A capacitor is to be tested with a megohmmeter. If the meter is connected to a shorted capacitor, the meter pointer should _____________. A. immediately swing to the maximum resistance value B. deflect to zero and remain at that position C. swing to a high reading and gradually decrease D. swing to zero then gradually increase with slight pointer movements down scale

1 Answer

Answer :

Answer: B

Related questions

Description : A capacitor can be tested using a megohmmeter or an ohmmeter. If the meter is connected to a shorted capacitor, the meter pointer should _____________. A. immediately swing to the maximum resistance ... deflect to and remain at zero D. immediately swing to a high reading and then gradually decrease

Last Answer : Answer: C

Description : When a megohmmeter is being used on a alternating current machine, the meter pointer will dip toward 'zero' and then gradually rise to the true resistance value if the motor insulation is _____________. A. grounded B. good C. shorted D. dirty

Last Answer : Answer: B

Description : When using a megohmmeter to test insulation, good insulation will be indicated by _____________. A. slight kicks of the needle down scale B. a downward dip followed by a gradual climb to the true resistance ... C. a gradual rise in the pointer reading at the outset D. the initial dip of the pointer

Last Answer : Answer: B

Description : When a megohmmeter is being used to test insulation resistance, current leakage along the surface of the insulation is indicated by the megohmmeter's pointer _____________. A. dipping toward ... kicking slightly down scale as voltage is applied D. fluctuating around a constant resistance reading

Last Answer : Answer: C

Description : When a megohmmeter is being used to test insulation resistance, current leakage along the surface of the insulation is indicated by the megohmmeter pointer _____________. A. fluctuating around a ... slightly downscale as voltage is applied D. continually rising as the test voltage is applied

Last Answer : Answer: C

Description : Before measuring an unknown resistance with an ohmmeter, you should _____________. A. adjust the meter's pointer to mid-scale B. short the test leads and calibrate the meter reading to 'zero' C. change the meter's batteries D. center the meter's pointer at infinity

Last Answer : Answer: B

Description : Which of the following conditions indicates a short circuited capacitor when checking its condition with an ohmmeter? A. The capacitor shows charging, but the final resistance reading is appreciably less ... moves quickly to the low resistance side of the scale, then slowly recedes toward infinity.

Last Answer : Answer: B

Description : When a megohmmeter is used to test insulation, the gradual rise of the pointer reading as a result of continued cranking, is caused by _____________. A. good conductor resistance B. the ... insulation C. the inductive reactance of the windings D. the dielectric-absorption effect of the insulation

Last Answer : Answer: D

Description : A testing device called a 'growler' is being used to locate a shorted coil in the stator of an AC electrical machine. When the 'feeler' is moved over a slot containing the shorted coil _____________. ... . the meter needle will be deflected to zero D. the meter needle will be deflected to full-scale

Last Answer : Answer: A

Description : When using a megohmmeter to test the dielectric strength of wire insulation, a continuous series of slight downscale kicks by the pointer is result of ____________. A. good insulation B. the ... dirty insulation C. the capacitance of the windings D. the dielectric-absorption effect of the insulation

Last Answer : Answer: B

Description : When a megohmmeter is used to test the dielectric strength of wire insulation, the initial dip of the pointer toward 'zero' is caused by _____________. A. good insulation B. the leakage of ... of dirty insulation C. the capacitance of the circuit D. the dielectric absorption effect of the insulation

Last Answer : Answer: C

Description : A switchboard ammeter indicates a reading slightly above 'zero' when the leads are disconnected, this is caused by _____________. A. mechanical misalignment of the meter pointer B. a poor ground for the meter case C. static electricity in the air D. capacitors inside the meter storing charges

Last Answer : Answer: A

Description : Before measuring an unknown resistance with an ohmmeter, you should _____________. A. adjust the meter's pointers to mid-scale B. change the meter's batteries C. center the meter's pointer at infinity D. short the test leads and calibrate the meter

Last Answer : Answer: D

Description : A megohmmeter can be used to test for _____________. A. an open field coil B. a shorted field pole C. undercut mica D. reversed polarity

Last Answer : Answer: A

Description : The leads from a megohmmeter are attached to the leads of an AC motor field coil. A reading of infinity is obtained indicating a/an ____________. A. open field coil B. shorted field coil C. grounded field coil D. shunted field coil

