Two paralleled alternators are operating near rated load. If one trips out mechanically, which of the listed actions should be taken FIRST? A. Restart the tripped machine immediately. B. Strip the board of all non-vital circuits. C. Start the emergency generator. D. Transfer all vital loads to the emergency bus.

1 Answer

Answer :

Answer: B

Related questions

Description : Diesel generators #1 and #2 are operating in parallel at near full load capacity. Diesel generator #1 suddenly trips out mechanically due to low lube oil pressure. The reverse power relay functions ... all nonvital circuits. D. Secure alarms, reset reverse power relay, and restart #1 engine.

Last Answer : Answer: C

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation of the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. type of alternator

Last Answer : Answer: B

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation to the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. number of field poles per alternator

Last Answer : Answer: B

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description : Which of the listed sections of an emergency switchboard is used to supply power for alarm signals under emergency conditions? A. The generator and bus transfer section B. The 450 volt, 60 cycle, 3 phase bus C. The 120 volt, 3 phase, 60 cycle bus D. The 24 volt DC bus

Last Answer : Answer: D

Description : The graph shown in the illustration represents the speed droop curves of two equal capacity alternators about to be paralleled. When paralleled, the greater portion of the total load above 60% for each unit will be picked up ... unit 'A' B. by unit 'B' C. equally by each unit D. none of the above

Last Answer : Answer: A

Description : On a vessel with turbo-electric drive, which of the following conditions would indicate that the propulsion motor had dropped out of synchronization with the propulsion generator? A. Excessive ... Tripped main motor interlocks C. Overheated crosstie busses D. Closed contact in the field circuits

Last Answer : Answer: A

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Description : Why is it a good practice to have the frequency of the incoming alternator adjusted slightly higher than that of the loaded alternator when paralleling two alternators? A. This allows the oncoming machine to ... line. C. The reverse power relay is prevented from activating. D. All of the above.

Last Answer : Answer: D

Description : A diesel driven emergency generator is prevented from being paralleled with the ship's service generators by __________. A. an electrical interlock system B. an automatic paralleling trip switch C. the synchronizing oscilloscope D. the reverse current relay

Last Answer : Answer: A

Description : Two alternators rated are 200 KW at 4% regulation, 400 KW 5% regulation operating in parallel at 50HZ , when supply 600 KW the new frequency is a) 50 b) 49 c) 51.3 d) 47.7

Last Answer : Ans: 47.7

Description : When paralleling two AC generators, the frequency of the machine coming online, immediately prior to closing its breaker, should be ____________. A. slightly less than the oncoming generator frequency B. the ... bus frequency C. slightly greater than the bus frequency D. the same as the bus voltage

Last Answer : Answer: C

Description : The kilowatt load can be adjusted on a paralleled generator by using the _____________. A. field rheostat B. governor control C. automatic voltage regulators D. hand tachometer

Last Answer : Answer: B

Description : When paralleling two alternators using three synchronizing lamps, the flickering of all three lamps becomes progressively slower and slower. This means the ______________. A. frequency of the incoming ... the bus D. terminal voltage of the incoming alternator is approaching that of the bus

Last Answer : Answer: A

Description : Upon failure of the normal power supply, the emergency generator is placed on the line by the _____________. A. bus tie feeder B. automatic bus transfer device C. line connection feeder D. power failure alarm bus

Last Answer : Answer: B

Description : Upon failure of the normal power supply, the emergency generator is placed on the line by the _____________. A. main bus tie feeder B. automatic bus transfer device C. line connection feeder D. power failure alarm bus

Last Answer : Answer: B

Description : The power factor of an AC generator operating singularly is determined by the __________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: A

Description : In the illustration, the component labeled 'EXC' is _______. EL-0003 A. a separate class II regulated DC generator for critical direct current loads B. a generator feeding the FLD ... to drive the governor for turbogenerator speed. D. the electronic driver for the switchboard metering circuits

Last Answer : Answer: B

Description : How will a molded-case circuit breaker react after it has tripped, as a result of an overloaded circuit? A. The breaker will trip again if immediately reset. B. The breaker handle will lock in ... down. D. The breaker handle cannot be moved to the OFF position until the thermal element cools down.

Last Answer : Answer: A

Description : Which of the listed items will stop a motor due to a reduction in voltage and restart it when the voltage is restored to normal? A. Low voltage protection circuit B. Non-renewable link fuse C. Renewable link fuse D. Low voltage release circuit

Last Answer : Answer: D

Description : Where automatic restart does not present a hazard after a power failure, Coast Guard Regulations (46 CFR) require motor controllers for auxiliaries vital to the propelling equipment to be provided ... overload protection B. low voltage protection C. low voltage release D. reverse current protection

Last Answer : Answer: C

Description : The type of feature afforded auxiliaries vital to the operation of propelling equipment, where automatic restart after a voltage failure would not create a hazard, is termed _____________. A. low voltage protection B. high amperage protection C. low voltage release D. high amperage release

Last Answer : Answer: C

Description : The 'function generator' of the control circuit illustrated _______________. EL-0095 A. can be programmed to produce a non-linear output for a linear input depending on operating conditions B. is used for ... which or how many engines are needed for a required vessel speed D. all of the above

Last Answer : Answer: A

Description : The schematic diagram shown in the illustration represents which of the listed solid-state circuits? EL-0069 A. Bridge rectifier B. Magnetic amplifier C. Flip-flop generator D. Cathodic amplifier

Last Answer : Answer: A

Description : Two 3-phase, Y-connected alternators are to be paralleled to a set of common busbars. The armature has a per phase synchronous reactance of 1.7 Ohm and negligible armature resistance. The line voltage of the first machine is adjusted to ... will be  (A) 16.98 A (B) 29.41 A (C) 33.96 A (D) 58.82 A

Last Answer : Two 3-phase, Y-connected alternators are to be paralleled to a set of common busbars. The armature has a per phase synchronous reactance of 1.7 Ohm and negligible armature resistance. The ... instant they are paralleled. Under this condition, the synchronizing current per phase will be 16.98 A

Description : An insulation resistance test is performed on a particular piece of electric equipment. In addition to the resistance reading, what information listed below should be entered in the electrical log? A. ... D. The complete nameplate data from the resistance test instrument used to obtain the reading.

