If all three ground-detection lamps continue to burn at equal intensity after the test button is depressed and released, which of the listed conditions is indicated? A. No grounds exist B. All three phases are grounded C. The test switch is faulty D. The current transformers are shorted out

1 Answer

Answer :

Answer: A

Related questions

Description : On a switchboard, if all three ground detection lamps remain burning at half intensity when the test button is depressed, which of the listed conditions is indicated? A. No grounds exist. B. All three phases are grounded. C. The test switch is grounded. D. The current transformers are shorted.

Last Answer : Answer: A

Description : If all of the ground detection lamps burn with equal brilliance, whether the test button is depressed or released, then ___________. A. no grounds exist B. all phases are grounded C. all lamps show a ground D. all of the above

Last Answer : Answer: A

Description : A three-phase electrical system is equipped with ground detecting lamps. If one of the lamp goes dark and the other two burn normally before and after the test switch is operated, this indicates _______________. ... of the three phases D. the voltage to the dark lamp is less than that of the system

Last Answer : Answer: A

Description : In a three-phase electrical system, three ground detecting lamps are provided. If all three lamps REMAIN at half-brilliance when the ground detecting test switch is operated, ______________. A. there is a ... must be replaced C. there are no grounds present D. the light bulbs are of improper voltage

Last Answer : Answer: C

Description : In a three-phase electrical system, three ground detecting lamps are provided. One lamp goes dark and the others increase in brightness. When the test button is pushed, all lamps have equal illumination. You ... C. there are grounds on the lines with the bright lamps D. this is a normal condition

Last Answer : Answer: A

Description : The circuit illustrated represents a 2 wire DC ground detecting system. If the positive bus is grounded and the test button is pushed, which of the lamps will be brightest? EL-0008 A. X B. Y C. both will be equal brightness. D. both will go out.

Last Answer : Answer: C

Description : In the illustrated ground detection system with a ground on phase A, if the switch is opened __________. EL-0009 A. lamp A will dim or go out depending on the severity of the ground B. all three ... lamp A will be brighter D. lamp A will start flickering if the ground is in an AC induction motor

Last Answer : Answer: B

Description : The ground detection system, shown in the illustration for a low-voltage, threephase system has a ground in line 'A'. Therefore, lamp 'A' will burn ____________. EL-0009 A. dimly or be out, and lamps 'B' and ... and 'C' will burn dimly or be out D. brightly, and lamps 'B' and 'C' will burn normally

Last Answer : Answer: A

Description : As shown in the illustration, which listed action will occur first when push button 'Q' is depressed? EL-0017 A. Contacts 'H-1', 'H-2' and 'H-3' close. B. Contact 'H-4' closes. C. Operating coil 'C' energizes. D. Switch 'R' opens.

Last Answer : Answer: C

Description : The final step in testing a circuit for a ground involves the use of a megohmmeter. A grounded switch or cable will be indicated by a megohmmeter reading of ____________. A. 'zero' B. infinity C. steady in the high range D. unsteady in the low range

Last Answer : Answer: A

Description : A ground in an electrical circuit outside the engine room _____________. A. cannot be detected under normal conditions B. is of no consequence to engineering personnel C. is indicated at the branch circuit breaker panel D. is indicated by the ground detecting lamps on the main switchboard

Last Answer : Answer: D

Description : The motor starts when the start button in the illustration is pushed, but stops when the button is released the trouble is _________. EL-0007 A. the incorrect thermal overload coil B. a faulty 'M' coil C. a dirty contact on the Disc.Sw. at 'L3' D. a faulty holding relay contact

Last Answer : Answer: D

Description : A current-carrying conductor makes accidental contact with a wiring conduit. This will be indicated by a _____________. A. low switchboard wattmeter reading B. high switchboard wattmeter reading C. darkened switchboard ground detecting lamp D. darkened switchboard synchronizing lamps

Last Answer : Answer: C

Description : The circuit illustrated represents a single phase AC ground detecting system. If a ground occurs on line 'B', which of the lamps will burn the brightest? EL-0008 A. X B. Y C. Both will be equal brightness. D. both will go out.

