What are the logic’s adopted in barring gear motor?
For start permission
a) Local or remote start.
b) JOP is running.
c) Motor hand barring is permissive.
d) 42 contactor in MCC is off.
e) Turbine speed is <100 rpm.
Start permission (42S of MCC)
a) All above
b) Bearing oil pressure is >0.35 kg/ cm2.
c) No thermal over load of 42S.
d) No one-DG condition.
Start permission (42 of MCC)
a) Start permissive of 42S.
b) Barring gear engage or motor speed reached to 1475 rpm.
c) Turbine speed is <100 rpm.
d) Bearing oil pressure is >0.35 kg/ cm2.
e) No thermal over load of 42.
f) No one-DG condition.