You are attempting to parallel two AC generators and the synchroscope pointer is revolving slowly in the fast direction. You should _____________.  A. use the governor control switch to adjust the incoming voltage so it is equal to the bus voltage B. use the governor control switch to increase the speed of the machine on the line only C. close the circuit breaker when the synchroscope pointer approaches the 0° position D. use the field rheostat to adjust the speed of the incoming machine

1 Answer

Answer :

Answer: C

Related questions

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving fast in the clockwise direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... at any pointer position D. the same as the bus frequency but out of phase with it

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving in the fast direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... the same as the bus frequency and the circuit breaker may be closed at any pointer position

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer is revolving in the slow direction. This indicates that the frequency of the incoming machine is _____________. A. higher than ... same as the bus frequency, and the circuit breaker may be closed at any pointer position

Last Answer : Answer: B

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0° prior to closing the circuit breaker. This indicates ___________. A. the frequency of ... be closed after breaker has been reset D. there is an existing cross current between generators

Last Answer : Answer: A

Description : You are paralleling two alternators. The synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates that the ____________. A. alternator ... be closed C. incoming alternator is running too slowly D. synchroscope is defective or broken

Last Answer : Answer: B

Description : When paralleling two alternators the synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates the ____________. A. alternator voltages ... alternator is in phase with the bus voltage D. synchroscope pointer is defective or broken

Last Answer : Answer: C

Description : When paralleling two AC generators, the frequency of the incoming machine immediately prior to closing its breaker should be ____________. A. controlled by placing the governor switch in the automatic ... regulator C. slightly greater than the bus frequency D. slightly less than the bus frequency

Last Answer : Answer: C

Description : When paralleling two alternators, the synchronizing lamps remain lit as the synchroscope pointer approaches the 0°. This indicates the _____________. A. incoming alternator is running too fast B. alternator ... apart C. synchroscope is defective or broken D. alternator power factors are in phase

Last Answer : Answer: C

Description : When two AC generators are being paralleled, the breaker should be closed with the synchroscope pointer rotating in the ____________. A. 'slow' direction, just before the 12 o'clock position B. 'fast' ... just before the 12 o'clock position D. 'slow' direction, just after the 12 o'clock position

Last Answer : Answer: C

Description : As shown in the illustration, which of the listed actions of the synchroscope pointer is occurring? EL-0002 A. Revolving slowly in the slow direction. B. Revolving rapidly in the slow direction. C. ... stationary at the 12 o'clock position since the leading edges of the A phases are in phase.

Last Answer : Answer: C

Description : If the pointer of the synchroscope is rotating in the slow direction when you are preparing to parallel two alternators, the _____________. A. incoming machine is turning faster than the load alternator B ... alternator is ready to split D. incoming machine is beginning to pick up some of the load

Last Answer : Answer: B

Description : If two AC generators have just been placed in parallel, the true power load is initially distributed evenly by _____________. A. a balance coil B. changing field excitation C. adjusting the governor control settings D. a rheostat

Last Answer : Answer: C

Description : Which of the synchroscope illustrations depicts the appropriate direction of rotation and position for closing the circuit breaker when paralleling AC generators? EL-0053 A. A B. B C. C D. D

Last Answer : Answer: D

Description : When paralleling two AC generators, the synchroscope selector switch and frequency meter switch should be set up to sense the frequency of the _____________. A. bus B. generator on the line C. oncoming generator D. bus transfer relay

Last Answer : Answer: C

Description : An AC generator panel is fitted with both synchronizing lamps and a synchroscope. When the synchroscope pointer reaches the noon position, one synchronizing light is bright and the other is dark. This ... sequence is incorrect C. the phase sequence is correct D. the generator breaker may be closed

Last Answer : Answer: B

Description : Prior to closing the breaker when paralleling two AC generators, the recommended practice is to have the frequency of the incoming machine _____________. A. slightly less than the line frequency B. the same as the line frequency C. slightly greater than the line frequency D. all of the above

Last Answer : Answer: C

Description : When paralleling two AC generators, the frequency (cycles) of the incoming generator, just prior to closing the circuit breaker, should be _____________. A. slightly less than the frequency of the generator on ... C. slightly more than the frequency of the generator on the line D. all of the above

Last Answer : Answer: C

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : Equal power factors on paralleled AC generators are maintained by an automatic _____________. A. voltage regulator B. reverse power relay C. reverse current relay D. governor control switch

Last Answer : Answer: A

Description : Moving the rheostat handle shown in the illustration, that is used to control a DC generator, towards the 'raise' direction will increase the _____________. EL-0030 A. field resistance B. armature resistance C. armature speed D. line voltage

Last Answer : Answer: D

Description : An equalizing connection between two compound-wound DC generators when paralleled, serves to _____________. A. reverse the polarity of the incoming generator as the series field weakens B. automatically ... the series field of the incoming generator D. parallel the series fields of the generators

Last Answer : Answer: D

Description : When paralleling two AC generators, the frequency of the machine coming online, immediately prior to closing its breaker, should be ____________. A. slightly less than the oncoming generator frequency B. the ... bus frequency C. slightly greater than the bus frequency D. the same as the bus voltage

Last Answer : Answer: C

Description : Attempting to parallel an AC generator which is out of phase with the bus will result in which of the following problems? A. The breaker should trip. B. The KVA will decrease. C. The synchronizing lamps will burn out. D. The power factor will be unitized.

