Accidental grounds in a shipboard electrical system must be repaired as soon as possible as they will ____________. A. result in immediate power outages B. damage circuit breakers C. appear on the ground detection system D. damage insulation and may cause outages

1 Answer

Answer :

Answer: D

Related questions

Description : Which of the following represents a characteristic of an ungrounded electrical distribution system? A. Accidental contact between one line and ground does not cause an outage. B. Double ground faults on ... unnecessary. D. Accidental contact between one line and ground will always cause an outage.

Last Answer : Answer: A

Description : A ground is indicated by the ground-detecting system on the main electrical switchboard. The FIRST step in locating the actual ground is to _____________. A. close all circuit breakers in ... ground detection system indicates normal C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : When you are making a high potential test on a piece of repaired electrical machinery, a rise in leakage current indicates ____________. A. good insulation B. bad insulation C. high insulation power factor D. a high slot discharge factor

Last Answer : Answer: B

Description : In a three-phase electrical system, three ground detecting lamps are provided. One lamp goes dark and the others increase in brightness. When the test button is pushed, all lamps have equal illumination. You ... C. there are grounds on the lines with the bright lamps D. this is a normal condition

Last Answer : Answer: A

Description : Grounds occurring in electrical machinery as a result of insulation failure may result from _____________. A. deterioration through extended use B. excessive heat C. extended periods of vibration D. all of the above

Last Answer : Answer: D

Description : An accidental path of low resistance, allowing passage of abnormal amount of current is known as a/an ____________. A. open circuit B. short circuit C. polarized ground D. ground reference point

Last Answer : Answer: B

Description : Moisture absorbed in the windings or condensed on the surface of electrical machinery insulation ________. A. is good for long term preserving since most insulation is organic and contains some amount B. ... D. reduces the amount of current supplied or drawn by the machine so horsepower is limited

Last Answer : Answer: B

Description : When shipboard electrical distribution circuits are connected in parallel, additional parallel circuits will cause the total circuit resistance to _____________. A. increase, causing a drop in the line current B ... an increase in the line voltage D. decrease, causing an increase in the line current

Last Answer : Answer: D

Description : Unnecessary and frequent applications of varnish to the generator windings to repair defective insulation will result in ____________. A. heavy coatings of varnish interfering with heat dissipation B. ... of the rectifier assembly D. a built-up of varnish without changing generator operation

Last Answer : Answer: A

Description : A three-phase electrical system is equipped with ground detecting lamps. If one of the lamp goes dark and the other two burn normally before and after the test switch is operated, this indicates _______________. ... of the three phases D. the voltage to the dark lamp is less than that of the system

Last Answer : Answer: A

Description : In a three-phase electrical system, three ground detecting lamps are provided. If all three lamps REMAIN at half-brilliance when the ground detecting test switch is operated, ______________. A. there is a ... must be replaced C. there are no grounds present D. the light bulbs are of improper voltage

Last Answer : Answer: C

Description : If all of the ground detection lamps burn with equal brilliance, whether the test button is depressed or released, then ___________. A. no grounds exist B. all phases are grounded C. all lamps show a ground D. all of the above

Last Answer : Answer: A

Description : If all three ground-detection lamps continue to burn at equal intensity after the test button is depressed and released, which of the listed conditions is indicated? A. No grounds exist B. All three phases are grounded C. The test switch is faulty D. The current transformers are shorted out

Last Answer : Answer: A

Description : On a switchboard, if all three ground detection lamps remain burning at half intensity when the test button is depressed, which of the listed conditions is indicated? A. No grounds exist. B. All three phases are grounded. C. The test switch is grounded. D. The current transformers are shorted.

Last Answer : Answer: A

Description : Undervoltage trips are frequently installed on switchboard circuit breakers to trip ____________. A. out generators in the event of severe arcing or sparking B. out generators when there is reversal of power ... , but continues to run D. out generators when there is low voltage in the main circuit

Last Answer : Answer: D

Description : The removal of paint from electrical equipment, such as generators, should be cautiously undertaken because ____________. A. the mechanical shock of paint removal lessens the dielectric strength ... phase windings frequently become isolated from each other due to dust interference at the terminals

Last Answer : Answer: B

Description : When insulation failure produces a low resistance current path between two conductors, the resulting condition is known as ____________. A. an open B. a short circuit C. a ground D. a surge

Last Answer : Answer: B

Description : The part of the shipboard electrical system used to control the distribution of power to the branch circuits, is the _____________. A. bridge control panel B. disconnect links C. governor relay box D. main switchboard

Last Answer : Answer: D

Description : A breakable, mercury-filled thermometer should not be used in a lead-acid battery to measure electrolyte temperature, as an accidental breakage can cause ____________. A. severe sparking and explosions ... battery plates C. violent gassing at the positive plates D. corrosion on the battery terminals

Last Answer : Answer: A

Description : When working on electrical circuits containing large capacitors, in addition to deenergizing the circuit, which of the listed precautions should also be taken? A. Keep all radio equipment ... capacitor insulation resistance. C. Ground the capacitor terminals. D. Check capacitor circuit polarity.

Last Answer : Answer: C

Description : Julie is going on an extended trip for three weeks. She lives in a remote area where there are frequent electrical power outages which can last up to three or four days. Julie has quite a bit of food ... power, while another house may have no power. She won?t be able to have a neighbor chec -Riddles

Last Answer : One thing Julie could do is freeze a tray of ice-cubes, and turn the tray of ice upside down in her freezer. When she comes home, she should check the tray. If the ice cubes are still in the ... clean out the freezer. She will have to make a judgment call if the ice-cubes are only slightly thawed.

