A three-phase electrical system is equipped with ground detecting lamps. If one of the lamp goes dark and the other two burn normally before and after the test switch is operated, this indicates _______________. A. the dark lamp must be replaced B. there is a ground in the line with the dark lamp C. there are grounds in two of the three phases D. the voltage to the dark lamp is less than that of the system

1 Answer

Answer :

Answer: A

Related questions

Description : In a three-phase electrical system, three ground detecting lamps are provided. If all three lamps REMAIN at half-brilliance when the ground detecting test switch is operated, ______________. A. there is a ... must be replaced C. there are no grounds present D. the light bulbs are of improper voltage

Last Answer : Answer: C

Description : In a three-phase electrical system, three ground detecting lamps are provided. One lamp goes dark and the others increase in brightness. When the test button is pushed, all lamps have equal illumination. You ... C. there are grounds on the lines with the bright lamps D. this is a normal condition

Last Answer : Answer: A

Description : If all three ground-detection lamps continue to burn at equal intensity after the test button is depressed and released, which of the listed conditions is indicated? A. No grounds exist B. All three phases are grounded C. The test switch is faulty D. The current transformers are shorted out

Last Answer : Answer: A

Description : On a switchboard, if all three ground detection lamps remain burning at half intensity when the test button is depressed, which of the listed conditions is indicated? A. No grounds exist. B. All three phases are grounded. C. The test switch is grounded. D. The current transformers are shorted.

Last Answer : Answer: A

Description : If all of the ground detection lamps burn with equal brilliance, whether the test button is depressed or released, then ___________. A. no grounds exist B. all phases are grounded C. all lamps show a ground D. all of the above

Last Answer : Answer: A

Description : The ground detection system, shown in the illustration for a low-voltage, threephase system has a ground in line 'A'. Therefore, lamp 'A' will burn ____________. EL-0009 A. dimly or be out, and lamps 'B' and ... and 'C' will burn dimly or be out D. brightly, and lamps 'B' and 'C' will burn normally

Last Answer : Answer: A

Description : The circuit illustrated represents a single phase AC ground detecting system. If a ground occurs on line 'B', which of the lamps will burn the brightest? EL-0008 A. X B. Y C. Both will be equal brightness. D. both will go out.

Last Answer : Answer: A

Description : In the illustrated ground detection system with a ground on phase A, if the switch is opened __________. EL-0009 A. lamp A will dim or go out depending on the severity of the ground B. all three ... lamp A will be brighter D. lamp A will start flickering if the ground is in an AC induction motor

Last Answer : Answer: B

Description : An AC generator panel is fitted with both synchronizing lamps and a synchroscope. When the synchroscope pointer reaches the noon position, one synchronizing light is bright and the other is dark. This ... sequence is incorrect C. the phase sequence is correct D. the generator breaker may be closed

Last Answer : Answer: B

Description : Multiple grounds have developed and were initialy indicated by the grounddetecting system as one ground. The FIRST step in locating the grounds is to _____________. A. examine the main bus bars ... no longer indicates any grounds C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : A current-carrying conductor makes accidental contact with a wiring conduit. This will be indicated by a _____________. A. low switchboard wattmeter reading B. high switchboard wattmeter reading C. darkened switchboard ground detecting lamp D. darkened switchboard synchronizing lamps

Last Answer : Answer: C

Description : A ground on a particular phase of a three-phase low voltage distribution system would be indicated by a _____________. A. high switchboard wattmeter reading B. low switchboard wattmeter reading C. dark or dim switchboard ground detecting light D. bright switchboard ground detecting light

Last Answer : Answer: C

Description : A ground in an electrical circuit outside the engine room _____________. A. cannot be detected under normal conditions B. is of no consequence to engineering personnel C. is indicated at the branch circuit breaker panel D. is indicated by the ground detecting lamps on the main switchboard

Last Answer : Answer: D

Description : The circuit illustrated represents a 2 wire DC ground detecting system. If the positive bus is grounded and the test button is pushed, which of the lamps will be brightest? EL-0008 A. X B. Y C. both will be equal brightness. D. both will go out.