Last Answer : Answer: B

Description : An alternator operating in parallel begins to vibrate severely and eventually trips out on the reverse power relay. The cause of the vibration was a result of ______________________. A. the ... C. the alternator was operating out of synchronism D. flashover at the alternator collector rings

Last Answer : Answer: C

Description : The load sharing characteristics of two diesel alternators operating in parallel are directly related to the setting of their governors' ____________. A. load limit B. idle speed C. speed limit D. speed droop

Last Answer : Answer: D

Description : If the excitation is increased to one of two alternators operating in parallel, the _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. kilowatt load will be greatly increased D. ampere load will be greatly decreased

Last Answer : Answer: A

Description : To equalize the power factor of two alternators operating in parallel, the ____________. A. field excitation of both units is adjusted B. governors of both units are adjusted C. phase sequence is altered D. kilowatt load is evenly divided

Last Answer : Answer: A

Description : A shore power circuit breaker should be closed only _____________. A. when the ship's generators have been directly paralleled to those on shore B. in a shipyard C. if a quick disconnect coupling is used D. when the ship's generators have been removed from the bus

Last Answer : Answer: D

Description : In electronic circuits, DC voltages can be positive (+) or negative (-) when measured with respect to the _________. A. printed circuit board 'common' trace B. chassis, console frame or hull 'ground' C. analogue or digital circuitry 'common' bus D. all of the above

Last Answer : Answer: D

Description : When the operating handle of a molded case circuit breaker is in the mid-position, it indicates the circuit breaker is _____________. A. in the 'opened' position B. in the 'closed' position C. tripped D. reset

Last Answer : Answer: C

Description : When the operating handle of a molded-case circuit breaker is in the mid-position, the circuit breaker is indicated as being ____________. A. in the 'closed' position B. in the 'opened' position C. tripped D. reset

Last Answer : Answer: C

Description : When the operating handle of a molded-case circuit breaker is in the mid-position, this indicates that the circuit breaker is _____________. A. on B. off C. reset D. tripped

Last Answer : Answer: D

Description : When working on electrical circuits containing large capacitors, in addition to deenergizing the circuit, which of the listed precautions should also be taken? A. Keep all radio equipment ... capacitor insulation resistance. C. Ground the capacitor terminals. D. Check capacitor circuit polarity.

Last Answer : Answer: C

Description : According to Coast Guard Regulation (46 CFR) for emergency power and lighting systems, which of the listed items is the only permissible starting aid for the emergency diesel generator engine? A. Ether B. Lube oil heater C. Jacket water heater D. Fuel oil heater

Last Answer : Answer: C

Description : An equalizing connection between two compound-wound DC generators when paralleled, serves to _____________. A. reverse the polarity of the incoming generator as the series field weakens B. automatically ... the series field of the incoming generator D. parallel the series fields of the generators

Last Answer : Answer: D

Description : If the centrifugal switch or relay used for cutting out the starting winding of a split-phase induction motor fails to open once the motor is in operation, the _____________. A. motor will overspeed B ... C. motor will immediately stall under load D. motor torque will be above normal at rated speed

Last Answer : Answer: B

Description : Why is it desirable to operate paralleled AC generators at the same power factor? A. Circulating currents are kept to a minimum. B. Field excitation losses are kept to a minimum. C. Generator ... will have a lesser tendency to hunt. D. Because a power factor increase will decrease kilowatt output.

Last Answer : Answer: A

Description : In the illustration, if one of the devices labeled 'TURB' should fail the ___________. EL-0003 A. device labeled 'EXC' will drive the alternator B. device labeled 'BKR' for that ... -alternator D. emergency generator should automatically start and be placed on line to supply emergency load centers

Last Answer : Answer: B

Description : Due to the operating characteristics of the system, time lag fuses (or dual-element fuses) are necessary for use in _____________. A. main lighting circuits B. motor starting circuit C. emergency lighting circuits D. general alarm circuits

Last Answer : Answer: B

Description : If the pointer of the synchroscope is rotating in the slow direction when you are preparing to parallel two alternators, the _____________. A. incoming machine is turning faster than the load alternator B ... alternator is ready to split D. incoming machine is beginning to pick up some of the load

Last Answer : Answer: B

Description : In which of the situations listed will a megohmmeter give the most accurate readings? A. While the machine is in operation. B. While the machine is discharging static electricity. C. Immediately prior to ... machine. D. When the machine has been shut down and grounded for a period of 15 minutes.

Last Answer : Answer: D

Description : Handheld phase sequence indicators are useful when ________. A. preparing to parallel alternators B. connecting lighting branch circuits C. troubleshooting DC motors D. connecting shore power lines to the ship

Last Answer : Answer: D