, you should ____________. A. cool the machine with portable blowers and fans B. hold thermal overload relays open with blocks of ... the windings for cooling D. increase the residual magnetism value of windings to reduce eddy currents
Description : 'A-1', as shown in the illustration, is/are ____________. EL-0017 A. normally-closed overload relay contacts B. a double pole knife switch C. normally-open overload relay contacts D. a single pole knife switch
Description : The speed of a synchronous motor is varied by _____________. A. interchanging any two of the three live leads B. changing the voltage of the system C. changing the input frequency D. increasing the field excitation
Description : If the field circuits of an unloaded salient pole synchronous motor gets suddenly open circuited, then (A) The motor stops. (B) It continues to run at the same speed. (C) Its runs at the slower speed. (D) It runs at a very high speed.
Last Answer : Ans: B The motor continues to run at the same speed because synchronous motor speed does not depend upon load, Nα f.
Description : In the illustration if the compressor fails to start but the condenser fan motor is running the problem is _______. EL-0042 A. no power between L1 and L2 B. the yellow wire is open at the freezer temperature control switch C. the overload is open D. the blue wire from the defrost heater is open
Description : In the illustration if the compressor fails to start but the condenser fan motor is running the problem is _______. EL-0043 A. no power between L1 and L2 B. the yellow wire is open at the freezer temperature control switch C. the overload is open D. the blue wire from the defrost heater is open
Description : The synchronous reactance of the synchronous machine is ______________. (A) Ratio between open circuit voltage and short circuit current at constant field current (B) Ratio between short circuit ... (D) Ratio between short circuit voltage and open circuit current at different field current
Last Answer : Ans. A The Synchronous reactance of a synchronous machine is a total steady state reactance, presented to applied voltage, when rotor is running synchronously without excitation. Therefore , XS = Ef / IS = Emf of OC for same If / short circuit current
Description : Under normal conditions, the speed of a two-speed squirrel cage induction motor is changed by varying the ____________. A. frequency of the applied voltage B. resistance in the rotor circuit C. number of field poles D. amplitude of the applied voltage
Description : One method of testing for a reversed shunt field coil in a DC generator or motor is by connecting the field to a direct current source, at reduced field rated voltage, and test for ... placed near each field C. test lamp across adjacent fields D. copper jumper across the interpole connections
Description : A shaded-pole motor is a ____________. A. synchronous motor B. three-phase induction motor C. compound-wound motor D. single-phase induction motor
Description : A damper winding is designed as part of a synchronous motor to ____________. A. increase efficiency B. provide starting torque C. provide excitation D. eliminate slippage
Description : A motor using a rheostat in the motor circuit to vary the speed is called a ____________. A. squirrel-cage induction motor B. regenerative braking motor C. wound-rotor induction motor D. synchronous motor
Description : Where automatic restart does not present a hazard after a power failure, Coast Guard Regulations (46 CFR) require motor controllers for auxiliaries vital to the propelling equipment to be provided ... overload protection B. low voltage protection C. low voltage release D. reverse current protection
Description : In the illustrated motor controller circuit, which statment is true? EL-0023 A. The high and low speed lights operate at less than line voltage with a resistor in series. B. This controller can be ... . The wattage of the high speed light must be greater than the wattage of the low speed light.
Description : An open armature connection in a DC propulsion motor could be caused by ____________. A. low-load operation B. clogged ventilation ducts C. sparking at the brushes D. a grounded shunt field coil
Description : The leads from a megohmmeter are attached to the leads of an AC motor field coil. A reading of infinity is obtained indicating a/an ____________. A. open field coil B. shorted field coil C. grounded field coil D. shunted field coil
Description : A suspected 'open' in a motor field can be tested by using a/an ____________. A. potentiometer B. megger C. wattmeter D. ammeter