Last Answer : Answer: C

Description : A ground is indicated by the ground-detecting system on the main electrical switchboard. The FIRST step in locating the actual ground is to _____________. A. close all circuit breakers in ... ground detection system indicates normal C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : A current-carrying conductor making electrical contact with a wiring conduit will be indicated by a _____________. A. high switchboard wattmeter reading B. totally dark switchboard ground detecting light C. low switchboard wattmeter reading D. all of the above

Last Answer : Answer: B

Description : When a fluorescent lamp has reached the end of its useful life, it should be replaced immediately, or the resultant flashing may _____________. A. blow the lamp's circuit breaker B. explode, ... fly in all directions C. short circuit the ballast transformer D. damage the starter and the ballast

Last Answer : Answer: D

Description : When paralleling two alternators the synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates the ____________. A. alternator voltages ... alternator is in phase with the bus voltage D. synchroscope pointer is defective or broken

Last Answer : Answer: C

Description : Four lamps are connected in parallel in a single circuit. If one of the lamp burns out, the others will _____________. A. all go out B. become dimmer C. burn with their original intensities D. become brighter

Last Answer : Answer: C

Description : The 'safe switch' of the winch controller shown in the illustration is operated _______________. EL-0102 A. through the master switch handle B. when heater circuit current is high C. by contactor coil 'FR' D. manually by the winch operator

Last Answer : Answer: D

Description : Accidental grounds in a shipboard electrical system must be repaired as soon as possible as they will ____________. A. result in immediate power outages B. damage circuit breakers C. appear on the ground detection system D. damage insulation and may cause outages

Last Answer : Answer: D

Description : When paralleling two alternators using three synchronizing lamps, the flickering of all three lamps becomes progressively slower and slower. This means the ______________. A. frequency of the incoming ... the bus D. terminal voltage of the incoming alternator is approaching that of the bus

Last Answer : Answer: A

Description : When a console indicating lamp burns out, attempts to renew it should not be made while maneuvering because _______________. A. the new lamp may be of a higher wattage and cause heat damage to the lens ... D. a socket/wiring fault may cause a ground or short circuit to shut down a vital function

Last Answer : Answer: D

Description : If 200w, 100 w and 60 w lamps connected in series with 230V AC , which lamp glow brighter? Each lamp voltage rating is 230V.

Last Answer :  Each bulb when independently working will have currents (W/V= I)  For 200 Watt Bulb current (I200) =200/230=0.8696 A  For 100 Watt Bulb current (I100) =100/230=0.4348 A  ... current through it. So minimum power dissipated across it as min current X equal Voltage across =s min power dissipation

Description : In the illustrated test, if the lamp fails to light on any of the three windings then _________. EL-0027 A. all three windings are grounded and the motor should be sent out for repair B. ... the motor controller and the controller should be checked D. the test should be redone at a higher voltage

Last Answer : Answer: C

Description : Which of the following represents a characteristic of an ungrounded electrical distribution system? A. Accidental contact between one line and ground does not cause an outage. B. Double ground faults on ... unnecessary. D. Accidental contact between one line and ground will always cause an outage.

Last Answer : Answer: A

Description : When paralleling two alternators, the synchronizing lamps remain lit as the synchroscope pointer approaches the 0°. This indicates the _____________. A. incoming alternator is running too fast B. alternator ... apart C. synchroscope is defective or broken D. alternator power factors are in phase

Last Answer : Answer: C

Description : Which of the following actions must be carried out before a voltage tester can be used to test the three line fuses to a three-phase motor? A. The fuses must be removed from the circuit. B. The ... disconnected and tagged. D. Nothing need be done as long as the motor is running under a light load.

Last Answer : Answer: B

Description : Attempting to parallel an AC generator which is out of phase with the bus will result in which of the following problems? A. The breaker should trip. B. The KVA will decrease. C. The synchronizing lamps will burn out. D. The power factor will be unitized.