Last Answer : Answer: A

Description : When using the test set-up shown in the illustration, the lighted lamp indicates the winding is ____________. EL-0027 A. grounded B. good C. open D. shorted

Last Answer : Answer: A

Description : When troubleshooting motor controllers, a shorted relay or contactor coil is often indicated by _______________. A. a resistance reading of 'infinity' on an ohmmeter B. charred insulation and/or a blown ... of the coil's leads to ground D. a higher-than-normal voltage reading across the winding

Last Answer : Answer: B

Description : Multiple grounds have developed and were initialy indicated by the grounddetecting system as one ground. The FIRST step in locating the grounds is to _____________. A. examine the main bus bars ... no longer indicates any grounds C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : A grounded switch or cable will be indicated by a megohmmeter reading of _____________. A. infinity B. 'zero' C. being unsteady in the high range D. being unsteady in the low range

Last Answer : Answer: B

Description : You are using a mechanical voltage tester to check the fuses in a three-phase circuit supplying an electric motor. For which of the following reasons must the motor be stopped during the test? A. ... circuit would be indicated by the voltage tester with the circuit energized. D. All of the above.

Last Answer : Answer: B

Description : Accidental grounds in a shipboard electrical system must be repaired as soon as possible as they will ____________. A. result in immediate power outages B. damage circuit breakers C. appear on the ground detection system D. damage insulation and may cause outages

Last Answer : Answer: D

Description : When a megohmmeter is being used on a alternating current machine, the meter pointer will dip toward 'zero' and then gradually rise to the true resistance value if the motor insulation is _____________. A. grounded B. good C. shorted D. dirty

Last Answer : Answer: B

Description : To determine if a stator coil is grounded, you should use a/an _____________. A. ammeter B. ground detection lamp C. magneto D. megger

Last Answer : Answer: D

Description : A basic premise underlying analytical procedures is that a. The study of financial ratios is an acceptable alternative to the investigation of unusual fluctuations. b. Plausible relationships ... financial information may lead to the detection of material misstatements in the financial statements.

Last Answer : Plausible relationships among data may reasonably be expected to exist and continue in the absence of known conditions to the contrary.

Description : The illustrated motor fails to start and gives a loud hum when the start button is depressed, your first action should be to __________. EL-0007 A. disassemble the motor to fix the centrifical ... D. hold the 'M' contactor closed by hand while wearing electrical safety gloves to get motor started

Last Answer : Answer: B

Description : Which of the following represents a characteristic of an ungrounded electrical distribution system? A. Accidental contact between one line and ground does not cause an outage. B. Double ground faults on ... unnecessary. D. Accidental contact between one line and ground will always cause an outage.

Last Answer : Answer: A

Description : Which of the listed conditions might contribute to very rapid wearing of a DC machine's commutator bars? A. A grounded commutator bar B. Using improper carbon brushes C. Aligning the front and rear mica V-rings improperly D. An open circuit in the armature

Last Answer : Answer: B

Description : A ground is indicated by the ground-detecting system on the main electrical switchboard. The FIRST step in locating the actual ground is to _____________. A. close all circuit breakers in ... ground detection system indicates normal C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : The leads from a megohmmeter are attached to the leads of an AC motor field coil. A reading of infinity is obtained indicating a/an ____________. A. open field coil B. shorted field coil C. grounded field coil D. shunted field coil

Last Answer : Answer: A

Description : While testing a semi-conductor diode with an ohmmeter, both the forward and reverse readings are almost in the infinity range. This would indicate that the unit is _____________. A. good B. open C. grounded D. shorted

Last Answer : Answer: B

Description : When troubleshooting AC motors, a portable growler can be used for locating ____________. A. open field coils B. grounded field coils C. grounded stator coils D. shorted stator coils

