A ground is indicated by the ground-detecting system on the main electrical switchboard. The FIRST step in locating the actual ground is to _____________. A. close all circuit breakers in the distribution panel until the ground detector indicates normal B. open the individual circuit breakers, one by one until the ground detection system indicates normal C. change over generators D. check each circuit with a megohmmeter

1 Answer

Answer :

Answer: B

Related questions

Description : Multiple grounds have developed and were initialy indicated by the grounddetecting system as one ground. The FIRST step in locating the grounds is to _____________. A. examine the main bus bars ... no longer indicates any grounds C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : A ground in an electrical circuit outside the engine room _____________. A. cannot be detected under normal conditions B. is of no consequence to engineering personnel C. is indicated at the branch circuit breaker panel D. is indicated by the ground detecting lamps on the main switchboard

Last Answer : Answer: D

Description : A ground on a particular phase of a three-phase low voltage distribution system would be indicated by a _____________. A. high switchboard wattmeter reading B. low switchboard wattmeter reading C. dark or dim switchboard ground detecting light D. bright switchboard ground detecting light

Last Answer : Answer: C

Description : A current-carrying conductor making electrical contact with a wiring conduit will be indicated by a _____________. A. high switchboard wattmeter reading B. totally dark switchboard ground detecting light C. low switchboard wattmeter reading D. all of the above

Last Answer : Answer: B

Description : A current carrying conductor making an electrical contact with a wiring metal conduit is indicated by a _____________. A. low switchboard wattmeter reading B. reading of 1.0 on the power factor meter C. high switchboard voltmeter reading D. totally darkened switchboard ground-detecting light

Last Answer : Answer: D

Description : A current-carrying conductor makes accidental contact with a wiring conduit. This will be indicated by a _____________. A. low switchboard wattmeter reading B. high switchboard wattmeter reading C. darkened switchboard ground detecting lamp D. darkened switchboard synchronizing lamps

Last Answer : Answer: C

Description : The part of the shipboard electrical system used to control the distribution of power to the branch circuits, is the _____________. A. bridge control panel B. disconnect links C. governor relay box D. main switchboard

Last Answer : Answer: D

Description : Undervoltage trips are frequently installed on switchboard circuit breakers to trip ____________. A. out generators in the event of severe arcing or sparking B. out generators when there is reversal of power ... , but continues to run D. out generators when there is low voltage in the main circuit

Last Answer : Answer: D

Description : The purpose of a main switchboard circuit breaker's reverse-power trip is to _____________. A. prevent main circuit overload B. protect the circuit breaker blowout coil C. prevent alternator motorization D. prevent low voltage tripout

Last Answer : Answer: C

Description : Accidental grounds in a shipboard electrical system must be repaired as soon as possible as they will ____________. A. result in immediate power outages B. damage circuit breakers C. appear on the ground detection system D. damage insulation and may cause outages

Last Answer : Answer: D

Description : The final step in testing a circuit for a ground involves the use of a megohmmeter. A grounded switch or cable will be indicated by a megohmmeter reading of ____________. A. 'zero' B. infinity C. steady in the high range D. unsteady in the low range

Last Answer : Answer: A

Description : On a switchboard, if all three ground detection lamps remain burning at half intensity when the test button is depressed, which of the listed conditions is indicated? A. No grounds exist. B. All three phases are grounded. C. The test switch is grounded. D. The current transformers are shorted.

Last Answer : Answer: A

Description : A 'dead front' switchboard is one _____________. A. without switches on it B. with insulated switches and no exposed terminals C. without circuit breakers D. without safety hand rails nor rubber mats

Last Answer : Answer: B

Description : A megohmmeter is connected to each end of an individual motor winding. A low ohm reading indicates ____________. A. an open coil B. a loose coil C. good continuity D. a dirty coil

Last Answer : Answer: C

Description : A switchboard ammeter indicates a reading slightly above 'zero' when the leads are disconnected, this is caused by _____________. A. mechanical misalignment of the meter pointer B. a poor ground for the meter case C. static electricity in the air D. capacitors inside the meter storing charges

Last Answer : Answer: A

Description : The purpose of the automatic bus transfer shown in the illustration is to ___________. EL-0014 A. stepdown voltage to the lighting distribution panel B. provide emergency power to ... emergency switchboard from the main switchboard D. provide overcurrent protection to the lighting distribution panel

Last Answer : Answer: B

Description : A three-phase electrical system is equipped with ground detecting lamps. If one of the lamp goes dark and the other two burn normally before and after the test switch is operated, this indicates _______________. ... of the three phases D. the voltage to the dark lamp is less than that of the system

Last Answer : Answer: A

Description : The electrical energy necessary to transmit a person's voice over a sound-powered telephone circuit is obtained from _____________. A. dry cell batteries B. the ship's service switchboard C. the emergency switchboard D. the speaker's voice

Last Answer : Answer: D

Description : The 24 volt DC bus on the emergency switchboard is used to supply power to the _____________. A. general alarm system B. gyrocompass power failure alarm system C. smoke detection system D. all of the above