Last Answer : Answer: A

Description : The vertical dotted line connecting the small circular symbols at coordinates '05L', '09L', '13L', '21L', '25L', etc., shown in the illustration, indicate that all _______________. EL-0100 A. contacts are ... board 'TB2' C. wires are grounded at both ends of the line D. wires have a common shield

Last Answer : Answer: B

Description : A current carrying conductor making an electrical contact with a wiring metal conduit is indicated by a _____________. A. low switchboard wattmeter reading B. reading of 1.0 on the power factor meter C. high switchboard voltmeter reading D. totally darkened switchboard ground-detecting light

Last Answer : Answer: D

Description : While paralleling two (2) AC generators using synchronizing lamps only, both lamps will go dark when the generators are ____________. A. running at the same speed B. grounded C. of the same polarity D. in phase

Last Answer : Answer: D

Description : The following air gap readings were obtained from a horizontally mounted, bilge pump, induction motor, equipped with sleeve bearings: FWD END-AFT END, Top .045 - .049, Right Side .045 - .047, Left ... the aft bearing. C. The forward bearing should be lowered. D. The aft bearing should be lowered.

Last Answer : Answer: A

Description : The following air gap readings were obtained from a horizontally mounted, bilge pump, induction motor, equipped with sleeve bearings: FWD END -AFT END, Top .045 - .049 , Right Side .045 - .047, Left ... the aft bearing. C. The forward bearing should be lowered. D. The aft bearing should be lowered.

Last Answer : Answer: A

Description : When troubleshooting motor controllers, a shorted relay or contactor coil is often indicated by _______________. A. a resistance reading of 'infinity' on an ohmmeter B. charred insulation and/or a blown ... of the coil's leads to ground D. a higher-than-normal voltage reading across the winding

Last Answer : Answer: B

Description : When using the test set-up shown in the illustration, the lighted lamp indicates the winding is ____________. EL-0027 A. grounded B. good C. open D. shorted

Last Answer : Answer: A

Description : When electrical cables penetrate watertight bulkheads, _______________. A. they should be grounded on either side of the bulkhead B. they must be bent to a radius of six diameters C. a watertight stuffing tube capable of accepting packing should be employed D. they should be secured by a clamp

Last Answer : Answer: C

Description : If the illustrated motor fails to start and gives a loud hum when the start button is pushed, the problem is ________. EL-0007 A. one of the phases to the motor is not energized because of ... electrical distribution system D. 'OL1' is open because of 'T1' overload causing the motor to single phase

Last Answer : Answer: A

Description : What current is required to light two 75 watt lamps and one 40 watt lamp when connected in series to a 120 volt power source? A. 0.161 amperes B. 0.631 amperes C. 1.583 amperes D. 6.199 amperes

Last Answer : Answer: C

Description : A Hybrid Vehicle equipped with push button start will enter the power ON mode but will not enter the ready to drive mode .No diagnostic trouble code are stored this could cause by a) The high voltage safety ... removed b) A failed brake on/off switch c) An empty fuel tank d) A disconnect 12v battery

Last Answer : b) A failed brake on/off switch

Description : If the three-phase motor, shown in the illustrated schematic diagram, is running in the forward direction, which of the following actions must occur before the motor will reverse rotation? EL-0011 A. Normally-closed ... 'L1' and 'L3' must be interchanged via the 'R' contacts. D. All of the above.

Last Answer : Answer: C

Description : The electrical schematic shown in the illustration indicates the lighting feeder circuit is _____________. EL-0014 A. three phase, 450 volt, and 60 cycle B. three phase, 120 volt, and 60 cycle C. single phase, 120 volt, and 60 cycle D. not specified

Last Answer : Answer: A

Description : What are the advantages and disadvantages of three dark lamps method of synchronizing?

Last Answer : Advantages: · The synchronous switch using lamps is inexpensive · Checking for correctness of the phase sequence can be obtained in a simple manner which is essential especially when the Alternator ... The frequency of the incoming Alternator in relation to the bus-bar frequency is not available.