When a megohmmeter is being used to test insulation resistance, current leakage along the surface of the insulation is indicated by the megohmmeter pointer _____________. A. fluctuating around a constant resistance reading  B. dipping towards 'zero', then rising slowly C. kicking slightly downscale as voltage is applied D. continually rising as the test voltage is applied

1 Answer

Answer :

Answer: C

Related questions

Description : When a megohmmeter is being used to test insulation resistance, current leakage along the surface of the insulation is indicated by the megohmmeter's pointer _____________. A. dipping toward ... kicking slightly down scale as voltage is applied D. fluctuating around a constant resistance reading

Last Answer : Answer: C

Description : When using a megohmmeter to test the dielectric strength of wire insulation, a continuous series of slight downscale kicks by the pointer is result of ____________. A. good insulation B. the ... dirty insulation C. the capacitance of the windings D. the dielectric-absorption effect of the insulation

Last Answer : Answer: B

Description : When a megohmmeter is used to test insulation, the gradual rise of the pointer reading as a result of continued cranking, is caused by _____________. A. good conductor resistance B. the ... insulation C. the inductive reactance of the windings D. the dielectric-absorption effect of the insulation

Last Answer : Answer: D

Description : When a megohmmeter is used to test the dielectric strength of wire insulation, the initial dip of the pointer toward 'zero' is caused by _____________. A. good insulation B. the leakage of ... of dirty insulation C. the capacitance of the circuit D. the dielectric absorption effect of the insulation

Last Answer : Answer: C

Description : When a megohmmeter is used to test the insulation of a large motor, the initial dip of the pointer toward 'zero' is caused by ____________. A. good insulation B. the capacitance of the ... of the current along the surface of dirty insulation D. the dielectric-absorption effect of the insulation

Last Answer : Answer: B

Description : When using a megohmmeter to test insulation, good insulation will be indicated by _____________. A. slight kicks of the needle down scale B. a downward dip followed by a gradual climb to the true resistance ... C. a gradual rise in the pointer reading at the outset D. the initial dip of the pointer

Last Answer : Answer: B

Description : When a megohmmeter is being used on a alternating current machine, the meter pointer will dip toward 'zero' and then gradually rise to the true resistance value if the motor insulation is _____________. A. grounded B. good C. shorted D. dirty

Last Answer : Answer: B

Description : A capacitor is to be tested with a megohmmeter. If the meter is connected to a shorted capacitor, the meter pointer should _____________. A. immediately swing to the maximum resistance value ... and gradually decrease D. swing to zero then gradually increase with slight pointer movements down scale

Last Answer : Answer: B

Description : A capacitor can be tested using a megohmmeter or an ohmmeter. If the meter is connected to a shorted capacitor, the meter pointer should _____________. A. immediately swing to the maximum resistance ... deflect to and remain at zero D. immediately swing to a high reading and then gradually decrease

Last Answer : Answer: C

Description : A grounded switch or cable will be indicated by a megohmmeter reading of _____________. A. infinity B. 'zero' C. being unsteady in the high range D. being unsteady in the low range

Last Answer : Answer: B

Description : Before testing insulation with a megohmmeter, the windings of large machines should be grounded for about 15 minutes just prior to the test, because the ___________. A. static charge of the machine ... number of leakage paths C. insulation may be damaged D. insulation may be covered with moisture

Last Answer : Answer: A

Description : A low voltage source is being used for testing armature coils. A coil short circuit will be indicated by a _______. A. high voltage reading, while the other coil readings will have an ... the other coil readings are steady D. steady voltmeter reading, while the other coil readings are fluctuating

Last Answer : Answer: B

Description : A switchboard ammeter indicates a reading slightly above 'zero' when the leads are disconnected, this is caused by _____________. A. mechanical misalignment of the meter pointer B. a poor ground for the meter case C. static electricity in the air D. capacitors inside the meter storing charges

Last Answer : Answer: A

Description : Which of the following conditions indicates a short circuited capacitor when checking its condition with an ohmmeter? A. The capacitor shows charging, but the final resistance reading is appreciably less ... moves quickly to the low resistance side of the scale, then slowly recedes toward infinity.