Last Answer : Answer: A

Description : The insulation resistance of electric equipment and machinery should be tested for the lowest normal insulation values _____________. A. immediately after shutting down the machine B. every time the brush rigging is ... starting up the machine D. every 30 days whether the machine is in use or not

Last Answer : Answer: A

Description : A grounded switch or cable will be indicated by a megohmmeter reading of _____________. A. infinity B. 'zero' C. being unsteady in the high range D. being unsteady in the low range

Last Answer : Answer: B

Description : Prior to taking a resistance reading with a volt-ohm-milliammeter, the 'zero' setting must be adjusted. After clipping the two leads together, you find the adjustment knob will not return the pointer ... range setting B. weak batteries C. a faulty zero ohms knob D. a faulty meter movement

Last Answer : Answer: B

Description : You are calibrating a multimeter using internal batteries to supply power for resistance measurements. However, you are unable to adjust the pointer to 'zero' using the adjustment knob. Therefore, you should ... change scales to the R X 100 scale and adjust using the 'zero ohms' adjusting knob

Last Answer : Answer: A

Description : Prior to using an analog type ohmmeter, the leads are purposely shorted together. Which of the following actions should be taken if, when adjusting to 'zero' ohms, the indicating needle can not be ... be added to each final reading. D. The test reading should be subtracted from each final reading.

Last Answer : Answer: B

Description : If the voltage applied to a moving disk frequency meter decreases, while the applied frequency remains the same, the frequency indication will _____________. A. increase B. decrease C. remain the same D. oscillate

Last Answer : Answer: C

Description : If you obtain a low resistance reading with a megohmmeter connected between terminals 'A' and 'C' of the three-phase, wye-connected winding shown in the illustration, there is __________. EL-0074 A. no open circuit ... 'B' C. an open circuit between 'A' and 'C' D. an open circuit in both windings

Last Answer : Answer: A

Description : A resistance in a circuit of unknown value is to be tested using the voltmeter/ammeter method. Therefore, the meters should be connected with _____________. A. both meters in series with the ... parallel with the resistance D. the ammeter in parallel and the voltmeter in series with the resistance

Last Answer : Answer: C

Description : When a megohmmeter is used to test the insulation of a large motor, the initial dip of the pointer toward 'zero' is caused by ____________. A. good insulation B. the capacitance of the ... of the current along the surface of dirty insulation D. the dielectric-absorption effect of the insulation

Last Answer : Answer: B

Description : When troubleshooting motor controllers, a shorted relay or contactor coil is often indicated by _______________. A. a resistance reading of 'infinity' on an ohmmeter B. charred insulation and/or a blown ... of the coil's leads to ground D. a higher-than-normal voltage reading across the winding

Last Answer : Answer: B

Description : When testing a capacitor with an analog type ohmmeter, a good capacitor will be indicated when _____________. A. there is no meter deflection B. the meter deflects to a low resistance value and ... deflects to a low resistance value and increases rapidly to a higher value, but stays fairly low

Last Answer : Answer: C

Description : If reading AC current with the illustrated device and unsure of the range as a precaution , the first step should be to _________. EL-0047 A. secure power and test for voltage B. disconnect the ... resistance and use Ohm's law to calculate current D. unable to safely measure current with the device

Last Answer : Answer: A

Description : If the pointer on a megger fails to return to 'zero' when not being used, the _____________. A. megger is out of calibration B. megger is operating normally C. hairsprings are burned out D. pointer probably stuck in that position

Last Answer : Answer: B

Description : The resistance of most conducting materials will change as a result of temperature change. The resistance of copper will _____________. A. increase as temperature decreases B. decrease as temperature decreases C. remain the same between 20°F and 110°F D. remain the same between 68°F and 230°F

Last Answer : Answer: B

Description : The final step in testing a circuit for a ground involves the use of a megohmmeter. A grounded switch or cable will be indicated by a megohmmeter reading of ____________. A. 'zero' B. infinity C. steady in the high range D. unsteady in the low range

Last Answer : Answer: A

Description : When troubleshooting electronic equipment, you should use a high impedance multimeter ________________. A. to prevent excess current flow through the meter that would damage it B. for AC measurements only ... being tested D. so as not to load down the circuit and obtain erroneous voltage readings

Last Answer : Answer: D

Description : Which of the listed statements is correct when using an analog multimeter as an ohmmeter? A. The pointer should be adjusted to zero each time a new resistance range is selected. B. The ... C. Ohmmeters are not sufficiently sized to measure conductor insulation resistance. D. All of the above.