Last Answer : Answer: D

Description : An open coil in a transformer will be indicated by which of the listed conditions? A. 'zero' resistance accompanied by high inductance B. no resistance accompanied by stray inductance C. infinite resistance in addition to no inductance D. infinite resistance in addition to normal inductance

Last Answer : Answer: C

Description : While paralleling two (2) AC generators using synchronizing lamps only, both lamps will go dark when the generators are ____________. A. running at the same speed B. grounded C. of the same polarity D. in phase

Last Answer : Answer: D

Description : In the illustrated test, if the lamp fails to light on any of the three windings then _________. EL-0027 A. all three windings are grounded and the motor should be sent out for repair B. ... the motor controller and the controller should be checked D. the test should be redone at a higher voltage

Last Answer : Answer: C

Description : A generator has been exposed to water and is being checked for its safe operation. Therefore, it is necessary to _______________. A. check for shorted coils with a growler B. take moisture readings with a ... a megger D. ground the commutator, or slip rings and run it at half load for 12 hours

Last Answer : Answer: C

Description : Which of the following conditions will occur if the solenoid coil burns out on a cargo winch with an electrical brake? A. The brake will be set by spring force. B. The motor will overspeed and burn ... the cargo boom will fall. D. Nothing will happen; the winch will continue to operate as usual.

Last Answer : Answer: A

Description : If the contacts of a motor starter or controller fail to drop out when the 'stop' button is depressed the ____________. A. contacts are carrying excessive current B. contacts have become welded together C. shading coil is broken D. shading coil is loose

Last Answer : Answer: B

Description : As a general rule, the first troubleshooting action to be taken in checking faulty electric control devices is to _____________. A. draw a one line diagram of the circuitry B. test all fuses and measure the line voltage C. take megger readings D. insulate the apparatus from ground

Last Answer : Answer: B

Description : When you are using an ohmmeter to test a transistor for leakage, what is indicated by a low, but not shorted, reverse resistance reading?

Last Answer : A leaking transistor

Description : Which of the listed conditions occur when selection is made for 'third point hoist' on the winch shown in the illustration? EL-0102 A. Master switch contacts '5', '6', '7', '8', and '9' close. B. Contactors '2M', ' ... ' and '2A' drop out. D. Master switch contacts '3','4', '6', '8', and '9' close.

Last Answer : Answer: D

Description : Which of the listed conditions occur when '4th point lower' is selected on the winch shown in the illustration? EL-0102 A. Master switch contacts '3', '4', '6', '8', '9', & '10' close. B. Contactors '2, 3, & 4M' and ' ... , '7', '8', and '9' close. D. Contactors '1 & 3M' and '1, 2, & 3A' pick up.

Last Answer : Answer: B

Description : If a D.C. motor hums, but does not run when energized, which of the listed conditions could exist? A. Incorrect lead connections B. Incorrect brush setting C. A dirty commutator D. All of the above are correct.

Last Answer : Answer: D

Description : In replacing a defective transformer with a new one, which of the following actions must be carried out to insure proper operation of the equipment it serves? A. The secondary leads must be grounded ... magnetize it. D. The iron core must be grounded for 10 minutes to remove any residual magnetism.

Last Answer : Answer: B

Description : If a single-phase induction motor fails to start, the problem may be _____________. A. an open in the main winding B. a shorted shunt field C. a closed centrifugal switch D. low circuit frequency

Last Answer : Answer: A

Description : If a single-phase induction motor fails to start, the problem may be _____________. A. an open in the run winding B. a shorted shunt field C. a closed centrifugal switch D. low circuit frequency

Last Answer : Answer: A

Description : The winch shown in the illustration will not operate in any speed in the lowering direction and at an abnormal speed in 'first point hoist'. The possible cause is that _______________. EL-0102 A. ... '1M' in the power circuit are badly corroded D. master switch contacts 'MS6' have weak springs

Last Answer : Answer: B