Last Answer : Answer: B

Description : When troubleshooting motor controllers, a shorted relay or contactor coil is often indicated by _______________. A. a resistance reading of 'infinity' on an ohmmeter B. charred insulation and/or a blown ... of the coil's leads to ground D. a higher-than-normal voltage reading across the winding

Last Answer : Answer: B

Description : When testing a capacitor with an analog type ohmmeter, a good capacitor will be indicated when _____________. A. there is no meter deflection B. the meter deflects to a low resistance value and ... deflects to a low resistance value and increases rapidly to a higher value, but stays fairly low

Last Answer : Answer: C

Description : Before testing insulation with a megohmmeter, the windings of large machines should be grounded for about 15 minutes just prior to the test as the ______________. A. insulation may be damaged ... number of leakage paths D. larger machines may acquire a charge of static electricity during operation

Last Answer : Answer: D

Description : Before measuring an unknown resistance with an ohmmeter, you should _____________. A. adjust the meter's pointer to mid-scale B. short the test leads and calibrate the meter reading to 'zero' C. change the meter's batteries D. center the meter's pointer at infinity

Last Answer : Answer: B

Description : You are testing the insulation in an AC generator with a megohmeter. The resistance value of a dry, clean winding will ____________. A. continue to rise as the test potential is maintained, ... fairly steady after 5 to 7 minutes D. stabilize after approximately 2 to 4 minutes of fluctuation

Last Answer : Answer: A

Description : When using a multimeter for resistance measurements, it should be calibrated by clipping the loose ends of the leads together and _____________. A. setting the instrument pointer at 'zero' ohms B. ... the plus and minus terminals D. using a special purpose resistance measuring instrument (a bridge)

Last Answer : Answer: A

Description : The final step in testing a circuit for a ground involves the use of a megohmmeter. A grounded switch or cable will be indicated by a megohmmeter reading of ____________. A. 'zero' B. infinity C. steady in the high range D. unsteady in the low range

Last Answer : Answer: A

Description : To carry out an insulation resistance test, one terminal of the megohmmeter should be connected to the winding, with the other terminal being connected to the ____________________. A. power supply B. variable resistor C. frame of the machine D. armature

Last Answer : Answer: C

Description : When you are using an ohmmeter to test a transistor for leakage, what is indicated by a low, but not shorted, reverse resistance reading?

Last Answer : A leaking transistor

Description : Multiple grounds have developed and were initialy indicated by the grounddetecting system as one ground. The FIRST step in locating the grounds is to _____________. A. examine the main bus bars ... no longer indicates any grounds C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : A ground is indicated by the ground-detecting system on the main electrical switchboard. The FIRST step in locating the actual ground is to _____________. A. close all circuit breakers in ... ground detection system indicates normal C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : If the resistance of a circuit is cut in half and the applied voltage is kept constant, the current flow will be _____________. A. doubled B. quadrupled C. unchanged D. cut in half

Last Answer : Answer: A

Description : Which of the listed statements is correct when using an analog multimeter as an ohmmeter? A. The pointer should be adjusted to zero each time a new resistance range is selected. B. The ... C. Ohmmeters are not sufficiently sized to measure conductor insulation resistance. D. All of the above.

Last Answer : Answer: D

Description : The insulation of electric generators during short idle periods should be _____________. A. allowed to cool slowly to ambient temperatures B. flashed with direct current to remove any residual ... using strip or space heaters D. relieved of all capacitive charge by grounding the conductors

Last Answer : Answer: C

Description : Before using a volt-ohmmeter to measure resistance readings, you should _____________. A. replace all batteries B. test the insulation resistance of the leads C. make sure the test leads do not touch D. hold the leads together and 'zero' the meter

Last Answer : Answer: D

Description : A megohmmeter is used to measure _____________. A. voltage B. dielectric strength C. current D. power