Last Answer : Answer: D

Description : When using a multimeter for resistance measurements, it should be calibrated by clipping the loose ends of the leads together and _____________. A. setting the instrument pointer at 'zero' ohms B. ... the plus and minus terminals D. using a special purpose resistance measuring instrument (a bridge)

Last Answer : Answer: A

Description : When shipboard electrical distribution circuits are connected in parallel, additional parallel circuits will cause the total circuit resistance to _____________. A. increase, causing a drop in the line current B ... an increase in the line voltage D. decrease, causing an increase in the line current

Last Answer : Answer: D

Description : A milliammeter, with a full scale deflection reading of 100 milliamps, is known to have an accuracy of + or - 2%. A meter reading of 10 milliamps would indicate a line current of between _____________. A. 9.8 ... 9.8 and 10.2 milliamperes C. 8.0 and 12.0 milliamperes D. 8.0 and 10.0 milliamperes

Last Answer : Answer: B

Description : In which of the situations listed will a megohmmeter give the most accurate readings? A. While the machine is in operation. B. While the machine is discharging static electricity. C. Immediately prior to ... machine. D. When the machine has been shut down and grounded for a period of 15 minutes.

Last Answer : Answer: D

Description : A megohmmeter is connected to each end of an individual motor winding. A low ohm reading indicates ____________. A. an open coil B. a loose coil C. good continuity D. a dirty coil

Last Answer : Answer: C

Description : When used for taking resistance measurements, a volt-ohm-milliammeter is normally powered by _____________. A. a hand cranked generator B. internal storage batteries C. the current in the circuit being tested D. a step down transformer

Last Answer : Answer: B

Description : To test fuses in an energized circuit, you should use a ____________. A. low voltage light bulb B. megohmmeter C. voltmeter D. resistance meter

Last Answer : Answer: C

Description : When a capacitor was connected to the terminal of ohmmeter, the pointer indicated a low resistance initially and then slowly came to infinity position. This shows that capacitor is ?

Last Answer : When a capacitor was connected to the terminal of ohmmeter, the pointer indicated a low resistance initially and then slowly came to infinity position. This shows that capacitor is all right.

Description : When paralleling two alternators, the synchronizing lamps remain lit as the synchroscope pointer approaches the 0°. This indicates the _____________. A. incoming alternator is running too fast B. alternator ... apart C. synchroscope is defective or broken D. alternator power factors are in phase

Last Answer : Answer: C

Description : In testing a three-phase delta winding for an open circuit using a megohmmeter, you must ______________. A. test each phase with all connections intact B. measure the voltage across the open ... groups to avoid short circuiting D. open the delta-connections to avoid shunting the phase being tested

Last Answer : Answer: D

Description : In a boundary layer developed along the flow, the pressure decreases in the downstream direction. The boundary layer thickness in this case will (A) Decrease gradually (B) Increase gradually (C) Increase rapidly (D) Remain constant

Last Answer : (B) Increase gradually

Description : To carry out an insulation resistance test, one terminal of the megohmmeter should be connected to the winding, with the other terminal being connected to the ____________________. A. power supply B. variable resistor C. frame of the machine D. armature

Last Answer : Answer: C

Description : When a resistor is used as a shunt and is connected in parallel with a meter movement coil, it will provide _____________. A. a measurement of circuit resistance B. an increased accuracy of approximately 1.5 percent C. an extended meter range D. none of the above

Last Answer : Answer: C

Description : An AC generator produces 60 Hz at 1800 RPM. If the generator speed is increased to 1830 RPM, the cycles will _____________. A. remain at 60 Hz B. increase to 61 Hz C. decrease to 59 Hz D. increase to 63 Hz

Last Answer : Answer: B

Description : A good choice of shunt resistance will place the indicating pointer near what part of the meter scale with a normal load?

Last Answer : Midscale.