Last Answer : Answer: D

Description : Automatic voltage regulators provided on switchboards function to _____________. A. regulate the AC load on the generator B. protect the switchboard from high voltage C. govern prime mover speed to control voltage D. vary the field excitation to the generators

Last Answer : Answer: D

Description : A flickering ground detection lamp on a DC system would indicate a _____________. A. multiple-ground condition in the distribution system B. ground in an armature coil of an operating machine C. ground in a motor accompanied with a short D. short between two adjacent bars of the generator commutator

Last Answer : Answer: B

Description : When a megohmmeter is being used to test insulation resistance, current leakage along the surface of the insulation is indicated by the megohmmeter pointer _____________. A. fluctuating around a ... slightly downscale as voltage is applied D. continually rising as the test voltage is applied

Last Answer : Answer: C

Description : When a megohmmeter is being used to test insulation resistance, current leakage along the surface of the insulation is indicated by the megohmmeter's pointer _____________. A. dipping toward ... kicking slightly down scale as voltage is applied D. fluctuating around a constant resistance reading

Last Answer : Answer: C

Description : When using a megohmmeter to test insulation, good insulation will be indicated by _____________. A. slight kicks of the needle down scale B. a downward dip followed by a gradual climb to the true resistance ... C. a gradual rise in the pointer reading at the outset D. the initial dip of the pointer

Last Answer : Answer: B

Description : A grounded switch or cable will be indicated by a megohmmeter reading of _____________. A. infinity B. 'zero' C. being unsteady in the high range D. being unsteady in the low range

Last Answer : Answer: B

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving fast in the clockwise direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... at any pointer position D. the same as the bus frequency but out of phase with it

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving in the fast direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... the same as the bus frequency and the circuit breaker may be closed at any pointer position

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer is revolving in the slow direction. This indicates that the frequency of the incoming machine is _____________. A. higher than ... same as the bus frequency, and the circuit breaker may be closed at any pointer position

Last Answer : Answer: B

Description : Which of the following represents a characteristic of an ungrounded electrical distribution system? A. Accidental contact between one line and ground does not cause an outage. B. Double ground faults on ... unnecessary. D. Accidental contact between one line and ground will always cause an outage.

Last Answer : Answer: A

Description : In a three-phase electrical system, three ground detecting lamps are provided. One lamp goes dark and the others increase in brightness. When the test button is pushed, all lamps have equal illumination. You ... C. there are grounds on the lines with the bright lamps D. this is a normal condition

Last Answer : Answer: A

Description : Which of the following is/are true concerning electric power operated watertight door systems? A. Each motor driven door must use the main bus as its source of power. B. Each distribution panel for ... to permit quick activation of the system. D. Each system must have a separate branch circuit.

Last Answer : Answer: D

Description : Before any work on electrical or electronic equipment is performed, which of the following precautions should be carried out? A. De-energize the applicable switchboard bus. B. Bypass the interlocks. C. ... supply circuit breaker in the open position. D. Station a man at the circuit supply switch.

Last Answer : Answer: C

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : A switchboard, for a AC electrical distribution system, will be provided with which of the following components? A. Frequency meter. B. Ammeter C. Voltmeter D. All of the above

Last Answer : Answer: D

Description : Motor name plate data includes '°°C rise'. This indicates the _____________. A. actual running temperature of the winding from no load to full load B. permissible temperature rise ... above normal full load operating temperature D. maximum allowable temperature rise for continuous no load service

Last Answer : Answer: B

Description : A three-phase alternator is developing 300 amps, with a 0.8 power factor, at 450 volts. The true indicated power on the kilowatt meter, located on the main switchboard, will be ____________. A. 133 kw B. 155 kw C. 187 kw D. 212 kw

Last Answer : Answer: C

Description : Which of the following should be the FIRST step in removing a generator from parallel operation? A. Trip the generator off the switchboard. B. Turn off all electrical equipment. C. Remove the load from the 'off going' generator. D. Increase the cycles of the generator staying on the line.

Last Answer : Answer: C

Description : The electrical energy necessary to power a sound-powered telephone's small vibrating bell is obtained from _________. A. the emergency batteries for the general alarm B. each station's hand-cranked generator C. the emergency switchboard D. normal 115 volt DC supplies

Last Answer : Answer: B

Description : If all three ground-detection lamps continue to burn at equal intensity after the test button is depressed and released, which of the listed conditions is indicated? A. No grounds exist B. All three phases are grounded C. The test switch is faulty D. The current transformers are shorted out

Last Answer : Answer: A

Description : The electrical schematic shown in the illustration indicates the lighting feeder circuit is _____________. EL-0014 A. three phase, 450 volt, and 60 cycle B. three phase, 120 volt, and 60 cycle C. single phase, 120 volt, and 60 cycle D. not specified

Last Answer : Answer: A

Description : When a megohmmeter is used to test the dielectric strength of wire insulation, the initial dip of the pointer toward 'zero' is caused by _____________. A. good insulation B. the leakage of ... of dirty insulation C. the capacitance of the circuit D. the dielectric absorption effect of the insulation

Last Answer : Answer: C