Last Answer : Answer: B

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : Which of the instruments listed is used to check insulation resistance? A. Magneto B. Megohmmeter C. Dynamometer D. Rheostat

Last Answer : Answer: B

Description : A ground on a particular phase of a three-phase low voltage distribution system would be indicated by a _____________. A. high switchboard wattmeter reading B. low switchboard wattmeter reading C. dark or dim switchboard ground detecting light D. bright switchboard ground detecting light

Last Answer : Answer: C

Description : The true power indicated by the pointer movement of a wattmeter depends on the current flow through the load, the magnitude of the potential across the load, and the ____________. A. power factor of the ... B. angle of coil displacement C. inertia of the movable coil D. high resistance from the load

Last Answer : Answer: A

Description : To properly use a hook-on-type volt/ammeter to check current flow, you must FIRST _____________. A. de-energize the circuit to allow connection of the instrument in series B. hook the jaws ... test leads to the appropriate terminals D. short the test leads and calibrate the instrument to zero

Last Answer : Answer: B

Description : You are calibrating a multimeter using internal batteries to supply power for resistance measurements. However, you are unable to adjust the pointer to 'zero' using the adjustment knob. Therefore, you should ... change scales to the R X 100 scale and adjust using the 'zero ohms' adjusting knob

Last Answer : Answer: A

Description : When you are making a high potential test on a piece of repaired electrical machinery, a rise in leakage current indicates ____________. A. good insulation B. bad insulation C. high insulation power factor D. a high slot discharge factor

Last Answer : Answer: B

Description : Prior to taking a resistance reading with a volt-ohm-milliammeter, the 'zero' setting must be adjusted. After clipping the two leads together, you find the adjustment knob will not return the pointer ... range setting B. weak batteries C. a faulty zero ohms knob D. a faulty meter movement

Last Answer : Answer: B

Description : To test fuses in an energized circuit, you should use a ____________. A. low voltage light bulb B. megohmmeter C. voltmeter D. resistance meter

Last Answer : Answer: C

Description : An ammeter reads slightly above 'zero' when its leads are disconnected, this is a result of ___________. A. mechanical misalignment of the meter pointer B. a poor ground for the meter case C. static electricity in the air D. resistors inside the meter storing charges

Last Answer : Answer: A

Description : A current-carrying conductor making electrical contact with a wiring conduit will be indicated by a _____________. A. high switchboard wattmeter reading B. totally dark switchboard ground detecting light C. low switchboard wattmeter reading D. all of the above

Last Answer : Answer: B

Description : A current-carrying conductor makes accidental contact with a wiring conduit. This will be indicated by a _____________. A. low switchboard wattmeter reading B. high switchboard wattmeter reading C. darkened switchboard ground detecting lamp D. darkened switchboard synchronizing lamps

Last Answer : Answer: C

Description : A current carrying conductor making an electrical contact with a wiring metal conduit is indicated by a _____________. A. low switchboard wattmeter reading B. reading of 1.0 on the power factor meter C. high switchboard voltmeter reading D. totally darkened switchboard ground-detecting light

Last Answer : Answer: D

Description : If the pointer on a megger fails to return to 'zero' when not being used, the _____________. A. megger is out of calibration B. megger is operating normally C. hairsprings are burned out D. pointer probably stuck in that position

Last Answer : Answer: B

Description : A short in the shunt field of a DC motor is best located by _____________. A. visual inspection of the commutator B. applying AC voltage to each field coil and measuring the voltage drop across ... using a growler and hacksaw blade D. isolating each coil from the others and using a megohmmeter

Last Answer : Answer: B

Description : Before measuring an unknown resistance with an ohmmeter, you should _____________. A. adjust the meter's pointers to mid-scale B. change the meter's batteries C. center the meter's pointer at infinity D. short the test leads and calibrate the meter

Last Answer : Answer: D

Description : A multimeter may be damaged by taking a _____________. A. voltage reading while in the ammeter mode B. current reading while in the voltmeter mode C. resistance reading while in the ammeter mode D. resistance reading while in the voltmeter mode

Last Answer : Answer: A