Description : The ground detection system, shown in the illustration for a low-voltage, threephase system has a ground in line 'A'. Therefore, lamp 'A' will burn ____________. EL-0009 A. dimly or be out, and lamps 'B' and ... and 'C' will burn dimly or be out D. brightly, and lamps 'B' and 'C' will burn normally

Last Answer : Answer: A

Description : The purpose of a short circuit forcing module (short time trip) installed in a branch line is to provide ____________. A. high speed clearance of low impedance short circuits in the branch B. ... C. isolation of short circuits by selective tripping of branch circuit breakers D. all of the above

Last Answer : Answer: D

Description : When a console indicating lamp burns out, attempts to renew it should not be made while maneuvering because _______________. A. the new lamp may be of a higher wattage and cause heat damage to the lens ... D. a socket/wiring fault may cause a ground or short circuit to shut down a vital function

Last Answer : Answer: D

Description : The shipboard general alarm system must receive its main source of power from _____________. A. a storage battery B. the emergency generator C. an auxiliary generator D. the ship's service generator

Last Answer : Answer: A

Description : Routine maintenance of dry-type transformers should include ____________. A. cleaning the windings, if accessible, with a vacuum cleaner or very low pressure air B. measuring and recording the winding ... . making sure that the units are close to bulkheads or corners to protect them from damage

Last Answer : Answer: A

Description : When an AC or a DC motor fails to start, the FIRST step in troubleshooting should be to check the ____________. A. motor windings for obvious opens B. motor controller leads for continuity C. fuse or circuit breaker D. motor controller leads for grounds

Last Answer : Answer: C

Description : An accidental path of low resistance which passes an abnormal amount of current is known as a/an _____________. A. polarized ground B. short circuit C. ground reference point D. open circuit

Last Answer : Answer: B

Description : A bridge used to locate accidental grounds on communications and power lines

Last Answer : Murray Loop

Description : A ground can be defined as an electrical connection between the wiring of a motor and its ____________. A. shunt field B. circuit breaker C. metal framework D. interpole

Last Answer : Answer: C

Description : Multiple grounds have developed and were initialy indicated by the grounddetecting system as one ground. The FIRST step in locating the grounds is to _____________. A. examine the main bus bars ... no longer indicates any grounds C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : Which of the spaces listed is defined as a 'location requiring an exceptional degree of protection' when considering the installation of shipboard electrical equipment? A. Machinery space B. Chart room C. Console room D. Accommodation space

Last Answer : Answer: A

Description : The cross-sectional area of shipboard electrical cable is expressed in _____________. A. millimeters B. gage numbers C. centimeters D. circular mils

Last Answer : Answer: D

Description : Electrical leads and insulation on a motor should be painted with ____________. A. heat-resisting acrylic B. heat-resisting aluminum C. insulating varnish D. insulating white lead

Last Answer : Answer: C

Description : When using a megohmmeter to test the dielectric strength of wire insulation, a continuous series of slight downscale kicks by the pointer is result of ____________. A. good insulation B. the ... dirty insulation C. the capacitance of the windings D. the dielectric-absorption effect of the insulation

Last Answer : Answer: B

Description : Insulation resistance of high voltage circuit breakers is more than (a) 1 mega ohms (b) 10 mega ohms (c) 100 mega ohms (d) 500 mega ohms

Last Answer : (c) 100 mega ohms

Last Answer : Insulation resistance of high voltage circuit breakers is more thanĀ 100 mega ohms.

Description : Low voltage releases as used in some shipboard motor starter and control equipment will have which of the following characteristics? A. They trip circuit contactors when the motor starts to overspeed. B. ... coil of the starter. D. They allow the motor to restart upon restoration of normal voltage.

Last Answer : Answer: D

Description : Which of the following statements is true regarding the illustrated circuit? El-0069 A. This full wave bridge should never be used aboard ship because the ground on lead 'A' will show on ... be direct current suitable for electronic circuits requiring voltage regulation. D. All the above are true.

Last Answer : Answer: B

Description : Motor controllers are seldom troubled by grounds because ________________. A. cabinet heaters always keep internal components dry B. special insulation is used on wire for vital circuits C. ... on controller panels greatly reduce vibration D. contactors and relays are mounted on nonconducting panels

Last Answer : Answer: D

Description : In an alternating current electrical system, a low system power factor is a direct sign of _____________. A. wasted energy B. efficient operation C. a short in the exciter field windings D. an excessive number of minor system grounds

Last Answer : Answer: A

Description : In the illustration, the component labeled 'G' _________. EL-0031 A. is lined with cardboard to maintain a moisture (electrolyte) barrier between cells B. is a one piece container with compartments for each individual cell C. must be UL approved for shipboard use D. can only contain one cell

Last Answer : Answer: B

Description : The air gap in an induction motor should be checked periodically with a feeler gage to detect ____________. A. rotor contact with the laminations B. changes in armature magnetic strength C. excessive bearing wear D. electrical damage to the rotor

Last Answer : Answer: C

Description : Which of the following statements concerning electrical cables is correct? A. Where they pass through watertight bulkheads, they should be fitted with watertight stuffing boxes. B. Electric cable coverings should ... , or glued in place where nonmetallic insulation is used. D. All of the above.

Last Answer : Answer: A

Description : A wattmeter is used to determine ____________. A. the power being consumed by electrical equipment B. partial circuit resistance C. current flowing in a circuit D. voltage existing between two points in a circuit

Last Answer : Answer: A

Description : A transformer in an electric circuit serves to ____________. A. generate its own electrical power B. transform electrical energy into mechanical energy C. increase or decrease circuit voltage as required D. convert AC current to DC current

Last Answer : Answer: C