Last Answer : Answer: A

Description : To remove an alternator operating in parallel with another unit from the main electrical bus, you must FIRST _________. A. adjust the power factor on both units B. set the desired voltage on ... C. open the circuit breaker on the outgoing alternator D. remove the load from the outgoing alternator

Last Answer : Answer: D

Description : Kilowatt load is divided between two AC generators operating in parallel by _____________. A. adjusting the governor controls B. varying the excitation voltage C. increasing both prime mover speeds simultaneously D. decreasing both prime mover speeds simultaneously

Last Answer : Answer: A

Description : The kilowatt load can be adjusted on a paralleled generator by using the _____________. A. field rheostat B. governor control C. automatic voltage regulators D. hand tachometer

Last Answer : Answer: B

Description : Two AC generators of the same capacity are operating in parallel. One with a zero speed droop setting and the other with a 5% speed droop. If its capacity is not exceeded, the unit whose ... B. maintain the frequency of the system C. have poor sensitivity characteristics D. have poor power response

Last Answer : Answer: B

Description : An open occurring within the field rheostat of an AC generator can be detected by short circuiting its terminals and observing a ____________. A. negative deflection of the wattmeter pointer B. ... of the wattmeter pointer C. buildup of alternator voltage D. low, but constant alternator voltage

Last Answer : Answer: C

Description : The KW load is evenly distributed between two alternators just placed in parallel by adjusting _____________. A. a balance coil B. the governor settings C. the field excitation D. a rheostat

Last Answer : Answer: B

Description : An alternator is being paralleled with one on the line. At the INSTANT the circuit breaker is closed, the frequency of the incoming alternator will normally _____________. A. increase B. not change C. decrease D. be exactly 60 hertz

Last Answer : Answer: C

Description : A shore power circuit breaker should be closed only _____________. A. when the ship's generators have been directly paralleled to those on shore B. in a shipyard C. if a quick disconnect coupling is used D. when the ship's generators have been removed from the bus

Last Answer : Answer: D

Description : Automatic voltage regulators provided on switchboards function to _____________. A. regulate the AC load on the generator B. protect the switchboard from high voltage C. govern prime mover speed to control voltage D. vary the field excitation to the generators

Last Answer : Answer: D

Description : The voltage of an operating AC turbogenerator is raised or lowered by adjusting the _____________. A. exciter generator governor controls B. synchronizing switch C. phase sequence switch D. generator field exciter

Last Answer : Answer: D

Description : The division of the kilowatt load between two AC generators operating in parallel is controlled by the settings and characteristics of the _____________. A. voltage regulators B. field rheostats C. reverse power relays D. prime mover governors

Last Answer : Answer: D

Description : The frequency of an AC generator is adjusted by means of the ____________. A. main alternator field rheostat B. exciter field rheostat C. prime mover governor control D. equalizing reactor

Last Answer : Answer: C

Description : When securing an AC generator, you should FIRST ___________. A. open the generator circuit breaker B. switch the voltage regulator to 'manual' C. decrease the field excitation to minimum D. reduce the load on the unit

Last Answer : Answer: D

Description : The frequency of an AC generator is controlled by the _____________. A. rheostat B. governor C. exciter D. capacitor

Last Answer : Answer: B

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description : The governor control switch of an alternator is moved to the 'raise' position. This action will _____________. A. raise the no-load speed setting of the governor B. raise the percentage of speed droop C. lower the no-load speed setting of the governor D. lower the percentage of speed droop

Last Answer : Answer: A

Description : In the illustration, the contacts between terminals 26 and 27 should be closed when _________. EL-0046 A. using one generator in isochronous mode only B. using two or more generators in ... through varying loads in parallel or single operation D. the circuit breaker is closed for that generator

Last Answer : Answer: C

Description : The simplest method of controlling the terminal voltage of compound-wound DC generator is with a _____________. A. hand-operated field rheostat connected in series with the shunt field circuit B. ... in series with the load D. balance coil diverting neutral current through the shunt field

Last Answer : Answer: A

Description : Before any work on electrical or electronic equipment is performed, which of the following precautions should be carried out? A. De-energize the applicable switchboard bus. B. Bypass the interlocks. C. ... supply circuit breaker in the open position. D. Station a man at the circuit supply switch.

Last Answer : Answer: C

Description : The speed of a wound-rotor induction motor _____________. A. will be fixed by the number of field poles B. can be varied by a rheostat-type control C. can only be synchronous speed at full load D. can only attain synchronous speed at no load

Last Answer : Answer: B

Description : The cycles per second developed by the alternator aboard your vessel is determined by _____________. A. the speed of the engine driving the alternator B. the resistance applied to the field rheostat C. the synchronous speed of induction D. the adjustments made to the voltage regulator

Last Answer : Answer: A

Description : Voltage generated by most AC generators is fed from the machine to the bus by means of ____________. A. brushes on a commutator B. brushes on slip rings C. slip rings on a commutator D. direct connections from the stator

Last Answer : Answer: D